FieldServer FS-8700-43 Configuring the FieldServer as a Vesda Client, Data Arrays, Section Title

Page 6

FS-8700-43 VESDA Driver Manual

Page 6 of 18

4.Configuring the FieldServer as a VESDA Client

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Vesda Server.

4.1.Data Arrays

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Vesda communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes” section, and the data required from the servers needs to be mapped in the “Client Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

 

Section Title

 

 

 

Data_Arrays

 

 

 

Column Title

Function

Legal Values

 

Data_Array_Name

Provide name for Data Array

Up to 15 alphanumeric

 

characters

 

 

 

 

Data_Format

Provides data format

BIT,FLOAT,BYTE

 

Data_Array_Length

Number of Data Objects

1-10000

 

 

 

 

 

Example:

 

 

 

 

 

 

 

// Data Arrays

 

 

 

Data_Arrays

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

set_op,

bit,

32

 

VESDA01_1_f,

float,

32

 

VESDA01_1_b,

bit,

32

 

VESDA01_2_f,

float,

32

 

VESDA01_2_b,

bit,

32

 

VESDA01_3_f,

float,

32

 

VESDA01_3_b,

bit,

32

 

VESDA01_4_f,

float,

32

 

VESDA01_4_b,

bit,

32

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 6
Contents FS-8700-43 Vesda Table of Contents Vesda Description FS-8700-43 Vesda Driver ManualProvided by Supplier of 3rd Party Technology FieldServerTechnologies Hardware Connections Section Title Configuring the FieldServer as a Vesda ClientData Arrays Column Title Function Legal ValuesClient Side Node Descriptors Client Side Connection DescriptorsDriver Related Map Descriptor Parameters Map Descriptor Example VesdahliVesda data format for command 1 Set Operation Common Applications and ExamplesData Arrays Column Title Function Legal Values Vesda data format for command 4 Zone Update Data Block Description2 BIT offset FunctionClient Map Descriptors Column Title Function Legal Values Vesda data format for command 6 Remote InputData Array Column Title Function Legal Values Data Block Description BIT offset FunctionVesda data format for command 12 Current Fault Status Data Block Description Byte offset FunctionVesda data format for command 10 Update Display Status Data Block 2 Description Float offset Function Vesda data format for command 16 Update Airflow Status Sector setup Vesda Panel start-up delayZone setup Reading Smoke Levels on the Vesda PanelsThis page Intentionally Left Blank