Liebert PSITM ON/Alarm Silence/Battery Test Button, OFF Button, Controls and Indicators

Page 18

Controls and Indicators

6.0CONTROLS AND INDICATORS

All indicators illuminated

for illustrative purposes only.

6.1ON/Alarm Silence/Battery Test Button

This button controls output power to connected load(s) and has three functions:

On

Alarm Silence

Battery Test

ON—When the UPS is Off, pressing the ON/Alarm Silence/Battery Test button for more than one

(1)second will start the UPS, and an audible alarm sounds briefly. The UPS is capable of starting on battery (battery start).

Alarm Silence—When a UPS audible alarm is active, pressing and releasing the ON/Alarm Silence/ Battery Test button will silence the active audible alarm, whether mains power is present or not. Once the alarm silence function has been activated, all active audible alarms will remain silenced until a new alarm condition is detected.

NOTE

The LOW BATTERY, OVER TEMP and OVERLOAD warning audible alarms CANNOT be silenced.

Battery Test—To initiate a manual battery test, press the ON/Alarm Silence/Battery Test button for at least one second while operating from mains power with no alarm conditions present.

If all five (5) Battery indicators are not illuminated, allow the UPS to recharge the batteries for 24 hours.

After 24 hours, retest the batteries.

After the batteries have been retested, if all five (5) Battery indicators are not illuminated, con- tact your local dealer, Liebert representative or Liebert Worldwide Support Group.

6.2OFF Button

When the UPS is on (in either Normal or Battery mode), pressing the OFF button for more than one (1) second will shut down the UPS. An audible alarm sounds briefly.

14

Image 18
Contents PowerSure PSI Power AvailabilityPage Table of Contents Figures Important Safety Instructions Safety PrecautionsPage Glossary of Symbols Voltage Programming ButtonIntroduction Front view of UPSAC Input External BatteryRS232 DB-9 Cabinet Connector Port USB PortRelay Major ComponentsInput Automatic Voltage Regulator Battery ChargerBattery Inverter-1000/1440 Models OnlyWHAT’S Included Tower UPS Installation InstallationPreparation Rack-Mount UPS Conversion and Installation Two 2 M4x6 Flat Head Screws Rack Mount HandlesWasher M5x12 Flat Screw Vertical overlay for towerOption 1 Serial Communications RJ11/RJ45 connectionExternal Battery Cabinet Installation Key to Repo switch connections 24 VDC Sense GroundAll indicators illuminated For illustrative purposes only ON/Alarm Silence/Battery Test ButtonControls and Indicators OFF ButtonAC Input Indicator-Green Load Level Indicators-4 green, 1 amberBattery Level Indicators-5 green Buck/Boost Indicator-GreenOver Temp Indicator-Amber Fault Indicator-RedMains power present Within operational limits Normal ModeBuck/Boost Mode Indicator shows UPS in Boost Mode solid greenBattery Indicator illuminated Battery ModeBattery Recharge Operation Battery Indicator flashes greenCommunications DB-9 ConnectorRemote Shutdown Via the DB-9 Connector DB-9 pin assignmentData Line Protection Connectors USB Interface PortUPS Intelligent Communications Voltage Programming Procedure Load Level Indicators Voltage Programming ButtonInput Voltage Output Voltage Setting Range Battery Mode Maintenance Cleaning the UPSBattery Replacement Maintaining BatteriesInternal Battery Replacement Procedure Troubleshooting Status indicatorsTroubleshooting chart Problem Cause SolutionSpecifications UPS specificationsSee Battery run times Environmental Battery cabinet specificationsBattery Parameter Model Number PS1000RT2-230 PS1440RT2-230 PS2200RT2-230Battery run times Page Locations Technical Support/ServiceCompany Behind the Products Asia 23F, Allied Kajima Bldg

PSITM specifications

The Liebert PSITM is an advanced power protection system designed to ensure the reliability and efficiency of critical systems in data centers, industrial applications, and mission-critical environments. As the demand for uninterrupted power supply continues to grow, the Liebert PSI serves as an indispensable asset.

One of the main features of the Liebert PSI is its online double-conversion technology. This method guarantees a continuous supply of clean and stable power to connected loads by converting incoming AC power to DC, then back to AC. This process eliminates power disturbances such as voltage sags, surges, and harmonics, ensuring that sensitive equipment operates without interruption.

In addition to its robust power protection capabilities, the Liebert PSI offers scalable solutions to meet varying power requirements. Ranging from 5 kVA to 40 kVA, it can be configured for single or three-phase operation. This flexibility allows businesses to tailor the system to match their specific needs, whether they are expanding data center operations or simply upgrading existing infrastructure.

Another notable characteristic of the Liebert PSI is its energy efficiency. The unit is designed to operate with a high efficiency of up to 94%, which not only reduces operational costs but also minimizes the environmental impact. Moreover, it features an eco-mode that optimizes energy use during non-critical operations without sacrificing reliability.

The Liebert PSI is equipped with advanced communication and management capabilities. It includes an intuitive LCD display for real-time monitoring, enabling users to access vital information about the unit's performance and status. Additionally, it supports various communication protocols such as SNMP and Modbus, allowing for seamless integration into existing management systems.

Furthermore, the Liebert PSI is designed with an emphasis on modularity, allowing for easy upgrades and maintenance. This modular approach reduces downtime and enhances serviceability, ensuring that the system remains reliable throughout its lifecycle.

In summary, the Liebert PSITM stands out as a comprehensive power protection solution that combines cutting-edge technology, energy efficiency, and user-friendly features. Its commitment to safeguarding critical systems against power disturbances makes it a vital component in the infrastructure of any modern data center or industrial setting.