SMC Networks EX9-AC002-3 Input Block Model Indication Method, Input Block Model indication method

Page 11

Input Block Model Indication Method

Input Block

Model indication method

EX250 IE

Block type

1

Input points : 2, M12 connector (2pcs.)

2

Input points : 4,

M12 connector (2pcs.)

3

Input points : 4,

M8 connector (4pcs.)

Part Names

EX250-IE1

EX250-IE2

EX250-IE3

Tie-rod (2 pcs.)

Accessory

No.

Part names

Application

1

Input equipment connector

Connects the input equipment such as sensor, etc. Note1

 

 

 

2

Operation display LED

Displays the power source and input status. Note2

 

 

 

Note1 : For wiring method, refer to subsection "Wiring" (page 20) of section "Input Block" in this manual.

Note2 : For display and setting, refer to "Display/Setting" (page 22) in section "Input Block" in this manual.

Dimensions ( unit : mm )

EX250-IE1/2

 

EX250-IE3

 

21

21

 

 

 

 

 

 

 

 

 

 

72.6

67.4

59.8

59.8

Mounting/Installation

Refer to subsection "Mounting/Installation" (page 7) in this manual.

Specifications

Applicable sensor

Current source type(PNP input)

Current sink type(NPN input) *Selected with a switch.

 

 

 

 

Rated voltage

24VDC (It can have a voltage drop for 1V at max. to the

power source voltage of the SI Unit.)

 

 

 

 

Logical "1" input voltage VH

11 to 30V

Logical "0" input voltage VL

-3 to +5V

Logical "1" input current IH

8mA Typ.

Connection of 2-wire sensor

Possible

Logical "1" input current IL

Max.2.5mA

Input delay time

3msec. Typ.

Supply current to sensor

Max. 120mA / Input Block

Connector type of the input

IE1/2

M12 connector (4 pin, plug or 5 pin, plug)

equipment

 

 

IE3

M8 connector (3 pin, plug)

 

 

 

18

19

Image 11
Contents Reduced wiring system Contents Otherwise injury can result Do not operate beyond specification rangeOtherwise injury or failure can result Otherwise accident caused by malfunction can resultProduct Summary SafetySystem configuration general Part Names Dimensions unit mmMounting/Installation SI Unit Model Indication MethodPosition of End Plate Mounting/InstallationLayout of the EX9 series Output Block / Power Block Layout of the Input BlockMapping SpecificationsBasic specifications Higher-level busCable connection WiringCommunication wiring Power supply wiringSettings for display Display/SettingWiring Connecting one or two power supplies to SI UnitDefault settings Display/SettingSwitch setting Block type EX250-IE1 EX250-IE2 EX250-IE3 Tie-rod 2 pcs AccessoryInput Block Model Indication Method Input Block Model indication methodEX250-IE1/2/3 Input wiring Cable wiringInput connector pin layout EX250-IE1 M12 connector, 5 pin, SocketEX250-IE1 EX250-IE2/IE3 Power BlockDisplay Output BlockTie-rod 2 pcs Waterproof cap Accessory For socket1 pc Part Names Dimensions unit mmOutput Block Power Block Pin alignment and connection drawing of the Output Cable SpecificationOutput wiring Cable wiring Output connector pin layoutEX9-PE1 pin layout Power supply wiring Power BlockPower Cable Power Block Option DisplayOverall system TroubleshootingOption Green flashing Check the data rate and address TroubleshootingCheck the wiring and pin number EtherNet/IP compatible communication