General Information
DANGER
Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.
Battery electrolyte fluid is an extremely corro- sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.
Do not use any jumper cables or booster battery to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.
2A, 12VDC BATTERY CHARGER
Nominal Input AC Line Voltage | 120Vac | ||
Operating AC Line Voltage Range | 108Vac to | ||
|
|
| 132Vac |
Input AC Line Frequency | .............................. | 50 or 60Hz | |
AC Line Fuse | 2 Amp | ||
| Littelfuse P/N 218002 | ||
Battery Fuse | 5 Amp, Littelfuse | ||
| |||
Nominal Charge Rate |
| 2 Amps | |
Float Voltage (type) |
| 13.4 Volts | |
Battery Undervoltage Shutdown (typ) | 11 Volts | ||
LED Indicators |
|
|
|
AC Line Voltage > 108Vac | Green LED ON | ||
Battery Connected & Charging | Yellow LED ON | ||
(the Green LED must be ON to obtain a valid bat- | |||
tery charging indication, |
|
| |
Yellow LED ON if charge current > approx 0.5 | |||
Amps) |
|
|
|
Battery Current Drain (AC Power OFF) | ........ 30mA (typ) | ||
AC Line Connection | via terminal block | ||
| (AC Hot, AC Neut & GND) | ||
Battery Connections | via terminal block | ||
|
|
| (Pos +, Neg |
Be sure the AUTO/OFF/MANUAL switch is set to the OFF position, before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply to the battery charger is turned off, or sparking may occur at the battery posts as the cables are attached and cause an explosion.
10A, 12VDC BATTERY CHARGER
Nominal Input AC Line Voltage | ........................ | 120Vac |
Operating AC Line Voltage Range | 108Vac to 132Vac | |
Input AC Line Frequency | 50 or 60Hz | |
AC Line Fuse | 5 Amp, 5x20mm, | |
|
| Littelfuse P/N 218005 |
Battery Fuse | 15 Amp, Littelfuse ATO | |
|
| Blade P/N 257015 |
Nominal Charge Rate | 10 Amps | |
Equalize Voltage (typ) | 13.8 Volts | |
Float Voltage (typ) | 13.0 Volts |
Current at Equalize to Float Transition (typ) .. 5 Amps
Battery Undervoltage Shutdown (typ) | ...............11 Volts |
LED Indicators |
|
AC Line Voltage > 108Vac | Green LED ON |
Battery Connected & Charging | Yellow LED ON |
the Green LED must be ON to obtain a valid battery charging indication,
Yellow LED ON if charge current > approx 2 Amps)
Battery Current Drain (AC Power OFF) | ....... 30mA (typ) | |
AC Line Connections | ......................... via terminal block | |
| (AC Hot, AC Neut & GND) | |
Battery Connections | via terminal block | |
|
| (Pos +, Neg |
Control Connections | ......................AC Power Fail Relay, | |
| Form C, 2Amps, 12Vdc |
(N.O. Contact closes when ac line voltage is applied) (N.O. Contact opens when ac line voltage is removed)
12