Lochinvar 1.5, 1.3 2Status Screen, 1 SMART TOUCH Status Screen, PC Program Instructions

Page 5
2Status Screen

PC Program Instructions

2Status Screen

Figure 2-1SMART TOUCH Status Screen

To monitor and record the operation of the heater, click on the Status tab along the top of the Main Screen window (FIG. 1-1, page 4). When using the SITECS937Lab program, you will need to choose which controller you wish to monitor. The Status Screen will appear (see FIG. 2-1 above). The screen is divided into several sections.

The Sensors section displays the current temperatures seen by the Inlet, Outlet, System Inlet, System Outlet, Tank, Outdoor, and Flue sensors. It also shows the delta T across the heat exchanger and the voltage being applied to the 0-10Vdc input (FIG. 2-1). The controlling sensor is shown below the items mentioned above. The default controlling sensor is the Outlet sensor. If a System Supply sensor is connected, the control will automatically use it as the controlling sensor.

Below the temperature readings are Derivative Flue and Derivative Outlet. These show how quickly these temperatures are changing. The control will take certain actions based on these values. For instance, if the outlet temperature rises too quickly, the control will force the heater to run at low fire. Finally, the 0-10Vdc input Voltage and Flame Current are shown.

To the right of the sensor temperature readings are the various setpoints. The SH setpoint is the setpoint the SMART TOUCH uses during a space heating call for heat. Note that this setpoint will depend upon the outdoor temperature if the outdoor air sensor is connected. When the 0-10Vdc input is used, this setpoint will vary with the input voltage if it is used to control the setpoint. The HW setpoint is the setpoint used when a Tank sensor is connected. The HW Mod Setpt is the outlet temperature setpoint used when heating an indirect HW tank. The dSP setpoint is not used. Below these is a check box indicating if Night Setback is active or not.

Below the Sensors section is the Inputs section (FIG. 2-1). This section displays the status of the Enable (SH Thermostat) Input, HW Thermostat, Manual Reset High Limit, Flow Switch/Low Water Cutoff (optional), Gas Pressure Switch, Louver Proving Switch (optional), Air Pressure Switch, Blocked Drain Switch, Auto Reset High Limit Switch, and the status of the SH and DHW demands from ModBus.

Next to the Inputs section is the Outputs section (FIG. 2-1). This section shows the status of the Boiler (secondary) pump, System (primary) Pump, HW Pump, Blower, Gas Valve, Run-time Contacts, and Alarm Contacts.

5

Image 5
Contents SYNC - PCP Rev A ModelsSave this manual for future reference PC PROGRAM INSTRUCTIONS FOR THE SYNCContents Program installation 1InstallationUSB installation Program setupStarting the program Figure 1-3 Password WindowFigure 1-1 SMART TOUCH PC Main Screen Figure 1-2 Sitecs937Lab Main ScreenPC Program Instructions 2Status ScreenFigure 2-1 SMART TOUCH Status Screen PC Program Instructions Figure 2-1 continued2Status Screen PC Program Instructions 3Graphics ScreenFigure 3-1 SMART TOUCH Graphics Screen PC Program Instructions 4Fault History ScreenFigure 4-1 Fault History Screen PC Program Instructions 5Cascade ScreenFigure 5-1 Cascade Screen 6Parameters Set 1 System Setup Set 2 Functional DataParameter information screens Set 4 Menu ValuesRamp delay settings Set 1 System setup6Parameters continued Changeable parametersBlock time switching boiler on/off Block time switching boiler onBlock time Switch On/Off 2nd burner HW Set 2 Functional DataFigure 6-5 Parameter Set 2E Set 4 Menu valuesFigure 6-6 Parameter Set 4A Space Heating SH user setpoint User SetpMax service time Max Serv t Shift OA reset curve Shift Air ResetSH off-ondifferential SH off/on df Offset HW setpoint to end HW demandCascade max SH step power based Max outl temp Time to switch between HW and SH SH/HW sw timConfig SH control Tank differential tempMaster controlled through ModBus Demand conf CascadeReload short time ModBus out of order Figure 6-8 Parameter Set 4DRunning hours for service reminder Serv NotRun h No. of months for service reminder Serv Not timeBurner cycles for service reminder Serv Not cycl Figure 6-10 Parameter Set 4FBMS Power at min voltage BMS mod @minV Figure 6-11 Outdoor Air Reset CurveBMS Power at max voltage BMS mod @maxV Figure 6-12 Parameter Set 4GBMS Voltage at max power BMS V @max mod BMS Voltage at min power BMS V @min modBMS Demand Enable 1 Voltage Storing parameters on your PCRevision Notes Revision A initial release
Related manuals
Manual 16 pages 3.68 Kb Manual 12 pages 30.87 Kb Manual 56 pages 20.39 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 56 pages 40.75 Kb Manual 80 pages 59.46 Kb Manual 56 pages 36.01 Kb

1.5, 1.3, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.