Liebert UPStation GXT user manual Operating Procedures, On Maintenance Bypass

Page 16

OPERATING PROCEDURES

START-UP AND INITIALIZATION

Follow these steps in order to start up the GXT 6kVA UPS while connected to the Maintenance Bypass.

ON MAINTENANCE BYPASS

1.Set the Maintenance Bypass switch (SW1) to UPS position.

2.Close (position I) UPS Input switch (SW2).

3.Close (position I) Output Circuit breaker (CB1).

ON UPS

1.Close (position I) battery circuit breaker.

2.Close (position I) input circuit breaker.

3.Close (position I) output circuit breaker.

4.After the start-up sequence the UPS will automatically default to its internal bypass. The bypass LED will be lit.

5.Press UPS On/Alarm/Battery Test button for at least one second to turn the UPS on. The UPS ON LED will be lit.

6.Connected equipment may now be switched on.

SHUTTING DOWN THE UPS

Use the following procedure to power down the system.

ON UPS

1.Press Output OFF/Bypass button for at least 1 second, twice, within 4 seconds.

2.Open (position O) UPS output, input and battery circuit breakers.

ON MAINTENANCE BYPASS

1.Open (position O) output breaker (CB1).

2.Open (position O) UPS input switch (SW2).

TRANSFERRING SYSTEM FROM UPS TO MAINTENANCE BYPASS OPERATION

1.On UPS verify that Bypass LED is lit, if not, press UPS OFF/Bypass button for at least one second.

2.On Maintenance Bypass verify that the Bypass lamp is illuminated.

3.Rotate Bypass switch SW1 to the Bypass position.

4.Set UPS Input switch SW2 to the Off position (position O). This will remove power from UPS input.

! CAUTION

The connected load is now powered by the bypass source and is not protected.

TRANSFERRING SYSTEM FROM MAINTENANCE BYPASS TO UPS OPERATION

1.On Maintenance Bypass close (position I) UPS Input switch (SW2).

2.On UPS close (position I) input, output and battery circuit breakers.

3.After the start-up sequence the UPS will automatically default to its internal bypass. The bypass LED will be lit.

4.Press UPS ON/Alarm/Battery Test button for at least one second to turn the UPS on. The UPS ON LED will be lit.

5.On Maintenance Bypass verify that UPS Output LED is illuminated.

6.Rotate Bypass switch SW1 to the UPS position.

12

Image 16
Contents UPStation GXT 6kVA Maintenance Bypass Page Table of Contents Page Important Safety Instructions Save These InstructionsGlossary of Symbols Features General DescriptionSystem Description Standard ComponentsMaintenance Bypass component layout Bypass Switch Configurable Output DistributionMajor Components Amp OptionsWiring Preparation Cable InstallationPower Cable Installation Connecting Maintenance Bypass to UPStation GXT6000T GND3 Maintenance Bypass GND1 GND2 120V 240V Output TB4 WALL-MOUNT Diagram Diagram for Attaching Unit to WallHardwire Output Option Accessing terminal blockOperating Procedures On Maintenance BypassSpecifications Page Page Company Behind the Products