Appendix B. Carrier DataLink Device Error Response

The following notes are provided from the protocol specification.

Message

Explanation

Action

 

 

Check the spelling of the

#1 Invalid

The last command sent to the DataLink

command and verify that it

Command

device is not recognized.

contains the required

 

 

parameters.

 

 

Check the spelling of the table

#2 Invalid or Non-

The specified table does not exist in the

name(s). If using a WV or RV

command; verify that the table

Existent Table

specified element.

contains the specified

 

 

 

 

variables.

 

A Communication error has occurred

 

#3 Level II

due to other activity on the CCN

Verify the COMM2 connector

Communications

communication bus, a system element

is not disconnected and retype

Error

failure, or an incorrect address. The

the command.

 

command will not be executed.

 

 

 

Verify that the correct bus and

#6 Device Not

The specified system element’s bus and

element number have been

the element number were not found in

entered in the DTP-CONFG

Configured

the DTP-CONFG table.

table corresponding to the

 

 

 

device number.

 

 

Check the spelling of the

#7 Variable Does

The variable does not exist in the

variable name and verify that

Not Exist

specified table.

the CCN variable exists in the

 

 

specified system element.

#8 Invalid Data

The data was in an incorrect format.

Verify the format of the data.

#9 Access

An attempt was made to read or write to

Check variable.

a table or variable type that is not

Restricted

supported by the DataLink device.

 

 

 

#10 Limits

The value that was typed is outside the

Verify the limits and adjust the

Exceeded

specified variable’s upper or lower limits

force value.

#11 Alarms Not

There are no alarms currently in the

Reissue the command at later

time or adjust the alarm

Available

alarm buffer.

priority level.

 

 

#12 Cannot Force

The CCN system element does not

Choose different variable.

allow write access to the specified

Variable

variable.

 

 

 

 

The 8-character point (variable) name

Check the spelling of the point

#13 Parameter Not

(variable) name and verify that

used in the RT or WT command does

Found

the point name exists in the

not exist.

 

specified system element.

 

 

 

The command was accepted but not

Retype the command after

#14 Level II

understood by the specified system

checking the force priority and

element, an attempt was made to write

after verifying that the correct

Communications

to or read a variable with a higher force

bus and element number is

NACK

level, or an attempt was made to write or

entered in the DTP-CONFG

 

 

read from a UT203 controller.

table.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 26 Contents
FS-8700-82 Carrier DataLink Table of Contents Carrier DataLink Description FS-8700-82 Carrier DataLinkProvided by Suppler of 3 rd Party Equipment FieldServer TechnologiesHardware Connections Section Title Configuring the FieldServer as a Carrier DataLink ClientData Arrays/Descriptors Column Title Function Legal ValuesNone Client Side Connection DescriptionsFS-8700-82 Carrier DataLink Example SecondRDBC, WRBC, Wrbx Client Side Node DescriptorsColumn Function Legal Values Title TZONE1’ Driver Related Map Descriptor ParametersTiming Parameters ‘EVERYTHING’Map Descriptor Example 1 Read a Table Map Descriptor Example 2 Read a Variable Map Descriptor Example 3 Write a VariableMap Descriptor Example 4 Write Day of Week DOW or Time Configuring the FieldServer as a Carrier DataLink Server Server Side Connection DescriptorsServer Side Nodes Driver Specific Map Descriptor Parameters Timing Parameters Map Descriptor Example As a server Driver Limitations and ExclusionsAs a client GeneralAppendix A. Advanced Topics Appendix A.1. Table Names Equipment Type Table NameFS-8700-82 Carrier DataLink Equipment Type Table Name Dadump DEV 02 Display Appendix A.3.2. Client reads a variable Appendix A.3. Map Descriptor Length ExplainedAppendix A.3.1. Client Reads a Table Appendix A.3.3. Client writes a variableAppendix A.4.2. Extending the List of Discrete State Words FS-8700-82 Carrier DataLinkPage 24Appendix A.4.5. Occupancy Strings / Values Appendix A.4.3. Time ValuesAppendix A.4.4. Numeric Values Appendix A.5. Timing ConsiderationsNack Appendix B. Carrier DataLink Device Error ResponseMessage Explanation Action Appendix C. Driver Notes Appendix C.1. Driver Stats DacarrierstatsOffset Description Everything Appendix D. Driver Error MessagesError Message Explanation FS-8700-82 Carrier DataLink Error Message Explanation This page Intentionally Left Blank