SMC Networks EX250 and EX9-AC Series Comprehensive Manual

Page 9

Wiring ( continued )

Connecting one or two power supplies to SI Unit.

Both single power supply and two power supply systems can be adopted, however, the wiring shall be made separately (for solenoid valves/output and for input and control) for either system.

Display/Setting

Settings for display

SI

A. Two power supplies

Brown : 24VDC (for solenoid valves/output)

White : 0V (for solenoid valves/output)

2

1

SOL PWR MS NS

1

24VDC

24VDC

Grey : Earth

Blue : 24VDC (for input and control)

Black : 0V (for input and control)

Cable Part No. : EX500-AP -S

 

5

3

4

Power supply

connector

0

SETTINGS

B. Single power supply

 

 

 

 

 

 

 

 

 

 

 

 

Brown : 24VDC (for solenoid valves/output)

 

 

 

 

 

 

 

 

 

 

 

 

White : 0V (for solenoid valves/output)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Grey : Earth

24VDC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blue : 24VDC (for input and control)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Black : 0V (for input and control)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cable Part No. : EX500-AP -S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

5

34

Power supply

connector

Display

 

Contents

SOL

OFF

The power supply for solenoids is insufficient

 

 

Green light ON

The power supply for solenoids is normal

 

 

 

 

PWR

OFF

The power supply for input and control is insufficient

 

 

Green light ON

The power supply for input and control is normal

 

 

 

 

 

OFF

The power supply for control is OFF

 

 

 

 

Green light ON

Operating normally

 

 

 

MS

Green flashing

Setting error (Device has not been configured)

 

 

 

 

Red flashing

Recoverable internal error

 

 

 

 

Red light ON

Unrecoverable internal error

 

 

 

 

OFF

The power supply for control is OFF or IP address not set

 

 

 

 

Green flashing

EtherNet/IP-level communication not established

 

 

 

NS

Green light ON

Multiple EtherNet/IP-level communications established

 

 

 

 

Red flashing

Multiple EtherNet/IP-level communications time out

 

 

 

 

Red light ON

IP address duplicated

 

 

 

14

15

Image 9
Contents Reduced wiring system Contents Otherwise injury or failure can result Do not operate beyond specification rangeOtherwise accident caused by malfunction can result Otherwise injury can resultSafety System configuration generalProduct Summary Mounting/Installation Dimensions unit mmSI Unit Model Indication Method Part NamesLayout of the EX9 series Output Block / Power Block Mounting/InstallationLayout of the Input Block Position of End PlateBasic specifications SpecificationsHigher-level bus MappingCommunication wiring WiringPower supply wiring Cable connectionWiring Display/SettingConnecting one or two power supplies to SI Unit Settings for displayDisplay/Setting Switch settingDefault settings Input Block Model Indication Method EX250-IE1 EX250-IE2 EX250-IE3 Tie-rod 2 pcs AccessoryInput Block Model indication method Block typeInput connector pin layout Input wiring Cable wiringEX250-IE1 M12 connector, 5 pin, Socket EX250-IE1/2/3Display Power BlockOutput Block EX250-IE1 EX250-IE2/IE3Part Names Dimensions unit mm Output Block Power BlockTie-rod 2 pcs Waterproof cap Accessory For socket1 pc Output wiring Cable wiring SpecificationOutput connector pin layout Pin alignment and connection drawing of the Output CablePower supply wiring Power Block Power Cable Power BlockEX9-PE1 pin layout Option DisplayTroubleshooting OptionOverall system Check the wiring and pin number TroubleshootingEtherNet/IP compatible communication Green flashing Check the data rate and address