HARDWIRE OUTPUT OPTION

This product is intended to be installed by a qualified electrician only.

1.COMPLETELY REMOVE ALL POWER FROM THE FRAME. If the Maintenance Bypass is connected to the UPS, disconnect external battery supply.

2.Remove the end cover plate to access the terminal block (see Accessing terminal block below).

3.Without disconnecting from the terminal block, unscrew and pull out the hardwire plate(s).

4.Route all wires from the hardwire plate(s) to the terminal block.

5.Connect the GROUND wire to the grounding bar strip (GND1).

Accessing terminal block

6.Connect the remaining wires in accordance with the wiring diagram (located inside the base enclosure).

NOTE

When wiring 120 V loads, LINE must be alternated between TB4-1 and TB4-3 to balance the 120V load. Connect all neutral wires to TB4-4.

7.Replace the receptacle plates and the end cover plate, using care to not damage the wires.

11

Image 15
Contents UPStation GXT 6kVA Maintenance Bypass Page Table of Contents Page Save These Instructions Important Safety InstructionsGlossary of Symbols Standard Components FeaturesGeneral Description System DescriptionMaintenance Bypass component layout Amp Options Bypass SwitchConfigurable Output Distribution Major ComponentsCable Installation Wiring PreparationPower Cable Installation Connecting Maintenance Bypass to UPStation GXT6000T GND3 Maintenance Bypass GND1 GND2 120V 240V Output TB4 Diagram for Attaching Unit to Wall WALL-MOUNT DiagramAccessing terminal block Hardwire Output OptionOn Maintenance Bypass Operating ProceduresSpecifications Page Page Company Behind the Products