5.3.Interpreting Sentry-Sensor Controls

A Sentry-Sensor control presents data for one single sensor one single Sentry. The color changes to report the status, and the control displays the gas concentration, tag name and units.

Red: Sensor concentration is above the alarm set point.

Orange: Sensor concentration is above warning set point.

 

A warning is

 

An alarm is

active and there

 

is no alarm.

Status is normal.

active.

 

 

 

 

 

 

 

 

There

is

a

 

 

Sensor

Tag

 

problem

 

with

 

 

 

this sensor.

 

 

 

 

Name

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor

 

 

 

 

 

 

 

 

concentration

Gas

 

 

 

 

 

 

 

engineering units.

 

 

 

 

 

 

 

concentration.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensor Tag Name

If the sensor tag name found in the Sentry is blank then the sensor tag

 

 

 

name allocated during construction of the web page is displayed.

 

 

 

 

 

 

 

 

Sensor Engineering

The engineering units as configured in the Sentry. If none are configured

 

 

 

Units

 

in the Sentry, then none are shown.

 

 

 

 

 

Sensor

 

If the value is less than 10 then one decimal point is shown.

 

 

 

 

Concentration

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the Sentry-Sensor controls report ‘offline’

 

 

 

 

 

 

or “Format Err” then the problem indicated

 

 

 

 

 

 

does not relate to the state of the Sensor but

 

 

 

 

 

to the transfer of new data to the web page.

 

 

 

 

 

There are a number of possible causes

 

 

 

 

 

 

 

 

 

 

 

 

described in the Trouble Shooting section.

 

 

 

 

 

If this happens once, after the WebServer

 

 

 

 

 

has been reset then ignore this error.

 

 

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 16
Contents Sentry LANServer Applicability & EffectivityTable of Contents LED1 Product Description General FeaturesOperation Sentry Firmware Version ConnectionsModel 5391-01 LANServer with 2-4 Sentry Controllers Page Quick Start LANServer Terminology Quick StartSetting Browser Security Settings for ActiveX controls Browser Security SettingsActiveX Controls and Security T12017-SentryLANServerUsersManual Customize the settings Setting the Browser Privacy Settings for Cookies Cookies and Browser SecuritySpecify the WebServer IP address and then click Allow T12017-SentryLANServerUsersManual Interpreting Zone Buttons T12017-SentryLANServerUsersManual Interpreting Sentry-Sensor Controls Interpreting Sentry -Combo Controls Interpreting Sentry Alarms Understanding the Alarm Table Colors Acknowledging AlarmsClick Retry to clear the dialog Interpreting Sentry Events Event Report TypesPage Understanding the Events What happens if Event Logging is disabled?Events Page and the Date / Time Potential Problems with Event Logging File Problems Space ProblemsEvent File Maintenance Limited number of event recordsManaging Sentry Events Uploading Potential Problems with an Upload How Event Time Stamps are reported Manual uploadInterpreting the Sentry Face Plate LED Current sensor number Gas Concentration for current sensor Sensor One User at a Time ActiveX Not InstalledLANServer Driver Ver .05f Required Description How the Control OperatesBackup File Contents Problems with Calibration Backup ControlInterpreting Analog, Text and LED controls Analog Controls Text ControlsLED Controls Using the LANServer to allow customers to upload files Appendix 1.3. Page login.htm not found Appendix 1.2. Objects report ‘Not Found’Appendix 1.6. Buttons Display in White Appendix 1.7. Cookie LengthAppendix 1.9. LANServer Configuration LED 40159,8 40977,8 40985,8Appendix 2. LANServer Error Messages FYIWEB#13 Err Not enough Space for alarm WEB#15 FYI ASO Max Limited to %d Web#68 FYI. Http Appendix 3. WinSock Error Messages Wsaeconnreset WsaenetresetWsaeafnosupport WsaealreadyWsaefault WsaedestaddrreqWsaehostdown WsaehostunreachWsaeisconn WsaemfileWsaemsgsize WsaenetdownWsaenotconn WsaenotsockWsaeopnotsupp WsaepfnosupportWsaeshutdown WsaesocktnosupportSockraw WsaetimedoutWsainvalidparameter WsainvalidproctableWsainvalidprovider WsaioincompleteWsanotinitialised WsanodataWsanorecovery HostsWsaproviderfailedinit WsasyscallfailureWINSOCK.DLL WsavernotsupportedWsaediscon WsaoperationabortedAppendix 4.2. LED1 Appendix 4. FieldServer ActiveX Controls Appendix 4.1. Ana1Appendix 4.3. Char1 Appendix 4.4. Limitations and Supported Environments Appendix 5. General Appendix 5.1 .1 Browser Caching This page Intentionally Left Blank