FieldServer FS-8704-09 SNMP instruction manual Trap Map Descriptors are then configured as below

Page 21

FS-8704-09 SNMP Driver Manual

Page 21 of 39

Non-COV Traps

The FieldServer can be configured to send a trap periodically or when a data is updated. A data update occurs when one protocol reads data from a remote device and the data is stored in a Data Array regardless of whether the data has changed or not. Each Trap Map Descriptor must specify the destination of the Trap by configuring a Remote_Client_Node_Descriptor, as shown in the example below. The OID to which the data value is to be bound in the Trap message is specified in the Map Descriptor.

First, the Trap destination Node is set up as follows:

Remote_Client_Node_Descriptors

 

 

 

Node_Name,

Node_ID,

Protocol,

Adapter,

IP_Address

NM_1,

1,

SNMP,

N1,

192.168.1.174

 

 

 

 

 

The Trap Map Descriptors are then configured as below:

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name,

Data_Array_Name, Data_Array_Offset,

Function,

Node_Name, SNMP_OID,

SNMP_Write_as_Trap,

Data_Type,

Length

PSU_Voltage_Alarm,

DA_AI3,

0,

Wrbx,

NM_1,

1.3.6.1.4.1.6347.1.1.0.0,

Yes,

Integer,

1

Wrbx to write on update.

Use Wrbc and add a Scan_Interval to have the trap send periodically.

This is what tells the driver that this is not a normal write and that the message should be sent as a trap.

Integer value or ASCII strings may be sent. If sending an ASCII string keep the length as one but note that the driver starts at the specified location and proceeds element by element of the Data Array building the string until it finds a zero which it regards as the marker for the end of string. If using Wrbx as the function the message is only sent when the 1st element is updated.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 9042 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 21
Contents Applicability & Effectivity Driver Manual FS-8704-09 Snmp VersionTable of Contents Integer Octetstream Timerticks String FS-8704-09 Snmp Driver Manual Snmp DescriptionMax Nodes Supported Required 3rd Party Hardware Station FS-8704-09 Snmp Driver Manual Hardware Connections3rd Party Nodes non-SNMP 3rd Party ClientSnmp Traps Data Arrays/DescriptorsSnmp FS-8704-09 Snmp Driver Manual Client Side Node Descriptors Timing Parameters Driver Related Map Descriptor ParametersRDBC, WRBC, Wrbx SnmpoidDAAI3 Rdbc FS-8704-09 Snmp Driver Manual Map Descriptor ExampleDAAI3 Wrbx OIDServer Side Data Arrays SNMPDA1SNMPDA2 Server Side Map Descriptors Server Side Node DescriptorsAppendix A.1.1. Trap Source IP Address DAAI3 Page FS-8704-09 Snmp Driver Manual Snmpoid 192.168.1.174 Status Normal Status LO Alarm Status HI Alarm Status Normal Status AlarmSNMPDA2 Snmptrap Appendix A.2.2. Polling for Integer bound DataTrap Map Descriptors are then configured as below Page TRAP-TYPE from RFC-1215 FIELDSERVER-MIB Definitions = BeginSnmp Comparison of Style2 to Style3 Comparison of Style1 to Style3 Sample Configuration File Style1 MIB File based on above configuration Style2 MIB File based on above configuration Style3 MIB File based on above configuration Style3 Traps Description Page FYI INTFYI MIB TrapERR SnmptypeseqFS-8704-09 Snmp Driver Manual State=%s FS-8704-09 Snmp Driver Manual UINT32