Chapter 7: Modbus Help
7. Modbus Help
7.1 Modbus ASCII/RTU Basics
The Modbus protocol emerged in the
de facto standard in the industry. It supports asynchronous
The original Modbus specification included two possible transmission modes: ASCII and RTU. Modbus RTU mode is the most common implementation, using binary coding and CRC
All Modbus communications are initiated by Modbus masters using a polling query/response format. The master can send broadcast messages (using a slave address of 0), which all slaves accept, but do not reply to. More commonly, the master polls individual slaves sequentially. In each poll, it sends a message containing a device address, followed by a function code, any data that may be required, and an error check field. The addressed slave responds with a similar message structure. Typically, it repeats back its address and the function code, and then sends a field indicating the number of bytes of data it is sending, followed by the data and the error check field.
Slave addresses can range from 1 to 247. Function codes include several common ones typically used in all applications and additional ones that may be implemented in specific cases. Common function codes include: Read Coil Status (01), Read Input Status (02), Read Holding Registers (03), and Read Input Registers (04).
When a master sends a message to a slave, it expects to receive a valid response within a certain length of time. If the slave does not receive the message, or if the slave receives the message but an error is detected, it does not respond. If the slave cannot respond appropriately for some other reason (e.g. it does not recognize the function code), it will return a message containing an exception response.
7.2 Hints and Tips
A few simple suggestions that may assist you if your system is experiencing problems include:
•Slowing down the polling rate may be helpful if power cycling doesn’t cure the problem.
•A common misperception is that every serial network must terminate with a resistor. While this was true of early serial network configurations, it’s typically the wrong
A sometimes difficult problem is the difference in grounding voltage between various network locations. Stray voltage from lightning or other sources may also find its way onto the network. These conditions make isolation necessary in many settings.
Page 52 |