GarrettCom 6K16V hooked up at the last, B4.1 UL Requirements for DC-powered units, B5.0 OPERATION

Page 60
hooked up at the last.

Magnum 6K16V Managed Fiber Switch

Installation and User Guide (06/04)

hooked up at the last.

When power is applied, the green PWR LED will illuminate.

Note: The GND should be hooked up first. The 6K16V unit has a floating ground, so the user may elect to Ground either + or = terminal to suit the customer’s use.

Before connecting hot lines to the Terminal Block of –48VDC, 24VDC or 125VDC, always use a digital voltmeter to measure the output voltage of the power supply and determine the lead which is more “+ve potential”. The more “+ve” voltage lead from 48V or –48V supply must be connected to the post labeled “+”.

An ON-OFF manual switch is optional for DC power. This can be used to cut off power connections and as a RESET for the Magnum 6K16V Switch.

B4.1 UL Requirements for DC-powered units

1.Minimum 18AWG cable for connection to a Centralized DC power source.

2.Minimum 14AWG cable for connection to a earthing wiring.

3.Use only with Listed 10 A circuit breaker provided in building installation.

4.“Complies with FDA radiation performance standards, 21 CFR subchapter J.” or equivalent.

5.Fastening torque of the lugs on the terminal block: 9 inch-pound max.

6.Centralized DC Power Source cable securement, use at least four cable ties to secure the cable to the rac,k at least 4 inches apart, with the first one located within 6 inches of the terminal block.

B5.0 OPERATION

Operation of Magnum 6K16V Switches with the optional -48VDC, 24VDC and 125VDC power supply is identical to that of the standard AC-powered models.

B6.0 ORDERING INFORMATION

To order the optional -48VDC power supply factory installed, add a suffix of “- -48VDC” after the product’s standard model # Example: Magnum 6K16VR-48VDC.

Similarly to order the optional 24VDC or 125VDC industrial specific power supply factory installed, add a suffix of “ 24VDC” or “125VDC” after the product ‘s standard model #. Example: Magnum 6K16V- 24VDC, Magnum 6K16V-125VDC.

B7.0 TROUBLESHOOTING

Please refer to Section 6.0 for troubleshooting

www . GarrettCom . com

53

Image 60
Contents www . GarrettCom . com Managed Fiber SwitchInstallation and User Guide HardwareMagnum 6K16V Managed Fiber Switch Hardware Installation and User GuideTrademarks Contacting GarrettCom, Inc Federal Communications CommissionRadio Frequency Interference Statement Reorient or relocate the receiving antennaSPECIFICATIONS InstallationIntroduction OPERATION5.0 Introduction - Magnum 6K16V Managed Fiber Switch PM TROUBLESHOOTINGAPPENDIX A WARRANTY INFORMATION APPENDIX B Internal DC Power Supply Options6K-SERIES MANAGED FIBER SWITCHES, GIGABIT, 100 AND QUAD-SERIES FIBER SWITCHES, 100 & 10MBPS, FIBER AND“OUTDOOR” ETHERNET SWITCH, FOR TEMPERATURE PERSONAL SWITCHES, 10/100MBMEDIA CONVERTERS, 10MB AND 100MB SERIES BRIDGE PORT MODULES BPMS, 4 TYPES, FOR SEGMENTTRANSCEIVERS, 10MB SERIES MINI-TRANSCEIVERS AND COAX MODELS1.0 SPECIFICATIONS 1.1 Technical Specifications Fiber Multi-mode connector types supportedPerformance Network Standards and Compliance, hardwareFiber Single-mode connector types Alarm Relay ContactsManagement Console connector Power Supply InternalPer-port jumpers and switches Agency ApprovalsNEBS Test Classification NEBS Compliant Email sales@GarrettCom.com for detailsMagnum Managed Fiber Switch 16 ports max Configuration OptionsMODEL DESCRIPTION 1.2 Ordering Informationfiber ports connector 2.0 Introduction 2.1 Inspecting the Package and Product 2.2 Product Description - Magnum 6K16V Managed Fiber Switch 100Mb, mode, and connector 2.2.1 Eight-port SFF fiber modules 6K8-MTRJ, 6K8-MLC, 100Mb fiberFig.2.2.2 SFF Fiber Port Modules 6K8-MTRJ to the left and 6K8-MLC or -SLC below2.2.2 Eight-Port Copper Module, 6K8-RJ45 4@ RJ-45 + 2@ 100Mb SC The Magnum Combosix-port modules are also available with 4@ MTRJ 100Mb mm SFF2.2.4 Four-Port 10 Mb and 100Mb mm Fiber ST Modules 2.2.6 Gigabit 1000Mbps port modules1@ 1000Mb Fiber SC + 2@ 100Mb SC 1@ 1000Mb Fiber SC + 4@10/ 100Mb2.2.6 Packet Prioritization, 802.1p QOS 2.2.7 Frame Buffering and Flow Control2.2.8 Managed Network Software MNS-6K for Magnum 6K16V ftp//ftp.garrettcom.com2.3 Features and Benefits „ Managed switching for high performance Ethernet LANs„ Switching services includes 802.1p QoS packet prioritization „ Features Fiber-Built-InExample 1 Magnum 6K16V Switch for a Industrial application 2.4 ApplicationsFig. 2.1- The Industrial factory floor application with Magnum 6K16V InternetSNMP Monitor 3.0 Installation 3.1 Locating Magnum 6K16V Switches3.2 Connecting Ethernet Media 3.2.1 Connecting Fiber Optic ST-type, “twist-lock” 3.2.2 Connecting Fiber Optic SC-type, Snap-In3.2.3 Connecting Single-Mode Fiber Optic IEEE Standard3.2.5 Connecting Twisted Pair CAT5E or better, Unshielded or Shielded Media3.2.6 Connecting Gigabit Media Using GBICs 3.3 DIN-Rail Mounting3.3.1 Mounting Dimensions for 6K16V with metal brackets 3.4 Powering the Magnum 6K16V Managed Fiber Switch 3.5 Alarm Contacts for monitoring internal power, and Software Traps Relay Contacts3.6 6K16V Port Module 6KPM Installation 3.6.1 Preparation for Installing and Removing 6KPMsBe sure the power cord is unplugged and will void the warrantyCaution Be careful not to disturb the power supply Step 2. Remove Chassis CoverFigure 3.6.1a Removing the Front panel from the unit Figure 3.6.1b Magnum 6K16V, Top view without chassis cover3.6.2 Installing 6KPM Cards in the Magnum 6K16V Step 3. Remove front panel face plate retaining screwsFigure 3.6.1c Top View - 6KPM retaining screws hold Face Plate Fig 3.6.2a Granddaughter Board shown separatelyFig. 3.6.2c Daughter Board, top view of version for 4 copper 10/100 portsFig. 3.6.2g Top View 6KPM Module installed inside a 6K16V Figure 3.6.2f Securely latching up 6KPM Cards into a Magnum 6K16VCaution Be sure the power cord is unplugged 3.6.3 Removing 6KPM Cardsfirmly. Figure 3.6.3a Top View - 6 retaining s crews shown by arrows Step 3. Remove 6KPM Card3.7 Connecting a Management Console Terminal to Magnum 6K16V DB-9 Console port connector3.7.1 RS-232 DB-9 Console Com port Serial port pin assignments Enlarged view of Magnum 6K16V Console Port area4.1 Switching Functionality 4.0 OPERATIONFiltering and Forwarding Address Learning4.3 Up-link Manual Switches set as = , for RJ-45 port only Power LED, ON when external power is applied to the unitFull / Half duplex LED, ON when the port is running full Speed LED, ON when the speed is 100Mbps , OFF when theAuto-negotiation per-port for 802.3u-compliant switches occurs when 4.6 Power Budget Calculations for Magnum 6K16V PM’s with Fiber Media 4.5 Flow-control, IEEE 802.3x standardLXSC40 and the “Cable Loss” for 9/125 Single-mode is 0.2 dB/km LXSC70 Magnum 6K16V Managed Fiber Switch Installation and User Guide 06/046KP4V Km, fdx5.0 Introduction - Magnum 6K16V Managed Fiber Switch Port Modules 5.1 Inspecting the Package and Product5.2 6KPM Module Description 5.2.1b 6KP4-F10ST, 4@10Mb multi-mode FX-ST “twist lock” Module ports are ST connectors and configured as 10MbHalf-duplex by default connectors and configuredmode SC-type connectors. It module of the 6K16V SwitchThe Magnum 6KP6 RJMSC is also a Combo 6 Portas 25+ Km see Power Budget, Section “small-form-factor” 5.2.5 6KP8-MTRJ, 8 @100Mb multi-mode FX , MTRJ Small-Form-factorThe functionality of this 100BASE-FX multi-mode 4 port module is 6KP8-MTRJMTRJ connectors give an advantage 5.2.6 6KP8-45MT, 4@ 10/100Mbps RJ-45 and 4@100Mb multi-mode FXMTRJ Small-Form-Factor The Magnum 6KP8-45MT5.2.9 6KP8-RJ45 Twisted Pair, 10/100Mb 8-Port connecting to a hub or another switch 5.2.11 GBIC-SXSC Gigabit fiber1000Mb, multi-mode SC Connector 6KP8VSingle-Mode Fiber port LC 5.2.11a GBIC-LXSC Gigabit fiber 1000Mb, multi-mode SC Connector 5.2.12 6KM-BLNK6.0 TROUBLESHOOTING 6.1 Before Calling for Assistance6.2 When Calling for Assistance 6.3 Return Material Authorization RMA ProcedureNo Problem Found GarrettCom, Inc 213 Hammond Ave Fremont, CA Attn. Customer Service6.4 Shipping and Packaging Information B1.0 SPECIFICATIONS FOR MAGNUM 6K16V SWITCHES, DC POWER B2.0 -48VDC, 24VDC and 125VDC POWER, THEORY OF OPERATIONB3.0 APPLICATIONS FOR DC POWERED ETHERNET SWITCHES B4.0 6K16V’S -48V, 24, 125 OR 5VDC INSTALLATIONB4.1 UL Requirements for DC-powered units B7.0 TROUBLESHOOTINGhooked up at the last B5.0 OPERATIONPower Supply Internal, 24VDC Dual-Source, model # Dual-Src-24V Power Supply Internal, 125VDC Dual-Source, model # Dual-Src-125VC3.0 DUAL-SOURCE OPTION, THEORY OF OPERATION C4.0 FEATURES AND BENEFITS OF THE DUAL-SOURCE DESIGN C5.0 INSTALLATIONC5.1 UL Requirements C6.0 ORDERING INFORMATIONExample Magnum 6K16VR-48VDC C7.0 OPERATION