Falcon SG800-1T, SG800-2T specifications Installation Instructions

Page 6

CHAPTER 2

INSTALLATION INSTRUCTIONS

1.Verify the following is included in the UPS shipping carton:

(1)UPS, (1) Software Diskette(s) & Manual, (1) Power Cord (800VA-1KVA models only),

(1)Owners Manual & (1) UPS/Computer Cable.

2.Verify the UPS unit is configured for the proper input/output voltage and frequency. This information is stated on the nameplate label located on the rear or the side panel of the unit. If any special input plug and output receptacle configurations were specified at the time of order, verify for proper configuration.

3.Set the dip switches located on the UPS rear panel for the nominal UPS output voltage desired. See the dip switch setting tables located on page 6.

In most cases the nominal UPS output voltage should be set to match the incoming utility voltage. This will assure a close matching voltage in the event the UPS is placed on bypass. NOTE: Disregard the "ON" marking on the side of the actual dip switch housing; use the tables in this manual or the silkscreen on the UPS rear panel only.

Dip switch 3 "enables" or "disables” the "Green Mode" function. The UPS is shipped from the factory with the switch set in the "disabled" position (up). If SW3 is switched down or to the "enabled" position, the Green Mode function is activated. When the

load connected to the output of the UPS drops to under 10% of the full rated UPS output for 30 seconds, the UPS is automatically placed into bypass and the inverter is turned off.

NO BATTERY BACKUP IS PROVIDED AFTER THE GREEN MODE HAS ACTIVATED.

Dip switch settings must be made while the UPS is turned off. Any changes made while the UPS is turned on will not take effect until the UPS is turn off and back on again since the switch settings are read by the microprocessor only during initial UPS power up.

4.To prevent accelerated battery discharge during shipment, the 1-3kVA models have had the battery fuse removed. INSTALL THE BATTERY FUSE PRIOR TO TURNING ON THE UPS INPUT CIRCUIT BREAKER OR PLUGGING IN THE UPS. Prior to installing the battery fuse, depress the battery pre-charge button located on the UPS rear panel for two seconds prior to inserting the battery fuse. Not applicable to 1kVA models.

CAUTION

NEVER REMOVE THE BATTERY FUSE WHILE THE UPS AC CIRCUIT BREAKER IS TURNED ON AND OPERATING FROM THE UTILITY VOLTAGE OR UPS DAMAGE MAY RESULT. THE UPS MUST BE COMPLETELY SHUT DOWN PRIOR TO DISABLING THE INTERNAL BATTERY SUPPLY.

CAUTION

In the event this UPS is to be turned off or stored for more than four weeks, the battery fuse must be removed to prevent excessive battery discharge. If placed in long-term storage, every four months the UPS must be plugged in and turned on for 24 hours to allow the batteries to recharge and prevent battery damage due to the normal battery self-discharge asociated with sealed lead-acid batteries. Failure to follow these procedures may cause battery damage and invalidate your warranty.

4

Image 6
Contents Owners Operating Manual Table of Contents SG Series ON-LINE UPS System Block Diagram Important Safety Instructions True Regenerative On-Line Design Input Power Factor CorrectionExtended Battery Bank Option Microprocessor ControlInstallation Instructions Page SW1 Installation Procedure for Extended Battery Banks Typical Extended Battery Bank & UPS InterconnectionSG800VA-3kVA Tower Extended Battery Bank Selection Guide For 800VA-1KVA ModelsLoad Level Indicator Leds OperationInverter Indicator LED Category two alarms Audible AlarmsCategory one alarms = UPS Output Voltage is of RangeRear Panel Details SG800-1T & SG1K-1T Typical Rear Panel OverviewSG800-2T & SG1K-2T Typical Rear Panel Overview SG1.5K-1T, SG2K-1T & SG3K-1T Typical Rear Panel Overview SG1.5K-2T, SG2K-2T & SG3K-2T Typical Rear Panel OverviewBreaker Communications Interfaces LocationSupported Protocols No on-bypass signal With on-bypass signalTypical Falcon Dry Contact Relay Board No-bypass signal Typical Falcon Opto-coupler Interface CardOpto Board Internal Circuitry APC Style Dry Contact Relay Board APC Style BoardCare & Maintenance Battery Life vs. TemperatureBattery Replacement Storing the UPS and Batteries FCC ConsiderationsSUPPORT@FALCONUPS.COM Technical SupportRequesting Technical Information or Support 800.842.6940 Falcon Web SupportNEW Product Limited Warranty Falcon ELECTRIC, INCSG SeriesTM UPS Plus 2kVA 3kVA 2kVA & 3kVA