Generac Power Systems R-200A technical manual Switch Position Condition System Low

Page 6

General Information

R-panel Technical Manual

 

 

 

 

 

 

 

 

 

Switch Position

 

 

Condition

System

Low

Low

Low

High

Over

Over

Manual

Auto

Off

 

 

 

Ready

Fuel

Bat

Oil

Temp

Speed

Crank

 

 

 

 

 

Generator Switch is

OFF

@

X

OFF

OFF

OFF

OFF

 

 

O

 

 

in the OFF Mode

 

 

 

 

 

 

 

 

 

 

 

 

System Ready for

ON

@

X

OFF

OFF

OFF

OFF

 

O

 

 

 

Automatic Start

 

 

 

 

 

 

 

 

 

 

 

 

Generator Switch is

OFF

@

X

OFF

OFF

OFF

OFF

O

 

 

 

 

in the MANUAL Mode

 

 

 

 

 

 

 

 

 

 

 

 

Weekly Exerciser

X

@

Flashing

Flashing

Flashing

Flashing

Flashing

O

O

O

 

 

is not Set (Note A)

 

 

(---------------------------------------1 sec rate -------------------------------------)

 

 

 

 

 

Battery Voltage <12.2V

X

@

ON

 

 

 

 

O

O

O

 

 

for > 1 minute

 

 

(Non-Latching)

 

 

 

 

 

 

 

 

 

Battery Voltage <6V

OFF

@

ON

 

 

 

 

O

O

 

 

 

For > 0.05 seconds

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

ON

 

 

 

O

O

 

 

 

To Low Oil Pressure

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

 

ON

 

 

O

O

 

 

 

To High Cooant Temp

 

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

 

 

ON

 

O

O

 

 

 

To Engine Overspeed

 

 

 

 

 

 

 

 

 

 

 

 

Unit Failed to Start

OFF

@

X

 

 

 

ON

O

O

 

 

 

During it's Crank Cycle

 

 

 

 

 

 

 

 

 

 

 

 

Utility Voltage is

Flashing

@

X

 

 

 

 

O

O

 

 

 

< 60% of Nominal

1 sec rate

 

 

 

 

 

 

 

 

 

 

 

Unit Shutdown due

OFF

@

X

 

Flashing

 

 

O

O

 

 

 

To Low Coolant Level

 

 

 

 

 

 

 

 

 

 

 

 

Engine Speed Signal

OFF

@

X

 

 

Flashing

 

O

O

 

 

 

Fault/RPM Signal Loss

 

 

 

 

 

 

 

 

 

 

 

 

Control Board is

Flashing

@

X

 

 

 

 

O

O

O

 

 

In GTS Mode

5 sec ON, 1 sec OFF

 

 

 

 

 

 

 

 

 

 

 

DIP Switch #5 is

OFF

@

ON

ON

ON

ON

ON

O

O

O

 

 

not set correctly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@= Low Fuel Pressure is a Yellow LED and will be ON when fuel pressure is less than 5 inches Water Column X = indicates that the LED can be ON or OFF depending on the Operating Mode (i.e. Manual, OFF or Auto) Note A: a RED LED fault indication has priority over the flashing LED's used to indicate exercise time not set

4

Image 6
Contents Technical Manual  General Hazards  Authorized Service Dealer Location Table of ContentsControl Board DIP Switch & Jumper Settings IntroductionDip Switch & Jumper Settings Old Revision Switch Position Condition System Low Engine Timing Utility RestoredGenerator Operation Utility FailureRE-CRANK Active AlarmNormal Exercise Mode Auto StartLOW Fuel Pressure Yellow LED Indicator LOW Battery RED LED IndicatorSystem Ready Green LED Indicator LOW OIL Pressure RED LED IndicatorAlarm Cancel RPM Signal Failure Flashing RED Overspeed IndicatorOvercrank RED LED Indicator Automatic Transfer Switch ATS ModeEngineered Transfer Switch 2-WIRE Start GTS Mode Voltage Regulator Adjustment Line NEU GND2A and 10A Battery Chargers ‹ R-200A J2 Connector 14 PIN White‹ 2A, 12VDC Battery Charger ‹ 10A, 12VDC Battery ChargerPanel Technical Manual Generac Power SYSTEMS, INC