Liebert PSITM Voltage Programming Procedure, Load Level Indicators Voltage Programming Button

Page 25

Voltage Programming Procedure

9.0VOLTAGE PROGRAMMING PROCEDURE

Figure 17 Load Level Indicators

Load Level

Indicators

Voltage

Programming

Button

1.Remove the front bezel from the UPS.

2.UPS must be operating in Normal (AC) mode.

NOTE

Mains power will be applied to the connected load.

3.The AC Input, Load, and Battery Level Indicators should be lit.

4.Press the Voltage Programming button for at least 5 seconds to enter the Configuration mode. The UPS will beep and all of the indicators on the front panel display will flash on and off for approximately 5 seconds. The next cycle will display the current configuration, either 220, 230 or 240 VAC. One of the Load Level Indicators will be flashing. Initially, the 0%-25% Load Level Indicator will be flashing, indicating the default setting of 230V as shown in Figure 17.

5.Press the ON button to step through the voltage settings until the appropriate Load Level Indicator is flashing.

6.Press the Voltage Programming button. The UPS will return to Normal mode operation.

The Voltage Programming button allows the operator to select the mains transfer voltage at which the UPS will switch to battery power. This also changes the inverter voltages. The voltage settings are as follows:

 

Input Voltage

Output Voltage

Setting

Range

(Battery Mode)

 

 

 

120V (230V)

166 - 272VAC

230VAC

(default)

 

 

110V (220V)

158 - 260VAC

220VAC

 

 

 

127V (240V)

172 - 283VAC

240VAC

 

 

 

21

Image 25 Contents
Power Availability PowerSure PSIPage Table of Contents Figures Safety Precautions Important Safety InstructionsPage Voltage Programming Button Glossary of SymbolsFront view of UPS IntroductionRS232 DB-9 Cabinet Connector Port External BatteryAC Input USB PortMajor Components RelayInput Battery Battery ChargerAutomatic Voltage Regulator Inverter-1000/1440 Models OnlyWHAT’S Included Installation Tower UPS InstallationPreparation Two 2 M4x6 Flat Head Screws Rack Mount Handles Rack-Mount UPS Conversion and InstallationVertical overlay for tower Washer M5x12 Flat ScrewRJ11/RJ45 connection Option 1 Serial CommunicationsKey to Repo switch connections 24 VDC Sense Ground External Battery Cabinet InstallationControls and Indicators ON/Alarm Silence/Battery Test ButtonAll indicators illuminated For illustrative purposes only OFF ButtonBattery Level Indicators-5 green Load Level Indicators-4 green, 1 amberAC Input Indicator-Green Buck/Boost Indicator-GreenFault Indicator-Red Over Temp Indicator-AmberBuck/Boost Mode Normal ModeMains power present Within operational limits Indicator shows UPS in Boost Mode solid greenBattery Recharge Operation Battery ModeBattery Indicator illuminated Battery Indicator flashes greenRemote Shutdown Via the DB-9 Connector DB-9 ConnectorCommunications DB-9 pin assignmentUSB Interface Port Data Line Protection ConnectorsUPS Intelligent Communications Load Level Indicators Voltage Programming Button Voltage Programming ProcedureInput Voltage Output Voltage Setting Range Battery Mode Battery Replacement Cleaning the UPSMaintenance Maintaining BatteriesInternal Battery Replacement Procedure Status indicators TroubleshootingProblem Cause Solution Troubleshooting chartUPS specifications SpecificationsBattery Parameter Battery cabinet specificationsSee Battery run times Environmental Model Number PS1000RT2-230 PS1440RT2-230 PS2200RT2-230Battery run times Page Company Behind the Products Technical Support/ServiceLocations Asia 23F, Allied Kajima Bldg