General Information
ACTIVE ALARM | LOW SPEED EXERCISE |
Low Oil Pressure, High Coolant Temp, Low Coolant Level, Overspeed, Overcrank, Engine Speed Signal Loss and a Dead Battery indication will all be latched shutdowns. In the event one of these conditions occurs, the unit will be shut down, the appropriate LED will be illuminated, and the unit will not start again without manual intervention (see
RE-CRANK
If an engine speed signal failure occurs while the gen- erator is running the engine will shutdown and then attempt a
NORMAL EXERCISE MODE
To select this mode, place DIP switch position 3 in the ON position.
In Normal Exercise Mode the generators will exercise at their normal running speed.
The
The weekly exercise cycle is set as follows:
1.Place the AUTO/OFF/MANUAL switch in the AUTO position.
2.Press and hold the "Set Exercise Time " switch for five (5) seconds and then release.
At this time all five (5) red LED's will flash for 10 seconds, then the engine will start and run for it's 12 minute exercise period, then shut down. The gen- erator will now start and run each week at approxi- mately the same time.
If battery power to the
In the event of a failure while running in this mode, the five (5) red LED's will stop flashing, the indi- vidual fault LED will turn on and the engine will be shut down. Once the AUTO/OFF/MANUAL switch is switched to OFF, the individual fault LED will turn off and the five (5) red LED's will begin flashing to show that the exercise mode has not yet been set.
To select this mode place DIP switch position 3 in the OFF position.
In Low Speed Exercise mode the normal speed 3600 rpm generators will exercise at 1800 rpm. The nor- mal 1800 rpm generators will exercise at 1400 rpm in this mode.
If the utility fails during the low speed exercise period, a 10 second timer will start. If the utility returns to a normal operating level, during this 10 second time interval the low speed exercise operation will contin- ue. If the utility is still not present (i.e. utility voltage less than 60% of nominal) when the above 10 second timer expires then the low speed exercise mode is terminated and the engine will ramp up to its normal running speed within five (5) seconds. If the utility returns during the five (5) second
If battery power to the
In the event of a failure while running in this mode, the five (5) red LED's will stop flashing, the indi- vidual fault LED will turn on and the engine will be shut down. Once the AUTO/OFF/MANUAL switch is switched to OFF, the individual fault LED will turn off and the five (5) red LED's will begin flashing to show that the exercise mode has not yet been set.
AUTO START
This unit is designed to automatically start in the event of a utility failure. A utility failure is defined as the utility voltage being less than approximately 60% of nominal, while the utility is considered good when it is restored to approximately 80% of its nominal value.
If the generator is already running under exercise when an auto start is required, it will simply transfer the load after a 15 second delay and then switch to auto operation.
6