FieldServer FS-8700-43 instruction manual Vesda data format for command 6 Remote Input

Page 12

FS-8700-43 VESDA Driver Manual

Page 12 of 18

4.5.3.VESDA data format for command 6 (Remote Input)

This command sends the Remote Input in a BIT data array.

Data Array

 

 

Column Title

 

Function

 

Legal Values

 

 

Data_Array_Name

 

Provide name for Data

 

Up to 32 alphanumeric

 

 

 

Array

 

characters

 

 

 

 

 

 

 

Data_Format

 

Provides data format

 

BIT

 

 

Data_Array_Length

Number of Data Objects

1 - 8

Client Map Descriptors

 

Column Title

 

 

Function

Legal Values

 

Map_Descriptor_Name

 

Name of this Map

Up to 32 alphanumeric

 

 

 

Descriptor

characters

 

 

 

Name of Data Array where

 

 

Data_Array_Name

 

data is to be stored in the

As above.

 

 

 

FieldServer

 

 

Data_Array_Location

 

Starting location in Data

0 –8

 

 

Array

 

 

 

 

 

Function

 

Function of Client Map

WRBX

 

 

Descriptor.

 

 

 

 

 

 

 

Name of Node to fetch data

One of the node names

 

Node_Name

 

specified in “Client Node

 

 

from

 

 

 

Descriptor” above

 

 

 

 

 

 

Data_Type

 

Data type

dig_output

 

Length

 

Length of Map Descriptor

1-8 (must not overflow the

 

 

data array)

 

 

 

 

 

 

Address

 

Starting address of read

1-8

 

 

block

 

 

 

 

 

Command

 

The command id as given in

6

 

 

 

the notes.

 

 

Network

 

The network number

1-255

 

Zone

 

The zone number

1-255

 

Sector

 

The sector number

1-255

Data Block Description34

 

 

 

 

BIT offset

 

Function

 

0

 

 

Stop Test

 

 

1

 

 

Scan Start

 

 

2

 

 

Start Test

 

 

3

 

 

Silence

 

 

4

 

 

De-Isolate

 

 

5

 

 

Isolate

 

 

6

 

 

Reset

 

 

7

 

 

Reserved

 

31 indicates TRUE; 0 indicates FALSE

4ONLY 1 OF THE 8 BITS MAY BE SET IN ONE COMMAND

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 12
Contents FS-8700-43 Vesda Table of Contents Vesda Description FS-8700-43 Vesda Driver ManualProvided by Supplier of 3rd Party Technology FieldServerTechnologies Hardware Connections Configuring the FieldServer as a Vesda Client Data ArraysSection Title Column Title Function Legal ValuesClient Side Node Descriptors Client Side Connection DescriptorsDriver Related Map Descriptor Parameters Map Descriptor Example VesdahliVesda data format for command 1 Set Operation Common Applications and ExamplesData Arrays Column Title Function Legal Values Vesda data format for command 4 Zone Update Data Block Description2 BIT offset FunctionVesda data format for command 6 Remote Input Data Array Column Title Function Legal ValuesClient Map Descriptors Column Title Function Legal Values Data Block Description BIT offset FunctionVesda data format for command 12 Current Fault Status Data Block Description Byte offset FunctionVesda data format for command 10 Update Display Status Data Block 2 Description Float offset Function Vesda data format for command 16 Update Airflow Status Vesda Panel start-up delay Zone setupSector setup Reading Smoke Levels on the Vesda PanelsThis page Intentionally Left Blank