Liebert installation manual Series 600T Single Module Systems Volt Input

Page 80

Series 600T Single Module Systems

208 Volt Input

 

 

 

 

 

 

 

Inverter Or

Required

Maximum

Maximum

 

 

Floor

 

 

AC

 

 

 

 

Bypass AC

Battery

Battery

Heat

 

 

Loading

 

 

Output

 

 

Rectifier AC

Output

Discon-

Current

Dissipa-

Dimen-

Approx.

Lb./Sq.ft

UPS Rating

Voltage

Options

Input Current

Current

nect

At End Of

tion

sions

Weight

(Concen-

 

 

 

Input

Input

 

 

 

 

Rating

Discharge

BTU/Hr

Inches

LB.

trated

kVA

kW

VAC

Filter

Xformer

Nom

Max

Nom

Max

Amperes

Amperes

Full Load

(WxDxH)

(unpacked)

Loading)

65

52

208

NO

NO

184

229

180

226

175

141

14,390

34x32x68

1,900

251

65

52

208

YES

NO

170

213

180

226

175

141

15,015

34x32x68

1,950

258

65

52

208

NO

YES

187

233

180

226

175

141

17,555

34x32x68

2,400

318

65

52

208

YES

YES

173

216

180

226

175

141

18,200

34x32x68

2,450

324

80

64

208

NO

NO

226

282

222

278

175

174

17,710

34x32x68

2,100

278

80

64

208

YES

NO

209

262

222

278

175

174

18,480

34x32x68

2,150

285

80

64

208

NO

YES

230

287

222

278

175

174

21,600

34x32x68

2,630

348

80

64

208

YES

YES

213

266

222

278

175

174

22,395

34x32x68

2,680

355

100

80

208

NO

NO

282

353

278

347

250

217

22,140

48x33x79

2,900

264

100

80

208

YES

NO

262

327

278

347

250

217

23,100

48x33x79

2,950

268

100

80

208

NO

YES

287

359

278

347

250

217

27,005

48x33x79

3,270

297

100

80

208

YES

YES

266

333

278

347

250

217

27,995

48x33x79

3,320

302

125

100

208

NO

NO

353

441

347

434

250

271

27,675

48x33x79

3,050

277

125

100

208

YES

NO

327

409

347

434

250

271

28,875

48x33x79

3,100

282

125

100

208

NO

YES

359

449

347

434

250

271

33,755

48x33x79

3,450

314

125

100

208

YES

YES

333

416

347

434

250

271

34,995

48x33x79

3,500

318

150

120

208

NO

NO

424

530

416

520

350

326

33,200

56x33x79

3,320

259

150

120

208

YES

NO

393

491

416

520

350

326

34,650

56x33x79

3,450

269

150

120

208

NO

YES

431

538

416

520

350

326

40,500

56x33x79

4,020

313

150

120

208

YES

YES

399

499

416

520

350

326

42,000

56x33x79

4,150

323

225

180

208

NO

NO

635

794

625

781

500

488

49,800

56x33x79

3,870

302

225

180

208

YES

NO

589

736

625

781

500

488

52,000

56x33x79

4,000

312

225

180

208

NO

YES

646

807

625

781

500

488

60,750

56x33x79

4,510

351

225

180

208

YES

YES

599

748

625

781

500

488

63,000

56x33x79

4,640

362

Applicable

 

13

 

1,4,8,

2,3,5,7,8,

6

6,8,9,

 

11

 

 

Notes:

 

 

 

9,11,12

9,11,12

 

11,12

 

 

 

 

A-2

Installation Manual

Image 80
Contents Series 600T UPS Page Installation Manual Table of Contents Figures Iii Page Installation Installation Considerations External Inspections Internal InspectionsBattery Safety Precautions Equipment LocationBattery Safety Precautions in French PER CSA Requirements Battery Cabinets Configuring Your Neutral and Ground Connections Open-Rack BatteriesGrounding Liebert Series 600T UPS, 65-225 kVA, Single Module Electrode Preferred Grounding Configuration, 208 VAC input and output Grounding Local Electrode Preferred Grounding Configuration, Power-Tie Systems Preferred Grounding Configuration, Battery Systems Preferred Battery Cabinet Grounding ConfigurationWiring Considerations Power WiringTypical One-Line Diagrams for SMS with Standard Dual Input Typical One-Line Diagrams of SMS with optional single input Abbreviations for Circuit Breakers Control Wiring Battery WiringWiring Connections Specific ConnectionsWiring Inspection Power Wiring Terminals Factory Supplied Torque SpecificationsField-Supplied Lugs ONE-HOLE LugsTypes TW= FEPW= TBS, SA Outline Drawing Single and Multi Module 65 & 80 kVA Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Bypass Transformer Cabinet, 65 & 80 kVA Bypass Transformer Cabinet, 100-225 kVA Battery Power Pack, 65 & 80 kVA Battery Power Pack, Size A, 100-225 kVA Outline Drawing, 3-Breaker MBC, 65 & 80 kVA Liebert Series 600T UPS, 65-225 kVA, Single Module Outline Drawing, 3-Breaker MBC, 125-350 Amps Outline Drawing, 3-Breaker MBC, 450 to 800 Amps Outline Drawing, 3-Breaker MBC, 600-800 Amps Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Liebert Series 600T UPS, 65-225 kVA, Single Module Line-up Detail, 65 & 80 kVA SMS with Battery Cabinets Liebert Series 600T UPS, 65-225 kVA, Single Module Installation Manual Line-up Detail, 65 & 80 kVA with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA Space Saver with 3-Breaker MBC Installation Manual Line-up Detail, 100-225 kVA with 3-Breaker MBC Installation Manual Terminal Details, 65 & 80 kVA Single Module Systems Terminal Details, 100 & 125 kVA Space Saver Terminal Details, 150 & 225 kVA Standard SMS Terminal Details, 100 & 125 kVA Standard SMS Terminal Details, 150 & 225 kVA Standard SMS Control Connection Locations, 65 & 80 kVA Control Connection Locations, 100 through 225 kVA Standard Control Wiring, Single Module System Option Wiring, Alarm Status Contacts Option Wiring, Maintenance Bypass Interlock Option Wiring, Remote Status Panel Interface Option Wiring, Remote Terminal IFM RS-232 Communications Option Wiring, SiteScan Interface Option Wiring, Customer Alarm Interface Option Wiring, Battery Temperature Sensor Option Wiring, Snmp Interface Option Wiring, Internal Modem Option Wiring, Maintenance Bypass Cabinet Module Battery Disconnect, 65 through 125 kVA Module Battery Disconnect, 150 & 225 kVA Remote Status Panel, Surface Mount Circuit Breaker Schedule, 65 through 225 kVA Circuit Breaker Schedule, Battery Cabinets, 65 to 500 kVA Installation Manual Appendix a Site Planning Data KVA Single Module Systems Series 600T Single Module Systems Volt Input 11,330 600 Liebert Series 600T UPS, 65-225 kVA, Single Module Company Behind the Products Technical Support