Liebert PSI XR Remote Shutdown Via the DB-9 Connector, Communication, DB-9 pin assignment

Page 22

Communication

6.0COMMUNICATION

6.1DB-9 Connector

The UPS has a DB-9 (9 pin female) connector on the rear to allow UPS status communications with a computer running Liebert MultiLink shutdown software. The connection provides serial communica- tion, On Battery and Low Battery signals. Liebert MultiLink software and a 6 ft. (1.8m) DB-9 serial cable are shipped with the UPS.

When power is interrupted and battery power is low, Liebert MultiLink software can signal the host computer to gracefully shut down the operating system.

Table 4

DB-9 pin assignment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DB-9 Pin

 

 

 

 

 

 

Assignment Description

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

Low Battery (open collector)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

UPS TxD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

UPS RxD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

Remote Shutdown (5-12V); on-battery operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

Common

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

Output Off, (short to Pin 5, non-latching); any mode operation

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

Low Battery (open emitter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

Utility Fail (open emitter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

Utility Fail (open collector)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pin Assignment

 

 

Collector to Emitter*

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

7

 

8

9

 

 

 

 

 

(+)

Open

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Collector

 

 

 

 

 

 

 

 

 

330 Ohms

 

 

 

 

 

 

 

 

 

 

 

 

1

2

3

4

5

 

 

 

(-)

Open

 

 

 

 

 

 

 

Emitter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.2Remote Shutdown Via the DB-9 Connector

The Liebert PSI XR can be shut down remotely by shorting Pins 5 and 6 or via Pins 4 and 5 of the DB-

9 connector.

6.2.1Any Mode Shutdown Via Pins 5 & 6

When Pin 6 is shorted to Pin 5, the UPS output is shut Off no matter what mode the UPS is operat- ing. The UPS cannot be started as long as the pins are shorted. When the short is removed, the UPS output can be enabled by pressing the ON/Alarm Silence/Manual Self-Diagnostic button.

6.2.2Battery Mode Shutdown Via Pins 4 & 5

While the UPS is operating on battery, a 5-12VDC signal for 2 seconds or longer is required to signal a shutdown. Signals for less than 2 seconds are ignored.

After Pin 4 receives the shutdown signal, a 2-minute shutdown timer begins a countdown. The shut- down timer cannot be stopped: If utility power returns during the 2-minute countdown, the shutdown timer continues until the end of 2 minutes and the UPS turns Off. The UPS will restart 10 seconds after utility power returns.

18

Image 22
Contents Liebert PSI XR Page Table of Contents Battery Maintenance TablesImportant Safety Instructions Battery Handling PrecautionsPage Glossary of Symbols Status Change ButtonPort 15A for 1500VA Nema 5-15R IntroductionPort 3000VA-rear view Not shown for clarity RS232 DB-9 Receptacles #1 and #2Handles WHAT’S IncludedRack-Mount Mounting Hardware Screws and Washers Fixed Mounting RailsRelative humidity InstallationPreparation Non-condensingTower UPS Installation StepRack-Mount UPS Conversion and Installation Convert the Liebert PSI XR for rack installationOrient Display for Installation Connect Input Power and LoadNetwork Equipment Connect Network Surge protectionConnect Computer Interface Port Network surgeExternal Battery Cabinet Installation EPO SwitchBattery cabinet connector color key Connect battery cabinets to UPS Name Status Indicators Description Controls and IndicatorsDisplay and status indicators function, legend 3 4Status Indicators Control ButtonsStatus Status indicators-color, illumination modeLED Battery Mode Normal ModeBuck/Boost Mode Battery Recharge OperationCommunication DB-9 ConnectorRemote Shutdown Via the DB-9 Connector DB-9 pin assignmentVoltage configurations RJ-45 Data Line Protection ConnectorsUPS Inverter/Transfer Voltage Configurations UPS CommunicationsInternal Battery Replacement Procedure Battery Charging, StorageBattery Maintenance Specifications Liebert PSI XR specificationsModel Number Battery cabinet specificationsBatteries Liebert PSI XR battery run times Troubleshooting Troubleshooting Troubleshooting Page Ti n Ne tIti That