Falcon SG800-2T, SG800-1T specifications SG SeriesTM UPS Plus

Page 25

 

SG SeriesTM UPS PLUS®

 

800VA to 1.5kVA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Number

 

 

SG800-1T

 

SG1K-1T

 

SG1K-2T

SG1.5K-1T

 

Nominal VA

 

 

800

 

1000

 

1000

1500

 

 

 

Electrical Input

 

 

 

 

 

 

 

 

 

 

 

Nominal AC Voltage

 

 

120V

 

120V

 

230V

120V

 

 

 

AC Voltage Range

 

 

87-140V

 

87-140V

 

170-275V

87-140V

 

 

 

Current-Amps

 

 

5.5

 

6.9

 

3.6

10.7

 

 

 

Frequency

 

 

 

 

50/60 Hz ± 5%

(Auto – Tracking)

 

 

 

 

Power Factor Correction

 

 

 

 

> 0.95

 

 

 

 

Efficiency (Typical)

 

 

 

 

 

> 86%

 

 

 

 

Electrical Output

 

 

 

 

 

 

 

 

 

 

 

Watts

 

 

560

 

700

 

700

1050

 

 

 

AC Voltage

 

 

100V

 

100V

 

200V

100V

 

 

(Switchable )

 

 

110V

 

110V

 

220V

110V

 

 

 

 

 

115V

 

115V

 

230V

115V

 

 

 

 

 

120V

 

120V

 

240V

120V

 

 

Frequency

 

 

 

 

50/60 Hz (Auto Tracking )

 

 

 

 

Frequency Stability

 

 

 

 

±0.3% (Battery Mode)

 

 

 

 

Voltage Regulation

 

 

 

 

 

± 2%

 

 

 

 

Step Load Change

 

 

 

 

± 7% for 100% load variation

 

 

 

 

Harmonic Distortion

 

 

 

 

< 3% Linear Load, < 5% Non -Linear Load

 

 

 

 

Overload

 

 

 

 

105% load for 50 Seconds

 

 

 

 

Crest Ratio

 

 

 

 

 

3:1

 

 

 

 

Battery

 

 

 

 

 

 

 

 

 

 

 

DC Voltage

 

 

 

 

36V

 

 

72V

 

 

Type

 

 

 

 

12V, 7AH Sealed Lead Acid Maintenance -Free

 

 

 

 

Back Up Time

@ Full Load

9 Minutes

 

 

6 Minutes

11 Minutes

 

 

 

@ 1/2 Load

25 Minutes

 

 

19 Minutes

30 Minutes

 

 

Recharge Time

 

 

 

 

8 Hours to 90%

 

 

 

 

Battery times are approximate.

 

 

 

 

 

 

 

 

 

Transfer Time

 

 

 

 

 

 

 

 

 

 

 

Line Fails/Recovers

 

 

 

 

 

Zero

 

 

 

 

UPS to Bypass or Reverse

 

 

 

 

< 4ms

 

 

 

 

After Overload

 

 

 

 

Auto Transfer to UPS

 

 

 

 

Electrical Connections

 

 

 

 

 

 

 

 

 

Input

 

 

6’ Cord with

 

6’ Cord with

 

6’ Cord with

6’ Cord with

 

 

 

 

 

5-15P

 

5-15P

 

Schuko or 6 -15P

5-15P

 

 

Output

 

 

(6) 5-15R

 

(6) 5-15R

 

(4) IEC 320

(6) 5-15R

 

 

Contact the factory for

other input/output

options.

 

 

 

 

 

 

 

 

Environmental

 

 

 

 

 

 

 

 

 

 

 

Operating Temperature

 

 

 

0º C - 40º C (32º F to 104º F)

 

 

 

 

Humidity

 

 

 

 

10% to 95% Non – Condensing

 

 

 

 

Altitude

 

 

 

 

 

7,000 Feet

 

 

 

 

Cooling

 

 

 

 

Low Velocity Forced Air Fans

 

 

 

 

Audible Noise @ 1 Meter

 

 

 

<45dBA

 

 

< 50dBA

 

 

Controls and Indicators

 

 

 

 

 

 

 

 

 

LED

 

 

Line, Inverter, Battery Reserve, Load, Bypass, Alarm, Crest, Battery & Load Capacity Level

 

 

 

Audible Alarms

 

 

DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp. , Over Load, Fau lt Alarm

 

 

 

Communications

 

 

 

RS-232 Serial Port

(Bundled UPSilon 2000 Software)

 

 

 

 

Mechanical

 

 

 

 

 

 

 

 

 

 

 

Dimensions H x W x D

inches

 

 

8.7 x 6.0 x 15.8

 

 

13.8 x 7.6 x 18.9

 

 

 

 

(mm)

 

 

(220.9 x 152.4 x 401.3)

(350.5 x 193.0 x 480 .0)

 

 

Weight

 

lb. (kg)

 

33 (14.9)

 

 

68 (30.9)

 

 

 

Agency Listing

 

 

UL 1778, CUL,

 

CE available with Schuko

UL 1778, CUL,

 

 

 

 

 

 

FCC Class A

 

plug only

FCC Class A

 

 

Available Options

 

 

 

 

 

 

 

 

 

 

 

Option A

 

 

60 Hz to 50 Hz Frequency Conversion

 

 

 

 

 

 

Option B

 

 

50 Hz to 60 Hz Frequency Conversion

 

 

 

 

 

 

Option C

 

 

SNMP/HTTP Network Card (Internal)

 

 

 

 

 

 

Option D

 

 

Standard Contact Closure Interface Card

 

 

 

 

 

 

Maintenance Bypass

 

 

Make-Before-Break External Wrap Around

 

 

 

 

 

 

External Battery Packs

 

Extended Run Time Battery Packs (minut es to hours)

 

 

 

 

Fast Battery Charger

 

 

Fast Charger internal to the Extended Battery Pack Cabinet (Required for battery times 2 hours or more.)

 

 

23

Image 25
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions Extended Battery Bank Option Input Power Factor CorrectionTrue Regenerative On-Line Design Microprocessor ControlInstallation Instructions Page SW1 Typical Extended Battery Bank & UPS Interconnection Installation Procedure for Extended Battery BanksFor 800VA-1KVA Models SG800VA-3kVA Tower Extended Battery Bank Selection GuideOperation Load Level Indicator LedsInverter Indicator LED Category one alarms Audible AlarmsCategory two alarms = UPS Output Voltage is of RangeSG800-1T & SG1K-1T Typical Rear Panel Overview Rear Panel DetailsSG800-2T & SG1K-2T Typical Rear Panel Overview SG1.5K-2T, SG2K-2T & SG3K-2T Typical Rear Panel Overview SG1.5K-1T, SG2K-1T & SG3K-1T Typical Rear Panel OverviewBreaker Location Communications InterfacesSupported Protocols With on-bypass signal No on-bypass signalTypical Falcon Dry Contact Relay Board Typical Falcon Opto-coupler Interface Card No-bypass signalOpto Board Internal Circuitry APC Style Board APC Style Dry Contact Relay BoardBattery Life vs. Temperature Care & MaintenanceBattery Replacement FCC Considerations Storing the UPS and BatteriesRequesting Technical Information or Support Technical SupportSUPPORT@FALCONUPS.COM 800.842.6940 Falcon Web SupportFalcon ELECTRIC, INC NEW Product Limited WarrantySG SeriesTM UPS Plus 2kVA 3kVA 2kVA & 3kVA