Cable Grounding and Termination

To maintain data transmission performance, network cabling must be terminated correctly. Termination requirements vary depending on the type of cable used for network connections – shielded or unshielded twisted pair - and the type of transceiver used.

Cable Grounding

The majority of LonWorks networks use twisted-pair wiring to interconnect the nodes, either shielded twisted pair (STP) or unshielded twisted pair (UTP). If shielded twisted pair wiring is used, the shield of the cable should be grounded as illustrated in Figure 1.

Shielded Twisted Pair

SHIELD GROUNDING CIRCUIT

470KW, 5%, ¼W

100nF, 100V, 10% Metallized Polyester

Figure 1. Cable Shield Grounding Circuit.

The 470KW resistor safely bleeds off any static charge on the cable’s shield, and the capacitor helps avoid DC and 50/60Hz ground paths from being formed through the shield. The cable shield should be grounded at least once per segment, and at each node if possible.

Cable Wiring and Termination

Termination of the network depends upon the type of transceiver used. In some installations, the termination circuit included on the LM104-P50 may be used; in others, it should not be used. The type of wire that may be used, per Echelon’s specifications, also varies by transceiver type.

Option 1 – RS-485

The RS-485-standard transceiver used in Option 1 boards specifies that a 120W, ¼ W resistor should be installed across the network connections (pins 2 and 3 on P3) at every node (see Figure 2).

7

Image 9
Contents LM104-P50 Table of Contents LM104-P50 Network Interface Options Product OverviewImportant Note Module SetupJP1 Service Jumper SettingsJP5 IRQ Select Device = Drive \PATH\ LM104INT.SYS Switches Software Driver InstallationDEVICE=C\LON\LM104INT.SYS /D1 /P1 /Q5 Cable Grounding and Termination Cable Wiring and TerminationCable Grounding Option 1 RS-485Termination of an LM104-P50-1 RS-485 network node Options 2 and 3 Twisted pair transceiversOption 6 Free Topology Transceiver Option 5 Power line carrier transceiversTroubleshooting Appendix a User ConnectorsMechanical EnvironmentalJ1/P1 J2/P2 Number Row a Row B Row C Row D Appendix BNo Connection NET Appendix CIRQ Select Appendix DConnectAir International Eastman Wire & Cable Windy City WireAppendix E Concerning Conformal Coatings Appendix FAppendix G PC/104 Specification, Version Echelon literatureAppendix H Standard Warranty ServiceWarranties Exclusive Limitation of Liability