A P P E N D I X
ANALOG INPUT 4-20MA REFERENCE
CHART
Analog 4-20Ma Gain/Offset Conversion Formula:
Gain = Sensor Range (High Value - Low Value) / 4
Offset = Sensor Low Value - Gain
Example: TH140 Humidity
Gain = (High Value (100)
Offset = (Sensor Low Value (0) - Gain (25)) =
Table A.1 Analog Input
RLE |
|
|
|
|
Product | Transducer Type | Range | Gain | Offset |
Number | ||||
TEMPERATURE |
|
|
| |
|
|
|
|
|
TH140 | Temperature (Display in Deg F) | 50°F - 95°F | 11 | 39 |
|
|
|
|
|
| Temperature (Display in Deg F | 32°F - 122°F | 22 | 11 |
|
|
|
|
|
| Temperature (Display in Deg C) | 10°C - 35°C | 6 | 4 |
|
|
|
|
|
| Temperature (Display in Deg C | 0°C - 55°C | 13 | |
|
|
|
|
|
| Humidity | 0% - 100% RH | 25 | |
|
|
|
|
|
T120 | Temperature (Display in Deg F) | 50°F - 95°F | 11 | 39 |
|
|
|
|
|
| Temperature (Display in Deg F) | 32°F - 122°F | 22 | 11 |
|
|
|
|
|
| Temperature (Display in Deg C) | 10°C - 35°C | 6 | 4 |
|
|
|
|
|
| Temperature (Display in Deg C) | 0°C - 50°C | 13 | |
|
|
|
|
|
CURRENT |
|
|
|
|
|
|
|
|
|
CT55 | Current | 0 - 5 Amps | 1 | |
|
| 0 - 55 Amps | 13 | |
|
|
|
|
|
www.rletech.com | 79 | 970.484.6510 |