Lochinvar 1.5, 1.3 No. of months for service reminder Serv Not time, 10 Parameter Set 4F

Page 17
No. of months for service reminder (Serv Not time)

PC Program Instructions

6Parameters (continued)

No. of months for service reminder (Serv Not time)

When the boiler control determines that a scheduled service is due based on days of installation, the boiler display will show a “Maintenance Required” screen. This parameter is adjustable by accessing parameter 4EA. The time range for this parameter is 0 months to 36 months. The default time is 12 months.

Running hours for service reminder (Serv NotRun h)

When the boiler control determines that a scheduled service is due based on the hours of actual operation, the boiler display will show a “Maintenance Required” screen. This parameter is adjustable by accessing parameter 4EB. The time range for this parameter is 0 hours to 100,000 hours. The default time is 10,000 hours.

Burner cycles for service reminder (Serv Not cycl)

When the boiler control determines that a scheduled service is due based on the number of boiler cycles, the boiler display will show a “Maintenance Required” screen. This parameter is adjustable by accessing parameter 4EC. The range for this parameter is 0 cycles to 100,000 cycles. The default is 10,000 cycles.

To adjust the Outdoor Air Reset curve, click on the tab labeled 4F OA Reset Curve (see FIG. 6-10 below).

Figure 6-10Parameter Set 4F

OA reset water temp at min outdoor temp (4FC) (Reset T Lo Out)

When the outdoor air temperature drops to its minimum setting (4FC), the water temperature setpoint will be at this value. However, if the SH user setpoint (4AA) is lower, it will override this setting. If the SH user setpoint is higher, the water temperature setpoint will continue to climb as the outdoor temperature drops below 4FC. This parameter can be changed by accessing parameter 4FA. The temperature range of this parameter is 0°F (-18°C) to 190°F. (88 °C). The default value is 180°F (82°C), (FIG 6-11, page 18).

OA reset water temp at max outdoor temp (4FD) (Reset T Hi Out)

When the outdoor air temperature rises to or above its maximum setting (4FD), the water temperature setpoint will be at this value. This parameter can be changed by accessing parameter 4FB. The temperature range of this parameter is 0°F (-18°C) to 190°F (88°C). The default value is 70°F (21°C), (FIG 6-11, page 18).

OA reset outdoor temp at max water temp (4FA) (Out T Hi Reset)

When the outdoor air temperature drops to this point, the water temperature setpoint will be at the setting given by parameter 4FA (if not overridden by the SH user setpoint). This parameter can be changed by accessing parameter 4FC. The temperature range of this parameter is -30°F (-34°C) to 90°F (32°C). The default value is 25°F (-4°C), (FIG 6-11, page 18).

OA reset outdoor temp at min water temp (4FB) (Out T Lo Reset)

When the outdoor air temperature rises to or above this point, the water temperature will be at its minimum setpoint. This parameter can be changed by accessing parameter 4FD. The temperature range of this parameter is -30°F (-34°C) to 90°F (32°C). The default value is 70°F (21°C), (FIG. 6-11, page 18).

Ramp delay (Ramp delay)

This parameter configures the ramp delay feature from off to on. This parameter can be changed by accessing parameter 4FE (FIG. 6-10). The control range of this parameter is 0 = Off, 1 = Ramp Up Only, and 2 = Ramp Up and Ramp Down. The default is 0.

Running hours for service reminder (Serv NotRun h) 17 Burner cycles for service reminder (Serv Not cycl)

Image 17
Contents SYNC - PCP Rev A ModelsSave this manual for future reference PC PROGRAM INSTRUCTIONS FOR THE SYNCContents Program installation 1InstallationUSB installation Program setupStarting the program Figure 1-3 Password WindowFigure 1-1 SMART TOUCH PC Main Screen Figure 1-2 Sitecs937Lab Main ScreenPC Program Instructions 2Status ScreenFigure 2-1 SMART TOUCH Status Screen PC Program Instructions Figure 2-1 continued2Status Screen PC Program Instructions 3Graphics ScreenFigure 3-1 SMART TOUCH Graphics Screen PC Program Instructions 4Fault History ScreenFigure 4-1 Fault History Screen PC Program Instructions 5Cascade ScreenFigure 5-1 Cascade Screen 6Parameters Set 1 System Setup Set 2 Functional DataParameter information screens Set 4 Menu ValuesRamp delay settings Set 1 System setup6Parameters continued Changeable parametersBlock time switching boiler on/off Block time switching boiler onBlock time Switch On/Off 2nd burner HW Set 2 Functional DataFigure 6-5 Parameter Set 2E Set 4 Menu valuesFigure 6-6 Parameter Set 4A Space Heating SH user setpoint User SetpMax service time Max Serv t Shift OA reset curve Shift Air ResetSH off-ondifferential SH off/on df Offset HW setpoint to end HW demandCascade max SH step power based Max outl temp Time to switch between HW and SH SH/HW sw timConfig SH control Tank differential tempMaster controlled through ModBus Demand conf CascadeReload short time ModBus out of order Figure 6-8 Parameter Set 4DRunning hours for service reminder Serv NotRun h No. of months for service reminder Serv Not timeBurner cycles for service reminder Serv Not cycl Figure 6-10 Parameter Set 4FBMS Power at min voltage BMS mod @minV Figure 6-11 Outdoor Air Reset CurveBMS Power at max voltage BMS mod @maxV Figure 6-12 Parameter Set 4GBMS Voltage at max power BMS V @max mod BMS Voltage at min power BMS V @min modBMS Demand Enable 1 Voltage Storing parameters on your PCRevision Notes Revision A initial release
Related manuals
Manual 16 pages 3.68 Kb Manual 12 pages 30.87 Kb Manual 56 pages 20.39 Kb Manual 52 pages 37.07 Kb Manual 16 pages 33.86 Kb Manual 56 pages 40.75 Kb Manual 80 pages 59.46 Kb Manual 56 pages 36.01 Kb

1.5, 1.3, 1 specifications

Lochinvar 1 is a remarkable achievement in the realm of modern technology and engineering. As a powerful and efficient water heater, it has been designed to cater to a wide range of residential and commercial needs. One of the standout features of Lochinvar 1 is its advanced heating technology, which incorporates a high-efficiency condensing design. This technology allows the unit to achieve impressive energy savings by maximizing heat transfer while minimizing energy consumption.

The Lochinvar 1 utilizes a stainless steel heat exchanger that enhances durability and corrosion resistance. This not only extends the lifespan of the unit but also ensures consistent performance over time. Coupled with a user-friendly control system, users can easily adjust settings and monitor performance, enhancing overall convenience and usability.

Another key characteristic of the Lochinvar 1 is its compact design, making it suitable for a variety of installation environments. Whether in a residential basement or a commercial utility room, the unit’s space-saving configuration allows for efficient use of available area without compromising on capability.

Safety features are integral to the Lochinvar 1, providing peace of mind for users. The unit is equipped with advanced monitoring systems that can detect irregularities and automatically shut down the system if necessary. This not only protects the equipment but also enhances the safety of the environment in which it operates.

In terms of performance, Lochinvar 1 boasts a high recovery rate, ensuring hot water is available on demand. This is particularly beneficial for settings with high water usage, allowing simultaneous operations without lag.

Moreover, the unit supports various venting options, offering flexibility during installation. Whether using traditional vertical venting or innovations like direct venting, Lochinvar 1 accommodates different building designs and local codes, making it highly versatile.

In conclusion, Lochinvar 1 epitomizes the melding of efficiency, reliability, and user-friendly technology. With its high-performance features, robust safety systems, and adaptable installation options, it stands out as a forefront player in the water heating industry, meeting the diverse needs of today's consumers and businesses alike.