8 Upgrading Firmware and Managing Configuration Data

8.1.2Updating F3400/F1000 Firmware via the EIA232 COM1 Port (X-Modem)

1Connect to the F3400/F1000 using HyperTerminal. For instruction on how to do so, see our support document “Connect HyperTerminal” available on the Documentation/Files section of the F-Series webpage at www.rletech.com.

2Start firmware updates by either:

a Pressing any key after power-up when a 10 second window provides an opportunity to abort the Flash Main Program, or

b Typing EX to exit to Bootloader once the Main Menu appears.

3From the F3400/F1000 Boot prompt, type ? and press ENTER to see the list of available commands.

4From the F3400/F1000 Boot prompt, type ID and press ENTER. Note which Flash has the lowest serial number. The Flash with the lowest serial number is the backup. The idea is to erase the backup, load the new version, which becomes the active Flash, then erase and load the other Flash.

5From the F3400/F1000 Boot Prompt, erase the back up Flash program (the one with the lowest serial number) by typing ERASE PRGM1or ERASE PRGM2 followed by ENTER. After a second or so, the screen will update with an OK.

6From the F3400/F1000 Boot prompt, type LOAD PRGM1 XMODEM or LOAD PRGM2 XMODEM followed by Enter. Select the same program that was erased.

7From the HyperTerminal menu select Transfer -> Send File. Use the browse button to select the F3400/F1000 firmware file from the computer's directory. The file must be binary and have a .bin extension. Select the file and upload it using the 1K X-Modem protocol. Then click Send.

8A transfer status screen will be displayed. The transfer time will take about 10 minutes. Once the transfer is complete, the transfer status window will automatically close. The HyperTerminal window will indicate that the upload is complete.

9From the F3400/F1000 Boot prompt, type RUN or power down the F3400/F1000 and restart it to verify that the new Flash program runs.

10Press ENTER to display the F3400/F1000 Main Menu and repeat the steps above to erase and download to the other Flash program chip.

11Once the firmware upgrade is complete, disconnect the serial cable and close HyperTerminal.

www.rletech.com

75

970.484.6510

Image 75
Contents Monitoring & Notification Revision History Product Registration Rletech.com 970.484.6510 Contents Remote Access Alarm ID Reference Tables Rletech.com Figures F3400/F1000 Accessories Wiring Tables Rletech.com Product Description System OverviewSystem Status LED Front Panel Indicators and ControlsTerminal Block Designations System Overview Terminal Block Designations SW1 Switch Settings Rear Panel IndicatorsSet the F3400/F1000’s IP Address InstallationGetting Started CommunicationObtain the Ethernet Address Troubleshooting the ARP/PING Commands Set the F3400/F1000’s IP Address using a Web BrowserSet the F3400/F1000s IP Address using a Telnet Connection Set the F3400/F1000’s IP Address Using an EIA232 ConnectionPower Supply and Ground Connections F3400/F1000 Wiring3 RJ11 Phone Line Connection 2 EIA232 COM1 ConnectionF3400/F1000 Ethernet Connection to a PC on a Subnet 4 RJ45 Ethernet ConnectionRelay K1 and K2 Connection F3400/F1000 Relay Output Wiring ExamplesMain Menu F3400/F1000 Web Interface OverviewHistorical Data Alarm HistoryEvent History Digital Status History Data History Data History Text Downloads Server Status IdentityWeb Links ConfigurationConfiguration Menu Configuration MenuInputs Inputs ConfigurationCalculator Link Configuration Menu Example Relays Relays ConfigurationSchedules Schedules Configuration MenuAlarm Management Modem Modem ConfigurationPhone Number Configuration Configure Phone NumbersConfiguration Menu Configuring Web Links Falcon Links Egg/NestSNMP/SYSLOG Modbus Interface 13 Modbus Interface Configuration14 LD Unit Modbus Slave Configuration LD Unit Modbus Slave ConfigurationModbus Packet Log Modbus Register Data LogSeries Modbus Slave Register Map Reset Modbus PortBACnet 17 BACnet ConfigurationServer Ping 18 Server Ping ConfigurationSystem 19 System ConfigurationInternet Protocol Clock22 User Administration Configuration User Administration Web Access23 Email Configuration Network Time Protocol 24 Network Time Protocol ConfigurationFlash Program Network StatisticsProduct Registration Configuration Menu 970.484.6510 EIA-232 Interface Flash Executable Code Unit Start UpInformation regarding the commands in this section Configuration Menu Factory Menu Main Configuration Menu SCTCP IP Configuration MenuIP Configuration Menu Commands Remote Access Configuration Modem Option Remote AccessDisplay Date/Time TI ADC Input Values AD POINT-TO-POINT Protocol Configuring the F3400/F1000Configuring the PC Upgrading F3400/F1000 Firmware Upgrading Firmware Managing Configuration DataPort = Upgrading F3400/F1000 Firmware via Tftp ClientUpgrading Firmware and Managing Configuration Data Loading/Saving F3400/F1000 Configuration Data Saving Configuration Data via Tftp ClientSaving Configuration Data via EIA232 COM1 Port X- Modem Loading Configuration Data via EIA232 COM1 Port X-Modem Loading Configuration Data via Tftp ClientPage Analog 4-20Ma Gain/Offset Conversion Formula Analog Input 4-20MA Reference ChartVoltage Figure B.1 T120D Temperature Sensors F3400/F1000 Accessories WiringFigure B.3 Dwyer Temperature/Humidity Sensors Figure B.6 HD150 & HD150-2 Gas Sensors Figure B.11 SeaHawk LDRA6, LD1000, and LD300 Leak Detection Configuring the SeaHawk LD5100 as an Analog InputF3400/F1000 Accessories Wiring F3400/F1000 Accessories Wiring 970.484.6510 Analog Tables Alarm ID Reference TablesThermistor Tables Digital Tables Alarm ID Reference Tables 970.484.6510 F3400 Technical SpecificationsHTTP/HTML Front Panel Interface Switches Technical Specifications 970.484.6510