Liebert Series 600T Power Wiring Terminals Factory Supplied, Torque Specifications

Page 28

 

Table 1

 

Power Wiring Terminals - Factory Supplied

UPS

CONNECTION

MODULE

TYPE

65 & 80 kVA

Bypass input wiring is top-entry, to busbars on top of the circuit breaker. Rectifier

input wiring is top-entry, directly to lugs on top of the input circuit breaker. DC link

 

 

and critical bus output connections are top entry, to frame-mounted lugs. A bottom-

 

entry access plate is standard, to enable the installer to pull AC cables and control

 

wiring through the module to the connections on top.

100-225 kVA

For “SpaceSaver” modules in the 48” frame, rectifier and bypass input wiring is top-

 

entry, directly to lugs on top of their respective circuit breakers. DC link and critical

 

bus output connection are top entry, to frame-mounted lugs.

 

Standard modules with top-and-bottom entry have access plates and a wireway on

 

the right side of the modules. All power connections are to bus bars in the wireway.

 

 

Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 and associated notes of the National Electrical Code (NFPA 70).

Use commercially available solderless lugs for the wire size required for your application. Refer to Table 3. Connect wire to the lug using tool and procedure specified by the lug manufacturer.

Table 2

Torque Specifications

 

NUT AND BOLT COMBINATIONS

 

 

 

 

BOLT SHAFT

GRADE 2

 

ELECTRICAL CONNECTIONS

SIZE

STANDARD

 

with Belleville Washers

 

Lb - in

 

N-m

 

Lb-in

 

 

 

N-m

1/4

53

 

 

6.0

 

 

46

 

 

 

 

5.2

5/16

107

 

 

12

 

 

60

 

 

 

 

6.8

3/8

192

 

 

22

 

 

95

 

 

 

 

11

1/2

428

 

 

22

 

 

256

 

 

 

29

 

 

 

 

 

 

 

 

 

CIRCUIT BREAKERS

 

 

 

TERMINAL BLOCK

 

WITH COMPRESSION LUGS

 

 

 

COMPRESSION LUGS

(For Power Wiring)

 

 

 

(For Control Wiring)

 

WIRE SIZE

Lb-in

 

 

N-m

 

AWG WIRE

 

Lb-in

 

N-m

OR

 

 

 

 

 

SIZE

 

 

 

 

 

RANGE

 

 

 

 

 

OR RANGE

 

 

 

 

 

#6 - #4

100

 

 

11

 

#22 -#14

 

3.5 to 5.3

 

0.4 to 0.6

#3 - #1

125

 

 

14

 

 

 

 

 

 

 

 

1/0 - 2/0

150

 

 

17

 

 

 

 

 

 

 

 

3/0 - 200 MCM

200

 

 

23

 

 

 

 

 

 

 

 

250 - 400 MCM

250

 

 

28

 

 

 

 

 

 

 

 

500 - 700 MCM

300

 

 

34

 

 

 

 

 

 

 

 

22

Installation Manual

Image 28
Contents Series 600T UPS Page Installation Manual Table of Contents Figures Iii Page Installation Installation Considerations External Inspections Internal InspectionsBattery Safety Precautions Equipment LocationBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Configuring Your Neutral and Ground Connections Open-Rack BatteriesGrounding Liebert Series 600T UPS, 65-225 kVA, Single Module Electrode Preferred Grounding Configuration, 208 VAC input and output Grounding Local Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Grounding Configuration, Battery Systems Preferred Battery Cabinet Grounding ConfigurationWiring Considerations Power WiringTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Control Wiring Battery WiringWiring Connections Specific ConnectionsWiring Inspection Power Wiring Terminals Factory Supplied Torque SpecificationsField-Supplied Lugs ONE-HOLE LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA Liebert Series 600T UPS, 65-225 kVA, Single Module Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Line-up Detail, 65 & 80 kVA with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA with 3-Breaker MBC Installation Manual Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS Terminal Details, 150 & 225 kVA Standard SMS Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA Installation Manual Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 Liebert Series 600T UPS, 65-225 kVA, Single Module Company Behind the Products Technical Support
Related manuals
Manual 128 pages 43.69 Kb