Controls and Indicators
4.1Control Buttons
4.1.1On/Alarm Silence/Manual Self-Diagnostic Test
This button controls output power to connected load(s). It has three functions:
•On
•Alarm Silence
•Manual
Alarm
Manual
If LED indicates the battery is weak: Allow the UPS to recharge the batteries for 8 hours. Retest the battery after recharge.
If LED still indicate battery weak after the battery has been retested, contact your local dealer, Emerson representative or Liebert Applications.
If LED indicates a Battery Fault: Contact your local dealer, Emerson representative or Liebert Applications.
If LED indicates UPS Fault: Remove the load, retest the self diagnostic test, if LED indicated UPS Fault, Contact your local dealer, Emerson representative or Liebert Applications.
NOTE
Refer to Figure 16 and Table 2 for details about the LEDs’ meaning.
4.1.2Off Button
When the UPS is operating in either Normal Mode or Battery Mode, pressing the Off button for more than three seconds will shut down the UPS.
4.2Status Indicators
4.2.1Status Change Button
The Status Change Button determines the information displayed by the five LEDs on the front panel. The default information shown by the LEDs is the load level on the UPS. Pressing the Status Change Button while the UPS is On prompts the LED display to show battery capacity for 5 seconds. This function assists in assessing the meaning of status indicators as described in 4.2.4 - UPS Status Indicators. See Figure 16 and Table 2 for the Status Change Button’s location.
4.2.2Load Level Indicator
The five LEDs at the top of the front panel illuminate with a steady glow to indicate the load level on the output of the UPS. The LEDs show the load level as a range, ± 5%. The LEDs’ load level meanings and colors are:
LED 1 | LED 2 | LED 3 | LED 4 | LED 5 |
|
|
|
|
|
10 - 24% — Green | 25 - 49% — Green | 50 - 74% — Yellow | 75 - 99% — Yellow | 100% or greater — Red |
|
|
|
|
|