Liebert PSI XR user manual Battery cabinet specifications, Model Number, Batteries

Page 26

 

 

 

 

Specifications

Table 7

Battery cabinet specifications

 

 

 

 

 

 

 

 

 

Model Number

PSRT3-24VBXR

 

PSRT3-48VBXR

 

 

 

 

 

 

 

PS1000RT3-120XR

 

PS2200RT3-120XR

 

Used w/UPS Model

PS1000RT3120XRW

 

PS2200RT3120XRW

 

PS1500RT3-120XR

 

PS3000RT3-120XR

 

 

 

 

 

PS1500RT3120XRW

 

PS3000RT3120XRW

 

 

 

 

Dimensions, W x D x H, in (mm)

 

 

 

 

 

 

 

 

Unit

17.3 x 19.3 x 3.5 (440 x 490.5 x 88)

 

 

 

 

Shipping

22 x 26.6 x 9 (560 x 675 x 228)

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

 

 

 

Unit

 

64 (29)

 

 

 

 

 

Shipping

 

73 (33)

 

 

 

 

 

Batteries

 

 

 

 

 

 

 

 

 

Type

Valve-regulated, nonspillable, lead acid

 

 

 

 

 

 

Quantity x Voltage x Ah

8 x 12 x 7.2

 

8 x 12 x 7.2

 

 

 

 

 

Manufacturer

CSB, YUASA or Equivalent

 

 

 

 

Environmental

 

 

 

 

 

 

 

 

Operating Temperature, °F (°C)

32 to 104 (0 to 40)

 

 

 

 

Storage Temperature, °F (°C)

5 to 104 (-15 to 40)

 

 

 

 

Relative Humidity

0% to 90%, non-condensing

 

 

 

 

Maximum Operating Altitude

10,000 ft. (3000m)

 

 

 

 

 

Agency

 

 

 

 

 

 

 

 

 

Safety

UL 1778, c-UL Listed

 

 

 

 

Emissions

FCC Part 15, Class A

 

 

 

 

Transportation

ISTA Procedure 1A Certification

 

 

 

 

 

22

Image 26
Contents Liebert PSI XR Page Table of Contents Battery Maintenance TablesImportant Safety Instructions Battery Handling PrecautionsPage Glossary of Symbols Status Change ButtonPort IntroductionPort 15A for 1500VA Nema 5-15R 3000VA-rear view Not shown for clarity RS232 DB-9 Receptacles #1 and #2Handles WHAT’S IncludedRack-Mount Mounting Hardware Screws and Washers Fixed Mounting RailsRelative humidity InstallationPreparation Non-condensingTower UPS Installation StepRack-Mount UPS Conversion and Installation Convert the Liebert PSI XR for rack installationOrient Display for Installation Connect Input Power and LoadNetwork Equipment Connect Network Surge protectionConnect Computer Interface Port Network surgeBattery cabinet connector color key EPO SwitchExternal Battery Cabinet Installation Connect battery cabinets to UPS Name Status Indicators Description Controls and IndicatorsDisplay and status indicators function, legend 3 4Status Indicators Control ButtonsLED Status indicators-color, illumination modeStatus Battery Mode Normal ModeBuck/Boost Mode Battery Recharge OperationCommunication DB-9 ConnectorRemote Shutdown Via the DB-9 Connector DB-9 pin assignmentVoltage configurations RJ-45 Data Line Protection ConnectorsUPS Inverter/Transfer Voltage Configurations UPS CommunicationsBattery Maintenance Battery Charging, StorageInternal Battery Replacement Procedure Specifications Liebert PSI XR specificationsBatteries Battery cabinet specificationsModel Number Liebert PSI XR battery run times Troubleshooting Troubleshooting Troubleshooting Page Ti n Ne tIti That