Wiring
Communication wiring
Connect the Ethernet Communication Cable to the communication connector of SI Unit.
Power supply wiring
Connect the Power Supply Cable to the power supply connector of SI Unit.
When selecting the power supply, refer to "Handling precautions" (page 3) in this manual.
Cable connection
Aligning the key groove with the communication connector
Tighten the lock nut on cable side by turning it clockwise by hand.
Confirm that the connector portion does not move.
12
43
Cable connection
Aligning the key groove with the power supply connector (plug) of
SI Unit, plug the Power Supply Cable (socket).
Tighten the lock nut on cable side by | M3 Earth terminal |
turning it clockwise by hand. |
|
Confirm that the connector portion |
|
does not move. |
|
Pin layout and connection diagram of Ethernet Communication Cable
M12 | 6.7 | RJ45 |
|
|
47.3 | 2000 | 45 |
Model No. :
|
| Terminal No. | Cable core wire external color | |
2 | 1 | 1 | ||
| ||||
|
|
| 2 | |
|
| +Tx 1 | 1 White/Orange 43 |
Pin layout and connection diagram of power supply connector cable for (unit : mm)
M12 |
| 6 |
|
14.9 | 18 |
|
|
34 | 30 | 5 | |
| 48 |
| 50 |
Model No. : EX500-AP -S
|
| +Rx 2 | 2 | Orange | 5 |
3 | 4 | - Tx 3 | 3 | White/Green | 6 |
|
| - Rx 4 | 4 |
| 7 |
|
|
| 5 |
| 8 |
Pin assignment of |
| Green | Pin assignment of | ||
| 6 | ||||
plug connector |
| 7 |
| plug connector | |
|
|
| 8 |
|
|
|
| Wiring diagram | Shield |
|
Cable specifications
Pin No. | Cable color: Signal name |
1Brown : 24VDC
2White : 0V (for solenoid valves/output)
3Blue : 24VDC 10% (for input and control)
4Black : 0V (for input and control)
5Grey : Earth
NOTE
1 2
5
43
Socket connector pin layout
Core wire | AWG 26 |
|
|
Sheath color | Blue green |
|
|
Ground the Earth terminal with the ground resistance at 100 ohm or less. Make the pin No.5 of
the power supply connector ungrounded, and ground at one point.
12 | 13 |