FieldServer FS-8700-43 instruction manual Data Block 2 Description Float offset Function

Page 15

FS-8700-43 VESDA Driver Manual

Page 15 of 18

Data Block 1 Description6

 

 

BIT offset

Function

 

0

 

Reserved Flash

 

1

 

Fault Filter Flash

 

2

 

Fault Airflow Flash

 

3

 

Fault Network Flash

 

4

 

Fault Power Flash

 

5

 

Fault Urgent Flash

 

6

 

Fault Zone Flash

 

7

 

Fault System Flash

 

8

 

OK Flash

 

9

 

Isolate Flash

 

10

 

Fault Minor Flash

 

11

 

Fault Major Flash

 

12

 

Alarm Fire2 Flash

 

13

 

Alarm Fire1 Flash

 

14

 

Alarm Action Flash

 

15

 

Alarm Alert Flash

 

16

 

Reserved

 

17

 

Fault Filter

 

18

 

Fault Airflow

 

19

 

Fault Network

 

20

 

Fault Power

 

21

 

Fault Urgent

 

22

 

Fault Zone

 

23

 

Fault System

 

24

 

OK

 

25

 

Isolate

 

26

 

Fault Minor

 

27

 

Fault Major

 

28

 

Alarm Fire2

 

29

 

Alarm Fire1

 

30

 

Alarm Action

 

31

 

Alarm Alert

Data Block 2 Description

 

 

FLOAT offset

 

Function

 

0

 

Average Smoke Level (Sector must be set to zero)

61 indicates TRUE; 0 indicates FALSE

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 15
Contents FS-8700-43 Vesda Table of Contents FS-8700-43 Vesda Driver Manual Vesda DescriptionProvided by Supplier of 3rd Party Technology FieldServerTechnologies Hardware Connections Column Title Function Legal Values Configuring the FieldServer as a Vesda ClientData Arrays Section TitleClient Side Connection Descriptors Client Side Node DescriptorsDriver Related Map Descriptor Parameters Vesdahli Map Descriptor ExampleVesda data format for command 1 Set Operation Common Applications and ExamplesData Arrays Column Title Function Legal Values Data Block Description2 BIT offset Function Vesda data format for command 4 Zone UpdateData Block Description BIT offset Function Vesda data format for command 6 Remote InputData Array Column Title Function Legal Values Client Map Descriptors Column Title Function Legal ValuesData Block Description Byte offset Function Vesda data format for command 12 Current Fault StatusVesda data format for command 10 Update Display Status Data Block 2 Description Float offset Function Vesda data format for command 16 Update Airflow Status Reading Smoke Levels on the Vesda Panels Vesda Panel start-up delayZone setup Sector setupThis page Intentionally Left Blank