Liebert PSI XR user manual Battery Charging, Storage, Internal Battery Replacement Procedure

Page 24

Battery Maintenance

7.0BATTERY MAINTENANCE

7.1Battery Charging, Storage

The batteries are valve-regulated, nonspillable, lead acid and must be kept charged to retain their design life. The Liebert PSI XR continuously charges the batteries when connected to the utility sup- ply, even while the UPS is switched Off.

If the Liebert PSI XR will be stored for an extended period, Liebert recommends connecting the UPS to input power for at least 8 hours every four to six months to keep the batteries charged.

7.2Internal Battery Replacement Procedure

NOTICE

This UPS is equipped with internal batteries that the user can replace without shutting down the UPS or connected loads (hot swappable). Caution must be exercised when replacing the batteries because the load is unprotected from power fluctuations and power failures.

To replace the batteries:

1.Remove the two screws on the left side of the front bezel.

2.Pull the front bezel off the UPS.

3.Remove the screw on the battery connectors holder.

4.Remove the two screws on the battery bracket.

5.Disconnect the two slotted, red/gray and black battery connectors.

6.Grasp the battery pack assembly by the handle and pull it out of the front of the UPS.

7.Unpack the new battery assembly, taking care not to destroy the packing.

8.Compare the new and old battery assemblies to make sure they are the same. If so, proceed with replacement. If they are different, STOP and contact your local dealer, Emerson representative or Liebert Applications.

9.Slide the new battery pack into the UPS.

10.Reattach the battery bracket with the two screws.

11.Reconnect the slotted, red/gray and black battery connectors.

12.Reinsert the screw on the battery connectors holder.

13.Reattach the front bezel.

Figure 18 Battery replacement

Step 1

Step 2

Step 3

Step 4

 

Load Level

Battery Level

20

Image 24
Contents Liebert PSI XR Page Table of Contents Battery Maintenance TablesImportant Safety Instructions Battery Handling PrecautionsPage Glossary of Symbols Status Change ButtonIntroduction Port 15A for 1500VA Nema 5-15RPort 3000VA-rear view Not shown for clarity RS232 DB-9 Receptacles #1 and #2WHAT’S Included Rack-MountHandles Mounting Hardware Screws and Washers Fixed Mounting RailsInstallation PreparationRelative humidity Non-condensingTower UPS Installation StepRack-Mount UPS Conversion and Installation Convert the Liebert PSI XR for rack installationOrient Display for Installation Connect Input Power and LoadConnect Network Surge protection Connect Computer Interface PortNetwork Equipment Network surgeEPO Switch External Battery Cabinet InstallationBattery cabinet connector color key Connect battery cabinets to UPS Controls and Indicators Display and status indicators function, legendName Status Indicators Description 3 4Status Indicators Control ButtonsStatus indicators-color, illumination mode StatusLED Normal Mode Buck/Boost ModeBattery Mode Battery Recharge OperationDB-9 Connector Remote Shutdown Via the DB-9 ConnectorCommunication DB-9 pin assignmentRJ-45 Data Line Protection Connectors UPS Inverter/Transfer Voltage ConfigurationsVoltage configurations UPS CommunicationsBattery Charging, Storage Internal Battery Replacement ProcedureBattery Maintenance Specifications Liebert PSI XR specificationsBattery cabinet specifications Model NumberBatteries Liebert PSI XR battery run times Troubleshooting Troubleshooting Troubleshooting Page Ne t ItiTi n That