Liebert Series 600T installation manual

Page 82

Series 600T Single Module Systems

600 Volt Input

 

 

 

 

 

 

 

Inverter Or

Required

Maximum

Maxmum

 

 

Floor

 

 

AC

 

 

Rectifier AC

Bypass AC

Battery

Battery

Heat

 

 

Loading

 

 

Output

 

 

Input

Output

Discon-

Current At

Dissipa-

 

Approx.

Lb./Sq.ft

UPS Rating

Voltage

Options

Current

Current

nect

End Of

tion

Dimensions

Weight

(Concen-

 

 

 

Input

Input

 

 

 

 

Rating

Discharge

BTU/Hr

Inches

LB.

trated

kVA

kW

VAC

Filter

Xformer

Nom

Max

Nom

Max

Amperes

Amperes

Full Load

(WxDxH)

(unpacked)

Loading)

65

52

600

NO

NO

63

79

63

78

150

140

12,340

34x32x68

1,600

300

65

52

600

YES

NO

58

73

63

78

150

140

12,950

34x32x68

1,650

309

65

52

600

NO

YES

64

80

63

78

150

140

15,435

34x32x68

2,200

413

65

52

600

YES

YES

59

74

63

78

150

140

16,065

34x32x68

2,250

422

65

52

208

NO

NO

63

79

180

226

150

141

13,355

34x32x68

1,800

338

65

52

208

YES

NO

59

73

180

226

150

141

13,975

34x32x68

1,850

347

65

52

208

NO

YES

64

80

180

226

150

141

16,490

34x32x68

2,400

450

65

52

208

YES

YES

60

75

180

226

150

141

17,125

34x32x68

2,450

459

80

64

600

NO

NO

77

97

77

96

175

173

15,185

34x32x68

1,800

338

80

64

600

YES

NO

72

90

77

96

175

173

15,940

34x32x68

1,850

347

80

64

600

NO

YES

79

98

77

96

175

173

18,995

34x32x68

2,430

456

80

64

600

YES

YES

73

91

77

96

175

173

19,770

34x32x68

2,480

465

80

64

208

NO

NO

78

97

222

278

175

174

16,445

34x32x68

2,050

384

80

64

208

YES

NO

72

90

222

278

175

174

17,200

34x32x68

2,100

394

80

64

208

NO

YES

79

99

222

278

175

174

20,290

34x32x68

2,680

503

80

64

208

YES

YES

73

92

222

278

175

174

21,075

34x32x68

2,730

512

100

80

600

NO

NO

97

121

96

120

225

216

18,980

48x33x79

2,450

223

100

80

600

YES

NO

90

112

96

120

225

216

18,920

48x33x79

2,520

229

100

80

600

NO

YES

98

123

96

120

225

216

23,745

48x33x79

3,075

280

100

80

600

YES

YES

91

114

96

120

225

216

24,715

48x33x79

3,145

286

100

80

208

NO

NO

97

122

278

347

225

217

20,550

48x33x79

2,750

250

100

80

208

YES

NO

90

113

278

347

225

217

21,500

48x33x79

2,820

256

100

80

208

NO

YES

99

124

278

347

225

217

25,265

48x33x79

3,375

307

100

80

208

YES

YES

92

115

278

347

225

217

26,345

48x33x79

3,445

313

125

100

600

NO

NO

121

151

120

150

250

270

23,725

48x33x79

2,600

236

125

100

600

YES

NO

112

140

120

150

250

270

24,900

48x33x79

2,670

243

125

100

600

NO

YES

123

154

120

150

250

270

29,680

48x33x79

3,200

291

125

100

600

YES

YES

114

143

120

150

250

270

30,895

48x33x79

3,270

297

125

100

208

NO

NO

122

152

347

434

250

271

25,690

48x33x79

2,900

264

125

100

208

YES

NO

113

141

347

434

250

271

26,875

48x33x79

2,970

270

125

100

208

NO

YES

124

155

347

434

250

271

31,705

48x33x79

3,500

318

125

100

208

YES

YES

115

143

347

434

250

271

32,930

48x33x79

3,570

325

150

120

600

NO

NO

145

182

144

180

300

324

28,480

48x33x79

2,920

265

150

120

600

YES

NO

135

168

144

180

300

324

29,880

48x33x79

3,050

277

150

120

600

NO

YES

148

185

144

180

300

324

35,615

48x33x79

3,570

325

150

120

600

YES

YES

137

171

144

180

300

324

37,070

48x33x79

3,700

336

150

120

208

NO

NO

146

183

416

520

300

326

30,825

56x33x79

3,270

255

150

120

208

YES

NO

135

169

416

520

300

326

32,250

56x33x79

3,400

265

150

120

208

NO

YES

148

186

416

520

300

326

38,045

56x33x79

3,920

305

150

120

208

YES

YES

138

172

416

520

300

326

39,520

56x33x79

4,050

316

225

180

600

NO

NO

218

272

217

271

500

486

42,710

48x33x79

3,260

296

225

180

600

YES

NO

202

253

217

271

500

486

44,825

48x33x79

3,390

308

225

180

600

NO

YES

221

277

217

271

500

486

53,420

48x33x79

4,210

383

225

180

600

YES

YES

205

257

217

271

500

486

55,605

48x33x79

4,340

395

225

180

208

NO

NO

219

274

625

781

500

488

46,240

56x33x79

3,660

285

225

180

208

YES

NO

203

254

625

781

500

488

48,380

56x33x79

3,790

295

225

180

208

NO

YES

223

278

625

781

500

488

57,070

56x33x79

4,610

359

225

180

208

YES

YES

206

258

625

781

500

488

59,280

56x33x79

4,740

369

Applicable

 

13

 

1,4,8,

2,3,5,7,8,

6

6,8,9,

 

11

 

 

Notes:

 

 

 

9,11,12

9,11,12

 

11,12

 

 

 

 

A-4

Installation Manual

Image 82
Contents Series 600T UPS Page Installation Manual Table of Contents Figures Iii Page Installation Installation Considerations External Inspections Internal InspectionsBattery Safety Precautions Equipment LocationBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Configuring Your Neutral and Ground Connections Open-Rack BatteriesGrounding Liebert Series 600T UPS, 65-225 kVA, Single Module Electrode Preferred Grounding Configuration, 208 VAC input and output Grounding Local Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Grounding Configuration, Battery Systems Preferred Battery Cabinet Grounding ConfigurationWiring Considerations Power WiringTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Control Wiring Battery WiringWiring Connections Specific ConnectionsWiring Inspection Power Wiring Terminals Factory Supplied Torque SpecificationsField-Supplied Lugs ONE-HOLE LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA Liebert Series 600T UPS, 65-225 kVA, Single Module Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Line-up Detail, 65 & 80 kVA with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA with 3-Breaker MBC Installation Manual Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS Terminal Details, 150 & 225 kVA Standard SMS Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA Installation Manual Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 Liebert Series 600T UPS, 65-225 kVA, Single Module Company Behind the Products Technical Support