Generac Power Systems 2A and 10A Battery Chargers, ‹ R-200A J2 Connector 14 PIN White

Page 13

General Information

R-panel Technical Manual

‹R-200A J1 CONNECTOR (23 PIN, GRAY=1800 RPM, WHITE=3600 RPM)

Pin #

1Governor 12V Supply

2Reserved (Do not connect any wires to this pin.)

3GND-B to Governor Driver

4Hi-Coolant Temp Input

50V to Governor Driver

65V Supply to Governor Driver

7Distributor (Hall Sensor) 12V Sensor Supply

8Low Coolant Level Input

9Crank Signal Input

10Crank Signal Return

11Low Fuel Pressure Input

12Governor Position Feedback Input

13Reserved (Do not connect any wires to this pin.)

14Coil + (Supply voltage to engine coil pack.)

15Coil A Driver

162.4L Distributor Sensor Return

172.4L Distributor Sensor Input

18Governor PWM Output

19Governor Enable Output

20Lo Oil Pressure Input

212.4L Flywheel Sensor Screen

22Coil C Driver

23Coil B Driver

‹R-200A J2 CONNECTOR (14 PIN WHITE)

Pin #

1Reserved

2Start (Crank) Relay Driver Output (minimum coil resistance is 90 ohms)

3Fuel (Run) Relay Driver Output (minimum coil resistance is 90 ohms)

42-wire Start Input (from relay contact in W- type transfer switch)

5Momentary Open Switch Input (B+)

62-wire Start Return (from relay contact in W- type transfer switch)

7Manual/Auto Input (+BS)

819.5VAC Utility Sense Input

9Reserved

10Transfer Switch Relay Driver Output (mini- mum coil resistance is 60 ohms)

11Manual Input

1219.5VAC Utility Sense Return

13Reserved

14GND-B (Battery Ground)

Refer to the individual generator wiring dia- grams and schematics for additional informa- tion.

2A AND 10A BATTERY CHARGERS

There are two types of battery chargers. A 2 Amp bat- tery charger and a 10 Amp battery charger.

The 2 Amp battery charger is a "float" type charger. A "float" type charger will charge the battery at its maxi- mum output current rating until the battery voltage reaches a "float" voltage and then the charge current will decrease to maintain the battery at that "float" voltage.

The 10 Amp battery charger is an "equalize" type charger. An "equalize" type charger will charge the battery at its maximum output current rating until the battery voltage reaches an "equalize" voltage and then the charge current will decrease to maintain the battery at a lower "float" voltage.

The 2 Amp charger incorporates fuses on both the input AC line and the battery charger output. The input AC line fuse is a Littelfuse 2 Amp, Slo-Blo Fuse, 5x20mm, P/N 218002. The AC line fuse is located on the charger printed-circuit board. The output DC bat- tery fuse is a Littelfuse 5 Amp, Mini-Blade Fuse, P/N 297005. The battery fuse is located on the charger printed-circuit board.

The 10 Amp charger incorporates fuses on both the input ac line and the battery charger output. The input AC line fuse is a Littelfuse 5 Amp, Slo-Blo Fuse, 5x20mm, P/N 218005. The AC line fuse is located on the charger printed-circuit board. The output DC battery fuse is a Littelfuse 15 Amp, ATO Fuse, P/N 257015. The battery fuse is located on the charger printed-circuit board.

These chargers require that the battery be connected to the charger in order to turn on. The battery voltage must also be above a certain "boost" voltage for the charger to turn-on.

The boost voltage required is approximately 11 volts for a 12V system. If the battery open-circuit voltage is less than the above boost voltage, it is recommended that the battery be checked.

If the voltage of the generator's 12V battery exceeds 15VDC, during normal charging operation, the bat- tery should be checked. Typical battery voltages, when a 12V battery is being charged, should be in the 13VDC to 15VDC range.

The 2 Amp and 10 Amp chargers are UL recognized for use in the R-panel enclosure and are not to be operated outside the R-panel enclosure.

11

Image 13
Contents Technical Manual  General Hazards  Table of Contents Authorized Service Dealer LocationIntroduction Control Board DIP Switch & Jumper SettingsDip Switch & Jumper Settings Old Revision Switch Position Condition System Low Generator Operation Utility RestoredEngine Timing Utility FailureNormal Exercise Mode Active AlarmRE-CRANK Auto StartSystem Ready Green LED Indicator LOW Battery RED LED IndicatorLOW Fuel Pressure Yellow LED Indicator LOW OIL Pressure RED LED IndicatorOvercrank RED LED Indicator RPM Signal Failure Flashing RED Overspeed IndicatorAlarm Cancel Automatic Transfer Switch ATS ModeEngineered Transfer Switch 2-WIRE Start GTS Mode Line NEU GND Voltage Regulator Adjustment‹ R-200A J2 Connector 14 PIN White 2A and 10A Battery Chargers‹ 10A, 12VDC Battery Charger ‹ 2A, 12VDC Battery ChargerPanel Technical Manual Generac Power SYSTEMS, INC