Chapter 3: Installation and Initial Setup
i.
PC Network Settings
IP Address = 192.168.0.1
Subnet Mask = 255.255.0.0
Default Gateway = 192.168.0.100
Change the Modbus Hardened Serial Server’s network settings to:
IP Address = 192.168.0.50
Subnet Mask = 255.255.0.0
Default Gateway = 192.168.0.100
j. Save the settings and remove power from the Modbus Hardened Serial Server.
k.
3.4.4 Configuring the LES431A Modbus Hardened Serial Server via the Serial Port
Your Modbus Hardened Serial Server can be configured via a serial port using Modbus Hardened Serial Server Manager. To use this feature, the Modbus Hardened Serial Server's serial port must be connected to the serial port of a PC (using a
Null-modem
cable
PC
Modbus Hardened
Serial Server
(LES431A)
Figure 3-33. Console Mode Setup.
To configure the Modbus Hardened Serial Server, use the Mode switch to put it into Console Mode.
To enter Console Mode, press and hold the Mode switch for between two and ten seconds. The LED indicators respond as follows:
1.The Ready LED blinks three times per second while the button is being pressed.
2.The Modbus Hardened Serial Server is in Console Mode when Port 1 LED is On and the Ready LED is Off.
Page 35 |