FieldServer FS-8700-43 Reading Smoke Levels on the Vesda Panels, Vesda Panel start-up delay

Page 17

FS-8700-43 VESDA Driver Manual

Page 17 of 18

Data Block 1 Description7

 

 

BIT offset

 

Function

 

0

 

Pipe1 status

 

1

 

Pipe2 status

 

2

 

Pipe3 status

 

3

 

Pipe4 status

Data Block 2 Description

 

 

BYTE offset

 

Function

 

0

Airflow in pipe 1 as percentage of normalised pipe airflow.

 

1

Airflow in pipe 2 as percentage of normalised pipe airflow.

 

2

Airflow in pipe 3 as percentage of normalised pipe airflow.

 

3

Airflow in pipe 4 as percentage of normalised pipe airflow.

4.5.7.Reading Smoke Levels on the VESDA Panels

The Vesda panel only allows the driver to read the average Smoke Level on all the ports. Polling for individual sector smoke levels will always return a value of zero.

Zone setup

If the zone on the Panel has not been configured the zone must be set to zero in the FieldServer configuration file.

Sector setup

Setting the sector to zero will allow the driver to poll for the average smoke level.

4.5.8.VESDA Panel start-up delay.

When the HLI is powered on the FieldServer will not be able to communicate with the Panel for 10 to 30 seconds. During this time the HLI starts up its application code and initializes various internal parameters.

71 indicates OPEN; 0 indicates CLOSE

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 17
Contents FS-8700-43 Vesda Table of Contents FS-8700-43 Vesda Driver Manual Vesda DescriptionTechnologies Provided by Supplier of 3rd Party TechnologyFieldServer Hardware Connections Data Arrays Configuring the FieldServer as a Vesda ClientSection Title Column Title Function Legal ValuesClient Side Connection Descriptors Client Side Node DescriptorsDriver Related Map Descriptor Parameters Vesdahli Map Descriptor ExampleData Arrays Column Title Function Legal Values Vesda data format for command 1 Set OperationCommon Applications and Examples Data Block Description2 BIT offset Function Vesda data format for command 4 Zone UpdateData Array Column Title Function Legal Values Vesda data format for command 6 Remote InputClient Map Descriptors Column Title Function Legal Values Data Block Description BIT offset FunctionData Block Description Byte offset Function Vesda data format for command 12 Current Fault StatusVesda data format for command 10 Update Display Status Data Block 2 Description Float offset Function Vesda data format for command 16 Update Airflow Status Zone setup Vesda Panel start-up delaySector setup Reading Smoke Levels on the Vesda PanelsThis page Intentionally Left Blank