Liebert Series 600T installation manual Wiring Considerations, Power Wiring

Page 21

8. WIRING CONSIDERATIONS

8.1. Power Wiring

Refer to Site Planning Data (Appendix A) and the installation drawings. Determine AC currents for your system based on kVA, kW, voltage, and options. Also refer to equipment nameplate for the model number, rating, and voltage. For wire termination data, refer to Tables 1-3.

1.Power wiring -- rectifier input, bypass input, UPS output, and battery cables -- must be run in individual, separate conduit or cable tray. Refer to the Outline and Terminal Details drawings (Figures 11-13 and 35-39) for location of the various power connections within the UPS.

CAUTION

Power and control wiring must be separated!

2.Observe local, state and national electrical codes. Verify utility power and its overcurrent protection rating will accommodate the UPS input rating, including battery recharging.

3.A safety ground wire must be run from building ground to ground point in the UPS Module Cabinet, the Battery Cabinet and the Power-Tie™ switchgear cabinet. See Sections 7.1 through 7.7. The grounding conductor shall comply with the following conditions of installation:

a.The insulated grounding conductor must be sized in accordance with the NEC and local codes. It must be green (with or without yellow stripes) and be installed as part of the branch circuit that supplies the unit or system.

b.The grounding conductor described above is to be grounded to earth at the service equip- ment or, if supplied by a separately derived system, at the supply transformer or motor- generator set in accordance with the instructions in Section 7 of this Manual.

c.The attachment-plug receptacles in the vicinity of the unit or system are all to be of a grounding type, and the grounding con- ductors serving these receptacles are to be

connected to earth ground at the service equipment.

4.Observe clockwise phase rotation of all power wiring. Phase A leads Phase B leads Phase C. A qualified electrician should check the phase rotation.

5.Power cables must be rated for less than 2 volts line drop at maximum rated system current.

6.Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 and associated notes of the National Electrical Code (NFPA 70) reprinted on page 24 of this manual.

CAUTION

The weight of power cables must be adequately supported to avoid stress on bus bars and lugs. The following restraining method is recommended to both to support cable weight and control cable movement during external fault conditions: Wrap line cables together at 6 inches and 12 inches from the terminals with 5 wraps of 3/8 inch nylon rope or equivalent (tensile strength of 2000 pounds). Support remainder of cable with 5 wraps every 6 inches or 1 wrap every 1 inch.

7.If site equipment includes a backup generator and automatic transfer switch(es), consult the manufacturers of those devices for information on sizing and interfacing to the UPS system.

8.The installing contractor can remove the access plates from the top left or top right sides of the UPS in order to cut entry holes for conduit. For units with bottom-entry cable access, there is a separate (third) access plate in the base of the unit, under the cable access wireway.

CAUTION

After cutting holes in the access plates, be certain that no foreign matter (metal shavings, sawdust, insulation or wire fragments, etc.) remains inside the UPS. Likewise be certain to block any “extra” holes in the plates through which foreign matter could later enter the UPS.

Liebert Series 600T UPS, 65-225 kVA, Single Module

15

Image 21
Contents Series 600T UPS Page Installation Manual Table of Contents Figures Iii Page Installation Installation Considerations Internal Inspections External InspectionsEquipment Location Battery Safety PrecautionsBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Open-Rack Batteries Configuring Your Neutral and Ground ConnectionsGrounding Liebert Series 600T UPS, 65-225 kVA, Single Module Electrode Preferred Grounding Configuration, 208 VAC input and output Grounding Local Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Battery Cabinet Grounding Configuration Preferred Grounding Configuration, Battery SystemsPower Wiring Wiring ConsiderationsTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Battery Wiring Control WiringSpecific Connections Wiring ConnectionsWiring Inspection Torque Specifications Power Wiring Terminals Factory SuppliedONE-HOLE Lugs Field-Supplied LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA Liebert Series 600T UPS, 65-225 kVA, Single Module Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Line-up Detail, 65 & 80 kVA with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA with 3-Breaker MBC Installation Manual Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS Terminal Details, 150 & 225 kVA Standard SMS Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA Installation Manual Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 Liebert Series 600T UPS, 65-225 kVA, Single Module Technical Support Company Behind the Products
Related manuals
Manual 128 pages 43.69 Kb