| SG SeriesTM UPS PLUS® |
| 800VA to 1.5kVA | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Model Number |
|
|
|
|
|
| ||||
| Nominal VA |
|
| 800 |
| 1000 |
| 1000 | 1500 |
|
|
| Electrical Input |
|
|
|
|
|
|
|
|
|
|
| Nominal AC Voltage |
|
| 120V |
| 120V |
| 230V | 120V |
|
|
| AC Voltage Range |
|
|
|
|
|
| ||||
|
|
| 5.5 |
| 6.9 |
| 3.6 | 10.7 |
|
| |
| Frequency |
|
|
|
| 50/60 Hz ± 5% | (Auto – Tracking) |
|
|
| |
| Power Factor Correction |
|
|
|
| > 0.95 |
|
|
| ||
| Efficiency (Typical) |
|
|
|
|
| > 86% |
|
|
| |
| Electrical Output |
|
|
|
|
|
|
|
|
|
|
| Watts |
|
| 560 |
| 700 |
| 700 | 1050 |
|
|
| AC Voltage |
|
| 100V |
| 100V |
| 200V | 100V |
| |
| (Switchable ) |
|
| 110V |
| 110V |
| 220V | 110V |
| |
|
|
|
| 115V |
| 115V |
| 230V | 115V |
| |
|
|
|
| 120V |
| 120V |
| 240V | 120V |
| |
| Frequency |
|
|
|
| 50/60 Hz (Auto Tracking ) |
|
|
| ||
| Frequency Stability |
|
|
|
| ±0.3% (Battery Mode) |
|
|
| ||
| Voltage Regulation |
|
|
|
|
| ± 2% |
|
|
| |
| Step Load Change |
|
|
|
| ± 7% for 100% load variation |
|
|
| ||
| Harmonic Distortion |
|
|
|
| < 3% Linear Load, < 5% Non |
|
|
| ||
| Overload |
|
|
|
| 105% load for 50 Seconds |
|
|
| ||
| Crest Ratio |
|
|
|
|
| 3:1 |
|
|
| |
| Battery |
|
|
|
|
|
|
|
|
|
|
| DC Voltage |
|
|
|
| 36V |
|
| 72V |
| |
| Type |
|
|
|
| 12V, 7AH Sealed Lead Acid Maintenance |
|
|
| ||
| Back Up Time | @ Full Load | 9 Minutes |
|
| 6 Minutes | 11 Minutes |
| |||
|
| @ 1/2 Load | 25 Minutes |
|
| 19 Minutes | 30 Minutes |
| |||
| Recharge Time |
|
|
|
| 8 Hours to 90% |
|
|
| ||
| Battery times are approximate. |
|
|
|
|
|
|
|
| ||
| Transfer Time |
|
|
|
|
|
|
|
|
|
|
| Line Fails/Recovers |
|
|
|
|
| Zero |
|
|
| |
| UPS to Bypass or Reverse |
|
|
|
| < 4ms |
|
|
| ||
| After Overload |
|
|
|
| Auto Transfer to UPS |
|
|
| ||
| Electrical Connections |
|
|
|
|
|
|
|
| ||
| Input |
|
| 6’ Cord with |
| 6’ Cord with |
| 6’ Cord with | 6’ Cord with |
| |
|
|
|
|
|
| Schuko or 6 |
| ||||
| Output |
|
| (6) |
| (6) |
| (4) IEC 320 | (6) |
| |
| Contact the factory for | other input/output | options. |
|
|
|
|
|
|
| |
| Environmental |
|
|
|
|
|
|
|
|
|
|
| Operating Temperature |
|
|
| 0º C - 40º C (32º F to 104º F) |
|
|
| |||
| Humidity |
|
|
|
| 10% to 95% Non – Condensing |
|
|
| ||
| Altitude |
|
|
|
|
| 7,000 Feet |
|
|
| |
| Cooling |
|
|
|
| Low Velocity Forced Air Fans |
|
|
| ||
| Audible Noise @ 1 Meter |
|
|
| <45dBA |
|
| < 50dBA |
| ||
| Controls and Indicators |
|
|
|
|
|
|
|
| ||
| LED |
|
| Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level |
|
| |||||
| Audible Alarms |
|
| DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp. , Over Load, Fau lt Alarm |
|
| |||||
| Communications |
|
|
| (Bundled UPSilon 2000 Software) |
|
|
| |||
| Mechanical |
|
|
|
|
|
|
|
|
|
|
| Dimensions H x W x D | inches |
|
| 8.7 x 6.0 x 15.8 |
|
| 13.8 x 7.6 x 18.9 |
| ||
|
|
| (mm) |
|
| (220.9 x 152.4 x 401.3) | (350.5 x 193.0 x 480 .0) |
| |||
| Weight |
| lb. (kg) |
| 33 (14.9) |
|
| 68 (30.9) |
|
| |
| Agency Listing |
|
| UL 1778, CUL, |
| CE available with Schuko | UL 1778, CUL, |
| |||
|
|
|
|
| FCC Class A |
| plug only | FCC Class A |
| ||
| Available Options |
|
|
|
|
|
|
|
|
|
|
| Option A |
|
| 60 Hz to 50 Hz Frequency Conversion |
|
|
|
|
| ||
| Option B |
|
| 50 Hz to 60 Hz Frequency Conversion |
|
|
|
|
| ||
| Option C |
|
| SNMP/HTTP Network Card (Internal) |
|
|
|
|
| ||
| Option D |
|
| Standard Contact Closure Interface Card |
|
|
|
|
| ||
| Maintenance Bypass |
|
|
|
|
|
|
| |||
| External Battery Packs |
| Extended Run Time Battery Packs (minut es to hours) |
|
|
| |||||
| Fast Battery Charger |
|
| Fast Charger internal to the Extended Battery Pack Cabinet (Required for battery times 2 hours or more.) |
|
|
23