5.11.1.Troubleshooting the Sentry FacePlate Screen

5.11.1.1.Communication Problems

The Sentry Faceplate can report a ‘Timeout’ for any one of the following reasons.

Sentry configured with an IP address that does not match the LANServer.

LANServer is not running.

It cannot obtain the data it requires from the LANServer. Each LANServer is expected to have 5 Data Arrays for each Sentry that it is connected to (DA_V_SENxxx, DA_U_SENxxx, DA_T_SENDxxx, DA_R_SENxxx, DA_FP_SENDxxx). If these data arrays do not exist then the faceplate will not be able to read data correctly.

If is reading data from the LANServer but the data is all zeros. This happens when the LANServer cannot read data from the Sentry’s.

It is reading data but network congestion is making the data reading intermittent and the responses take too long to reach the faceplate.

The Ethernet port used to communicate with the LANServer is blocked by the router.

The faceplate uses a protocol called SMT to communicate with the LANServer. If the PC is connected to the LANServer’s N2 adapter then the protocol has to be enabled. This concern doesn’t apply to N1 because it is enabled by default.

5.11.1.2.One User at a Time

Only one browsing PC may use the Sentry Faceplate keys at a time. As soon as someone pushes a key using one PC, the LANServer starts a timer. Key pushes from other browsing PC’s are ignored until the timer has expired. Currently the setting is 60 seconds.

The control reports this message: “Someone else is actively controlling the Sentry. The user can continue to monitor the device but attempts to control the device will be ignored. Try again later. This message is only printed once.”

5.11.1.3.LANServer Driver Ver. 1.05f Required

Different versions of the Sentry Faceplate require different versions of the LANServer. To ensure compatibility the Sentry faceplate checks the LANServer version number (The user can do this by using RUINET, going to the error screen, pushing the V key and looking for the version number of the HTTP driver.). If the versions are incompatible this is reported in the Lower Display area of the faceplate.

5.11.1.4.ActiveX Not Installed

The ActiveX Control must be installed on the browsing PC before it can be viewed or used. If it hasn’t been installed it will appear as an empty frame with a red ‘X’ in the top left corner, as illustrated below.

Installation is a formal process. The following lists are possibilities;

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-2269 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 31
Contents Applicability & Effectivity Sentry LANServerTable of Contents LED1 Product Description General FeaturesOperation Connections Sentry Firmware VersionModel 5391-01 LANServer with 2-4 Sentry Controllers Page Quick Start Quick Start LANServer TerminologySetting Browser Security Settings for ActiveX controls Browser Security SettingsActiveX Controls and Security T12017-SentryLANServerUsersManual Customize the settings Cookies and Browser Security Setting the Browser Privacy Settings for CookiesSpecify the WebServer IP address and then click Allow T12017-SentryLANServerUsersManual Interpreting Zone Buttons T12017-SentryLANServerUsersManual Interpreting Sentry-Sensor Controls Interpreting Sentry -Combo Controls Interpreting Sentry Alarms Acknowledging Alarms Understanding the Alarm Table ColorsClick Retry to clear the dialog Event Report Types Interpreting Sentry EventsPage Understanding the Events What happens if Event Logging is disabled?Events Page and the Date / Time Limited number of event records Potential Problems with Event Logging File ProblemsSpace Problems Event File MaintenanceManaging Sentry Events Uploading How Event Time Stamps are reported Manual upload Potential Problems with an UploadInterpreting the Sentry Face Plate LED Current sensor number Gas Concentration for current sensor Sensor One User at a Time ActiveX Not InstalledLANServer Driver Ver .05f Required How the Control Operates DescriptionProblems with Calibration Backup Control Backup File ContentsInterpreting Analog, Text and LED controls Text Controls Analog ControlsLED Controls Using the LANServer to allow customers to upload files Appendix 1.2. Objects report ‘Not Found’ Appendix 1.3. Page login.htm not foundAppendix 1.7. Cookie Length Appendix 1.6. Buttons Display in White40159,8 40977,8 40985,8 Appendix 1.9. LANServer Configuration LEDFYI Appendix 2. LANServer Error MessagesWEB#13 Err Not enough Space for alarm WEB#15 FYI ASO Max Limited to %d Web#68 FYI. Http Appendix 3. WinSock Error Messages Wsaealready WsaeconnresetWsaenetreset WsaeafnosupportWsaehostunreach WsaefaultWsaedestaddrreq WsaehostdownWsaenetdown WsaeisconnWsaemfile WsaemsgsizeWsaepfnosupport WsaenotconnWsaenotsock WsaeopnotsuppWsaetimedout WsaeshutdownWsaesocktnosupport SockrawWsaioincomplete WsainvalidparameterWsainvalidproctable WsainvalidproviderWsanodata WsanotinitialisedWsasyscallfailure WsanorecoveryHosts WsaproviderfailedinitWsaoperationaborted WINSOCK.DLLWsavernotsupported WsaedisconAppendix 4.2. LED1 Appendix 4. FieldServer ActiveX Controls Appendix 4.1. Ana1Appendix 4.3. Char1 Appendix 4.4. Limitations and Supported Environments Appendix 5. General Appendix 5.1 .1 Browser Caching This page Intentionally Left Blank