Figure 2. Alternative Grounding Configuration, 480 or 600 VAC input and output
7.2Alternative Grounding Configuration, 480 or 600 VAC Input and Output, Isolated Power Distribution Units,
This configuration is similar to that shown in Section 7.1, except that the service entrance neutral is not brought into the UPS module. In this configuration, the UPS output transformer is considered a separately derived source. The UPS module neutral is bonded to the UPS ground, which is connected to a local grounding electrode in accordance with NEC
Please note that this configuration represents a price/performance
This configuration is reserved for those applications which meet all the following criteria:
•The facility has
•The module rectifier input and bypass input are fed from the same source
•The connected load is strictly
•Special precautions are taken to prevent trip- ping the ground fault interruptors. The time delay should be set to at least 30 cycles to pre- vent tripping when the UPS performs a transfer or retransfer operation.
CAUTION
Failure to properly set the ground fault interruptors could cause loss of power to the critical load.
Liebert Series 600T UPS, | 9 |