Liebert user manual Connecting Maintenance Bypass to UPStation GXT6000T

Page 11

Connecting Maintenance Bypass to UPStation GXT6000T - 208

208

VAC

 

 

Output

 

 

1

2

TB4

3

4

 

GND3

MAINTENANCE BYPASS

GND1

GND2

Utility

UPS input

UPS output

TB1

TB2

TB3

 

NOTE

When using the Maintenance Bypass with an UPStation GXT6000T-208, a jumper (included with the accessory kit) must be connected to the TB3 (UPS output) terminal block on the Maintenance Bypass between TB3-1 and TB3-2, as shown.

1 2 3 1 2 3 12 3 4

Utility input L1

L2

NOTE

GMB12 models are supplied with an attached input power cord complete with L14-30 plug.

L1

L2

L1

L2

InputOutput

GXT6000T - 208

+-

Ext. battery

7

Image 11
Contents UPStation GXT 6kVA Maintenance Bypass Page Table of Contents Page Save These Instructions Important Safety InstructionsGlossary of Symbols Standard Components FeaturesGeneral Description System DescriptionMaintenance Bypass component layout Amp Options Bypass SwitchConfigurable Output Distribution Major ComponentsPower Cable Installation Cable InstallationWiring Preparation Connecting Maintenance Bypass to UPStation GXT6000T GND3 Maintenance Bypass GND1 GND2 120V 240V Output TB4 Diagram for Attaching Unit to Wall WALL-MOUNT DiagramAccessing terminal block Hardwire Output OptionOn Maintenance Bypass Operating ProceduresSpecifications Page Page Company Behind the Products