Generac Power Systems R-200A ‹ 2A, 12VDC Battery Charger, ‹ 10A, 12VDC Battery Charger

Page 14

General Information

R-panel Technical Manual

DANGER

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely corro- sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.

Do not use any jumper cables or booster battery to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.

‹2A, 12VDC BATTERY CHARGER

Nominal Input AC Line Voltage

120Vac

Operating AC Line Voltage Range

108Vac to

 

 

 

132Vac

Input AC Line Frequency

..............................

50 or 60Hz

AC Line Fuse

2 Amp Slo-Blo, 5x20mm,

 

Littelfuse P/N 218002

Battery Fuse

5 Amp, Littelfuse

 

Mini-Blade Fuse P/N 297005

Nominal Charge Rate

 

2 Amps

Float Voltage (type)

 

13.4 Volts

Battery Undervoltage Shutdown (typ)

11 Volts

LED Indicators

 

 

 

AC Line Voltage > 108Vac

Green LED ON

Battery Connected & Charging

Yellow LED ON

(the Green LED must be ON to obtain a valid bat-

tery charging indication,

 

 

Yellow LED ON if charge current > approx 0.5

Amps)

 

 

 

Battery Current Drain (AC Power OFF)

........ 30mA (typ)

AC Line Connection

via terminal block

 

(AC Hot, AC Neut & GND)

Battery Connections

via terminal block

 

 

 

(Pos +, Neg -)

Be sure the AUTO/OFF/MANUAL switch is set to the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the utility power supply to the battery charger is turned off, or sparking may occur at the battery posts as the cables are attached and cause an explosion.

‹10A, 12VDC BATTERY CHARGER

Nominal Input AC Line Voltage

........................

120Vac

Operating AC Line Voltage Range

108Vac to 132Vac

Input AC Line Frequency

50 or 60Hz

AC Line Fuse

5 Amp, 5x20mm,

 

 

Littelfuse P/N 218005

Battery Fuse

15 Amp, Littelfuse ATO

 

 

Blade P/N 257015

Nominal Charge Rate

10 Amps

Equalize Voltage (typ)

13.8 Volts

Float Voltage (typ)

13.0 Volts

Current at Equalize to Float Transition (typ) .. 5 Amps

Battery Undervoltage Shutdown (typ)

...............11 Volts

LED Indicators

 

AC Line Voltage > 108Vac

Green LED ON

Battery Connected & Charging

Yellow LED ON

the Green LED must be ON to obtain a valid battery charging indication,

Yellow LED ON if charge current > approx 2 Amps)

Battery Current Drain (AC Power OFF)

....... 30mA (typ)

AC Line Connections

......................... via terminal block

 

(AC Hot, AC Neut & GND)

Battery Connections

via terminal block

 

 

(Pos +, Neg -)

Control Connections

......................AC Power Fail Relay,

 

Form C, 2Amps, 12Vdc

(N.O. Contact closes when ac line voltage is applied) (N.O. Contact opens when ac line voltage is removed)

12

Image 14
Contents Technical Manual  General Hazards  Authorized Service Dealer Location Table of ContentsControl Board DIP Switch & Jumper Settings IntroductionDip Switch & Jumper Settings Old Revision Switch Position Condition System Low Engine Timing Utility RestoredGenerator Operation Utility FailureRE-CRANK Active AlarmNormal Exercise Mode Auto StartLOW Fuel Pressure Yellow LED Indicator LOW Battery RED LED IndicatorSystem Ready Green LED Indicator LOW OIL Pressure RED LED IndicatorAlarm Cancel RPM Signal Failure Flashing RED Overspeed IndicatorOvercrank RED LED Indicator Automatic Transfer Switch ATS ModeEngineered Transfer Switch 2-WIRE Start GTS Mode Voltage Regulator Adjustment Line NEU GND2A and 10A Battery Chargers ‹ R-200A J2 Connector 14 PIN White‹ 2A, 12VDC Battery Charger ‹ 10A, 12VDC Battery ChargerPanel Technical Manual Generac Power SYSTEMS, INC