Cisco Systems SFS 7008 manual About the Fabric Controllers, Removing a Fabric Controller

Page 42

42

9.Check the LEDs on the fan module to verify the status. Refer to “Fan LEDs” on page 69.

Fabric Controllers

About the Fabric Controllers

Refer to “Fabric Controller Modules” on page 18 for more specific information about this module.

About a Failed Fabric Controller

If you believe a fabric controller module has failed, contact technical support.

Refer to “Fabric Controller LEDs” on page 70 and “Monitor the Cards” on page 79 for monitoring information.

Locating a Failed Fabric Controller

The fabric controllers are located on the front of the chassis, behind the bezel cover. Refer to Figure 1-1for a diagram of the chassis. The slots are labelled on the chassis.

Considerations Before Removing a Fabric Controller Card

Before removing a fabric controller card from either a node or a core slot of the Topspin 270, keep the following in mind:

1.The fabric controllers cards in the core slots are paired to the Management Interface modules on the other side of the chassis.

Fabric controller card in slot 11 is paired to the Management Interface module in slot 15.

Fabric controller card in slot 12 is paired to Management Interface module in slot 16.

Therefore, before removing a fabric controller from a core slot, make sure that the second pairing of Fabric Controller/Management Interface module is intact.

2.Removing the fabric controller in the core slot that is currently acting as master will cause a fail-over to the standby pair of fabric controller/Management Interface modules.

It takes up to 3 seconds for the standby fabric controller to become a new master.

a.If you are removing a fabric controller card from a node slot, the card will be located in slots 9, 10, 13, and 14 (marked on the chassis).

b.If you are removing a fabric controller card from a core slot, the card will be located in slots 11 or 12.

Removing a Fabric Controller

1.Ground yourself appropriately.

2.Verify that you have a means of covering the slot before removing the module. Do not remove the module unless you have a replacement or a blanking panel for the slot, as overheating may occur.

3.Remove the bezel cover from the front of the switch.

4.Determine whether the Fabric Controller you want to remove is installed in a Core slot or a Node slot. Refer to Figure 1-1for a diagram of the chassis.

If you are removing a Fabric Controller from one of the core slots, make sure that the redundant core Fabric Controller is functional.

Removal of the Fabric Controller currently acting as master will cause a fail-over. It takes up to 3 seconds for the standby fabric controller to become a new master.

Image 42
Contents Part Number OL-7725-01 Product ID Page Regulatory Notices Vii Managing Individual Components Monitoring the Topspin 270 System 107 FCC Statement Safety Information Electrical CautionsViii Contact Information General CautionsPage System Architecture Hot StandbyHi-Availability InfiniBand ConnectivityFlexibility HardwareNon-Blocking Architecture Diagram of the ChassisAbout the Topspin 270 Chassis Fabric2Back Chassis View Chassis Slot Numbering 3Chassis Slot Numbering in Front Non-port SideConnections DimensionsPower Supplies LEDsFan Trays Management Interface ModulesMaster/Slave and Standby Roles Fabric Controller ModulesNode and Core Slots Node SlotChassis ID Module Rack AlarmLine Interface Modules LIM How the Chassis ID is UsedAdministrative Features Prepare the Site Read the Cautionary StatementsPrepare the Physical Environment for Topspin 270 System Rack Mount Installation Mount the Topspin 270 Chassis in a RackRequirements 2Unscrew Extra Rack Ears from the Chassis 3Chassis Set onto Shelf Install Optional HA Components 5Use Appropriate Screws to Attach Rack Ears to RailsConnect Management Devices Attach a Serial Console Cable to a PC or TerminalRecommended Management Configuration Power on the ChassisConnect an Ethernet Cable to the Ethernet Management Port Configure Basic Connectivity 8Power Jack LocationsAssigning an Address Statically Topspin-270config#interface mgmt-ethernetTopspin-270#copy running-config startup-config Assigning an Address DynamicallyAbout Connectors Connect Network DevicesConnecting InfiniBand Devices Manage the SystemOptional Launch the Chassis Manager Prepare Your DeviceLaunch Chassis Manager 10Web Browser Window Optional Install the Element Manager GUI About a Failed Power Supply Power Supply ModulesAbout the Power Supply Modules About the Field Replaceable UnitsRemoving a Power Supply Module Locating the Power Supply ModulePower Cord back Power Supply front Installing a New Power Supply Module 3Pulling the Power Supply Module from the BayRemoving a Fan Module Fan Tray ModulesAbout the Fan Tray Modules About a Failed Fan Tray5Loosening Captive Screws Installing a Fan Module 7Pushing Fan Module into SlotFabric Controllers About the Fabric ControllersRemoving a Fabric Controller 9Loosen Captive Screws Before Removing Installing a Fabric Controller Upgrading the Controller CardLine Interface Management Modules LIM About LIM CardsRemoving a LIM Card 12Removing a Pinch-Type Connector 14Loosen the Captive Screws Installing a LIM Module 17Closing the LIM Module LeversRemoving a Management Interface Module Management Interface ModulesAbout Management Interface Modules About a Failed Management Interface ModuleAbout Chassis ID Modules Installing a Management Interface ModuleChassis ID Modules Removing a Chassis ID Module20Loosen the Captive Screws Installing a Replacement Chassis ID Module Upgrade all Cards in a Chassis Upgrading a Topspin 270 with the CLISelect Maintenance File Management Upgrading a Topspin 270 with Element ManagerSelect Maintenance Boot Config Upgrading an Individual Controller Card Upgrading a Topspin 270 with the Chassis ManagerUpgrading a Controller Card with the CLI Show the standby Controller card Upgrading Individual Node Cards Upgrading a Node Card with the CLI5Copy the .img File to Server Switch Upgrading a Node Card with Element Manager6Watching the File Copy Progress 8Disable and Enable the Node Cards Upgrading Node Cards with the Chassis Manager Page Monitoring the Topspin 270 System Interpreting the Front Panel LEDsSystem-Wide Status LED Locating the System-Wide Status LEDInterpreting the System Status LED Power Supply LEDs Locating the Power Supply LEDsInterpreting the Power Supply LEDs 3Power Supply Identify LEDFan LEDs LocationInterpreting the Fan LEDs Fabric Controller LEDs Interpreting the Fabric Controller LEDsInterpreting the Back Panel LEDs Management Interface Module LEDsInterpreting the Management Interface LEDs 6Management Interface Module LEDsFan Tray Module Status LEDs Chassis ID LEDs Master Management Connection Status LEDLIM Status LEDs InfiniBand Port LEDsInterpreting the LIM Status LEDs Monitoring the System with Chassis Manager Monitor the DeviceInterpreting the InfiniBand Port LEDs Device Rear View and the Device Front View appear 11Chassis Manager 270 Device Front View Monitor the Cards 12Chassis Manager Cards WindowMonitor the InfiniBand Ports 13Chassis Manager Ports WindowMonitor the Power Supplies 14Chassis Manager Port Properties Dialog Box15Chassis Manager Power Supplies Window Monitor the FansMonitor the Temperature 17Chassis Manager Sensors WindowMonitoring the System with Element Manager Interpreting the Summary TabInterpreting the Power Supplies Tab Interpreting the Fans TabInterpreting the Sensors Tab Monitor the System With the CLI Monitor the Power SuppliesTopspin-270show power-supply Monitor the FansMonitor the Sensors Show sensorPage About Diagnostic Tests LED TestsSelf Tests Topspin-270#show diagnostic card Run Card TestsRun a Card Self-Test Example of completed test Run Chassis Tests Topspin-270# more sysloghwiflogTopspin-270config#diag chassis test standard Run a Chassis Standard TestRun Fan Tests Run a Self-Test on a FanTopspin-270#show diag post Enter the diag fan id command Run Power Supply Tests Run a LED Test on the Power SupplyTopspin-270#show diag fru-error Run a Self-Test on a Power Supply Topspin-270#show power-supplyTopspin-270#show diag power-supply Topspin-270#show diag fru-error Displaying Hardware Errors Topspin-270#show diagnostic postTopspin-270#more sysloghwiflog Error Types Topspin-270#show diagnostic fru-error101 102 Specifications and Compliance Certifications Chassis and Management InterfaceEMC/Immunity Electrical SpecificationsSafety AcousticsProduct Markings 106 Index

SFS 7008 specifications

The Cisco Systems SFS 7008 is a powerful storage solution designed to address the diverse and demanding needs of modern data environments. As organizations continue to generate and store vast amounts of data, the SFS 7008 delivers robust performance and scalability, making it a key player in high-performance computing (HPC) and enterprise data centers.

One of the main features of the SFS 7008 is its exceptional scalability. It supports a broad range of storage capacities, allowing organizations to easily expand their storage as their data requirements grow. This scalability ensures that businesses can adapt to changing workloads without significant disruption or the need for a costly overhaul of their storage infrastructure.

The SFS 7008 utilizes advanced technologies to optimize performance and efficiency. It employs a high-speed interconnect architecture that enables faster data transfer rates across multiple nodes. This feature is particularly beneficial for applications that require rapid access to large datasets, such as big data analytics and machine learning workloads. Moreover, the system supports multiple data protocols, including NFS, SMB, and iSCSI, making it versatile enough to handle various types of applications in diverse environments.

Another notable characteristic of the SFS 7008 is its data management capabilities. It features built-in tools that facilitate data replication, snapshotting, and backup, ensuring that organizations can maintain data integrity and availability at all times. These tools are essential for disaster recovery and provide peace of mind for businesses that rely on critical data for their operations.

Furthermore, the SFS 7008 is designed with security in mind. The system incorporates advanced security features that protect sensitive data from unauthorized access and breaches. These include encryption options and comprehensive access control mechanisms, allowing administrators to implement strict governance policies for data usage.

In summary, the Cisco Systems SFS 7008 stands out as a leading storage solution with its scalability, performance optimization, versatile protocol support, robust data management features, and enhanced security measures. As businesses continue to navigate the complexities of data management in today’s digital landscape, the SFS 7008 provides a reliable foundation for their storage needs, enabling them to harness the full potential of their data. This makes it an ideal choice for organizations seeking a future-proof storage solution.