GE GFK-2251 manual General Specifications, Standards, Applies to CE Marked units

Page 59

A

General Specifications

 

GENERAL SPECIFICATIONS

Standard(s)

 

 

 

 

Conditions

 

 

 

 

 

 

 

 

 

ISOLATION

 

 

 

 

 

 

 

 

 

 

 

Dielectric Withstand

UL 508, UL 840,

1.5KV DC (input power to secondary outputs)

 

 

IEC 664

 

 

 

 

 

 

ENVIRONMENTAL

 

 

 

 

 

 

 

 

 

 

 

Vibration

IEC 68-2-6

10 - 57 Hz, 0.012" displacement peak-peak

 

 

 

57 - 500 Hz, 1.0g acceleration

 

Shock

IEC 68-2-27

15g, 11ms, sinusoidal

 

 

Operating Temperature

 

0°C to 50°C

 

 

 

Storage Temperature

 

-20°C to +60°C

 

 

 

Humidity

 

5% to 95% RH (non-condensing)

 

Enclosure Protection

NEMA 250

NEMA Type 4, 4x and 12 when mounted in panel

 

 

 

 

 

EMC EMISSIONS

 

[applies to CE Marked units]

 

 

 

 

 

Radiated, Conducted

CISPR 11/EN 55011

“Industrial Scientific & Medical Equipment”

 

 

 

(Group 1, Class A)

 

 

 

CISPR 22/EN 55022

“Information Technology Equipment” (Class A)

 

 

47 CFR 15

referred to as FCC part 15, “Radio Devices” (Class A)

 

 

 

 

 

 

 

 

 

Harmonics

EN 61000-3-2

Class D

 

 

 

 

 

 

 

 

 

EMC IMMUNITY

 

[applies to CE Marked units]

 

 

 

 

 

 

 

 

Electrostatic Discharge

EN 61000-4-2

±

±

 

 

 

 

8KV Air, 4KV Contact

 

 

RF Susceptibility

EN 61000-4-3

10Vrms /m, 80Mhz to 1000Mhz, 80% AM, 1kHz sine wave

 

 

ENV 50140/

10Vrms /m, 900 ± 5Mhz, 100% PM, 200Hz square wave

 

 

ENV 50204

 

 

 

 

 

 

Fast Transient Burst

EN 61000-4-4

±

 

 

 

 

 

 

2KV: AC Input Port

 

 

 

 

±1KV: Signal Ports

 

 

Surge Withstand

EN 61000-4-5

±

) CM,

±

 

 

2KV (12

 

1kV (2

) DM: AC Input Port

 

 

 

±1kV (2) CM: Signal Ports (shielded)

 

 

ANSI C37.90A

+2.5KV CM & DM: AC Input Port

 

 

 

+2.5KV CM: Signal Ports (shielded)

 

Conducted RF

EN 61000-4-6

10Vrms, 0.15 to 80Mhz, 80%AM: AC Input & Signal Ports

 

Input Dips & Variation

EN 61000-4-11

AC Input Dips: 30 & 100% Nominal (10ms)

 

 

 

AC Input Variation: ±10% Nominal (10s)

 

Voltage Flicker

EN 61000-3-3

Dt < 3.3%, Dc < 3.3%, Dmax < 4.0%, Pst < 1.0: AC Input Port

GFK-2251

Appendix A Product Agency Approvals, Standards, and General Specifications

A-3

Image 59
Contents GE Fanuc Automation As Used in this Publication Preface Content of This ManualPage Contents Contents Cmos Checksum Error Example of Cable Shield Clamping Assembly Installation I/O Port Range Table Panel C Industrial Computer Features Feature Description Feature SummaryStatus LEDs Removable Hard Disk DriveFront Panel Keypads Channels Front Access PanelEthernet port and side expansion slots Network InterfaceApplication Software Expansion SlotsSetup Chapter Powerup and Software InstallationStartup for Windows NT Systems Startup for Windows 2000 Systems GFK-2251 GFK-2251 Powerup and Software Installation GFK-2251 GFK-2251 Powerup and Software Installation Directory Structure Installing Application SoftwareShutting Down the Computer Image RecoveryChapter Hardware Installation Cutting the Panel Cutout Installation GuidelinesAC Input Power Panel MountingPanel C Industrial Computer Dimensions Installing Panel Mounting ClipsInstalling Retaining Clips Blanking Plates Installing Expansion CardsConfiguring Expansion Cards Legacy ISA Only Chapter Connectors and Cabling Power Input Compact Flash Port Port ConfigurationsCommunications Ports USB PortsMouse and Keyboard Ports Pin Number Signal nameVideo Output Port Floppy Disk Drive and CD-ROM PortsPin Assignment Printer Port LPT1RS-232C Name Pin Assignment Serial Communication PortsEthernet Communication Port Pin No Signal DescriptionSix cable clamps included with assembly Ground Plate Outline, Mounting Dimensions, and Cable ClampExample of Cable Shield Clamping Assembly Installation Clamped Cable with Exposed Shield System Operation System Peripherals Operator Interfaces Period Membrane Keypad Scan Codes Touch Screen Driver for Windows Symbol Name FunctionControl and Status LEDs Touch ScreenNetwork Component Comments CommunicationsUSB Bios SettingsSystem Test and Initialization Diagnostics and TroubleshootingSelf-Test Diagnostics System Configuration VerificationDisplay TroubleshootingPowerup Symptom Possible Causes SolutionKeyboard MemoryExternal PS/2 Mouse PLC/PC Connection CommunicationsNetwork Communications To replace the battery Cmos Checksum Error Industrial PC Chapter Technical Data Monitor SystemGFK-2251 Description Agency Standard CommentsGovernment Regulations Applies to CE Marked units General SpecificationsStandards Panel C Nonincendive Field Wiring Control Drawing #DR00Cmos IndexIndex