Telenetics MIU Dial or Leased Line modem with RS-485 manual RS-232 Configuration Connector P2, Led

Page 4

3. MIU'S LED, SWITCH & SERIAL CONNECTOR SPECIFICATIONS

The CIU/485 communicates with industrial controllers through RS-485 compatible serial signaling. The RS-485 signal levels are used to interconnect with RS-485 compatible embedded controllers. The RS-232E signal levels are used to configure the CIU. The RS- 232E signal levels are also used to interconnect with RS-232E compatible embedded controllers if required.

The RS-232E is present on DB9(MIU), RS485 signal levels are available via four pins' connectors.

4.1The following lists the CIU/485 serial interfaces. All connector definitions are described in Appendix A

RS-232 Configuration Connector (P2)

 

 

Connector Type:

DB9, (MIU) female, straight board mounts.

 

 

Signal Levels:

RS-232

RS485

Configuration Connector (P1)

 

 

Connector Type:

4 pin terminal header with .138 spacing

 

 

Signal Levels:

RS485

3.2 MIU/485

LED

 

LED Blinks every 4 seconds with AC / DC power

3.3 MIU/485

LED & Switch 1 (internal)

S1-1

Closed (ON) LED Blinks with option CD (&C1 AT command) active

S1-2

Closed (ON) LED Blinks AC. DC Power ON Note select either 1 or 2

S1-3

Closed, option modem DTR

select DB9 DTR

S1-4 Closed, option modem DTR

select modem's CD

3.4 MIU/485 Switch S3 (external)

S3-2 Closed (ON) only for MIU/485 (J1) modem configuration or for RS232 embedded controllers.

S3-1,-3 &-4 Open (OFF)

S3-1 Closed (ON) only for MIU/485 (P1) RS485 connector (RS485 embedded controllers)

S3-2,-3 &m-4 Open (OFF)

3.5 MIU/485 A switch (external)

SA-1 Closed (ON) RS485 received data disable TX (Driver Output Enable) SA-2 Closed (ON) RS485 transmit data enable TX (Driver Output Enable) + 5ms SA-3 Closed (ON) RS485 RTS enable TX (Driver Output Enable) should be

Open (OFF)

SA-4 Closed (ON) RS485 received data is disables with TXD

Install Op and Diags for MIU Modems and RS485 (0049-0002-010A)

Page 2 of 16

Image 4
Contents Installation, Operation and Diagnostics Table of Contents Product Overview Product DescriptionMius LED, Switch & Serial Connector Specifications RS-232 Configuration Connector P2RS485 Configuration Connector P1 LEDSB-1 Closed on RS485 Received RX & /RX Power Connector P3 MIU Regulated Powe r Supply Range 48.0 to 220 Volts AC/DCEnvironmental Specifications Speed DistanceApprovals MIUXXX\485 Power Connection Sheet TWOMIUXXX/485 DIP Switch Setup Appendix A.CONNECTOR PIN Definitions Connector P2 RS-232 Configuration Connector DB9 MIUModule C-1 MIU S3 external Appendix C. Connector Diagostics RS485 Connection FailureDiagnostics RS485 Connection Failure