Falcon manual F3400/F1000 Wiring, Power Supply and Ground Connections

Page 23

2 Getting Started

2.4.F3400/F1000 Wiring

RLE Technologies recommends an 18AWG stranded copper wire for connection from each monitored point to a terminal block (TB) connection on the F3400/F1000. RLE recommends no more than 500 feet (152.4m) of wire at this specification. If longer runs are needed, please contact RLE Technologies for application guidance. Shielded twisted pair wiring is recommended for analog signal transmitters being wired outside of conduit runs and dropped ceiling applications.

2.4.1 Power Supply and Ground Connections

Connect an 18AWG ground wire from the ground terminal to a suitable earth ground. Plug the wall adapter into P1 and a UPS outlet as shown below. The wall adapter has a five foot power cord. RLE Technologies recommends powering the F3400/F1000 from a UPS supply to allow the F3400/F1000 to send alarm notification during a power outage.

Figure 2.1 24 VDC Power Supply Connection

www.rletech.com

23

970.484.6510

Image 23
Contents Monitoring & Notification Revision History Product Registration Rletech.com 970.484.6510 Contents Remote Access Alarm ID Reference Tables Rletech.com Figures F3400/F1000 Accessories Wiring Tables Rletech.com Product Description System OverviewSystem Status LED Front Panel Indicators and ControlsTerminal Block Designations System Overview Terminal Block Designations SW1 Switch Settings Rear Panel IndicatorsSet the F3400/F1000’s IP Address InstallationGetting Started CommunicationObtain the Ethernet Address Troubleshooting the ARP/PING Commands Set the F3400/F1000’s IP Address using a Web BrowserSet the F3400/F1000s IP Address using a Telnet Connection Set the F3400/F1000’s IP Address Using an EIA232 ConnectionPower Supply and Ground Connections F3400/F1000 Wiring3 RJ11 Phone Line Connection 2 EIA232 COM1 ConnectionF3400/F1000 Ethernet Connection to a PC on a Subnet 4 RJ45 Ethernet ConnectionRelay K1 and K2 Connection F3400/F1000 Relay Output Wiring ExamplesMain Menu F3400/F1000 Web Interface OverviewHistorical Data Alarm HistoryEvent History Digital Status History Data History Data History Text Downloads Server Status IdentityWeb Links ConfigurationConfiguration Menu Configuration MenuInputs Inputs ConfigurationCalculator Link Configuration Menu Example Relays Relays ConfigurationSchedules Schedules Configuration MenuAlarm Management Modem Modem ConfigurationPhone Number Configuration Configure Phone NumbersConfiguration Menu Configuring Web Links Falcon Links Egg/NestSNMP/SYSLOG Modbus Interface 13 Modbus Interface Configuration14 LD Unit Modbus Slave Configuration LD Unit Modbus Slave ConfigurationModbus Packet Log Modbus Register Data LogSeries Modbus Slave Register Map Reset Modbus PortBACnet 17 BACnet ConfigurationServer Ping 18 Server Ping ConfigurationSystem 19 System ConfigurationInternet Protocol Clock22 User Administration Configuration User Administration Web Access23 Email Configuration Network Time Protocol 24 Network Time Protocol ConfigurationFlash Program Network StatisticsProduct Registration Configuration Menu 970.484.6510 EIA-232 Interface Flash Executable Code Unit Start UpInformation regarding the commands in this section Configuration Menu Factory Menu Main Configuration Menu SCTCP IP Configuration MenuIP Configuration Menu Commands Remote Access Configuration Modem Option Remote AccessDisplay Date/Time TI ADC Input Values AD POINT-TO-POINT Protocol Configuring the F3400/F1000Configuring the PC Upgrading F3400/F1000 Firmware Upgrading Firmware Managing Configuration DataPort = Upgrading F3400/F1000 Firmware via Tftp ClientUpgrading Firmware and Managing Configuration Data Saving Configuration Data via EIA232 COM1 Port X- Modem Loading/Saving F3400/F1000 Configuration DataSaving Configuration Data via Tftp Client Loading Configuration Data via EIA232 COM1 Port X-Modem Loading Configuration Data via Tftp ClientPage Analog 4-20Ma Gain/Offset Conversion Formula Analog Input 4-20MA Reference ChartVoltage Figure B.1 T120D Temperature Sensors F3400/F1000 Accessories WiringFigure B.3 Dwyer Temperature/Humidity Sensors Figure B.6 HD150 & HD150-2 Gas Sensors Figure B.11 SeaHawk LDRA6, LD1000, and LD300 Leak Detection Configuring the SeaHawk LD5100 as an Analog InputF3400/F1000 Accessories Wiring F3400/F1000 Accessories Wiring 970.484.6510 Analog Tables Alarm ID Reference TablesThermistor Tables Digital Tables Alarm ID Reference Tables 970.484.6510 F3400 Technical SpecificationsHTTP/HTML Front Panel Interface Switches Technical Specifications 970.484.6510