FieldServer FS-8700-43 instruction manual Vesda data format for command 4 Zone Update

Page 11

FS-8700-43 VESDA Driver Manual

Page 11 of 18

4.5.2.VESDA data format for command 4 (Zone Update)

This request returns the Current Zone Status in a BIT data array. The format for the data is as follows:

Data Arrays

 

Column Title

Function

 

Legal Values

 

Data_Array_Name

Provide name for Data Array

 

Up to 15 alphanumeric

 

 

characters

 

 

 

 

 

Data_Format

Provides data format

 

BIT

 

Data_Array_Length

Number of Data Objects

1 - 16

 

 

 

 

 

Client Side Map Descriptors

 

Column Title

 

Function

 

Legal Values

 

 

Map_Descriptor_Name

 

Name of this Map

 

Up to 32 alphanumeric

 

 

 

Descriptor

 

characters

 

 

 

Name of Data Array where

 

 

 

 

Data_Array_Name

 

data is to be stored in the

 

As above.

 

 

 

FieldServer

 

 

 

 

Data_Array_Location

 

Starting location in Data

0 -16

 

 

 

Array

 

 

 

 

 

 

 

 

Function

 

Function of Client Map

 

RDBC

 

 

Descriptor.

 

 

 

 

 

 

 

 

 

 

Name of Node to fetch data

 

One of the node names

 

Node_Name

 

 

specified in “Client Node

 

 

from

 

 

 

 

 

Descriptor” above

 

 

 

 

 

 

Data_Type

 

Data type

 

dig_input

 

Length

Length of Map Descriptor

 

1-16 (must not overflow the

 

 

data array)

 

 

 

 

 

 

Address

 

Starting address of read

1-16

 

 

 

block

 

 

 

 

 

 

 

 

Command

 

The command id as given in

4

 

 

 

 

the notes.

 

 

 

 

Network

 

The network number

1-255

 

 

Zone

The zone number

1-255

 

 

Sector

 

The sector number

1-255

 

Data Block Description2

BIT offset

Function

BIT offset

Function

0

Other Zone Info

8

Fault Power

1

Scanning

9

Fault Urgent

2

Autolearning

10

Fault Zone

3

Normalising

11

Fault System

4

Isolated

12

Alarm Fire2

5

Fault Filter

13

Alarm Fire1

6

Fault Airflow

14

Alarm Action

7

Fault Network

15

Alarm Alert

21 indicates TRUE; 0 indicates FALSE

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 11
Contents FS-8700-43 Vesda Table of Contents FS-8700-43 Vesda Driver Manual Vesda DescriptionTechnologies Provided by Supplier of 3rd Party TechnologyFieldServer Hardware Connections Column Title Function Legal Values Configuring the FieldServer as a Vesda ClientData Arrays Section TitleClient Side Connection Descriptors Client Side Node DescriptorsDriver Related Map Descriptor Parameters Vesdahli Map Descriptor ExampleData Arrays Column Title Function Legal Values Vesda data format for command 1 Set OperationCommon Applications and Examples Data Block Description2 BIT offset Function Vesda data format for command 4 Zone UpdateData Block Description BIT offset Function Vesda data format for command 6 Remote InputData Array Column Title Function Legal Values Client Map Descriptors Column Title Function Legal ValuesData Block Description Byte offset Function Vesda data format for command 12 Current Fault StatusVesda data format for command 10 Update Display Status Data Block 2 Description Float offset Function Vesda data format for command 16 Update Airflow Status Reading Smoke Levels on the Vesda Panels Vesda Panel start-up delayZone setup Sector setupThis page Intentionally Left Blank