Kohler 48RCL, 38RCL, 60RCL manual Exercising the Generator Set, Generator Set Operation

Page 16

2.3 Exercising the Generator Set

Operate the generator set without load every week or every other week for 20 minutes. Perform all of the prestart checks before starting the exercise procedure. See Section 2.5 for instructions to set the automatic exerciser.

2.4 Generator Set Operation

2.4.1Local Starting and Stopping

Start: Press the RUN button to immediately start the generator set.

Stop: Press the OFF button. The engine stops.

Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.

2.4.2Automatic Starting and Stopping

An automatic transfer switch monitors the utility power and signals the generator set to start when utility power is lost. The ATS then transfers the load to the generator set.

When utility power is restored, the transfer switch transfers the load back to utility, runs the generator set with no load to cool down the engine, and then stops the generator set engine. The electric fans continue to run for two minutes after the engine shuts down to evacuate the engine compartment.

2.4.3Remote Starting and Stopping

A remote switch connected to terminals 3 and 4 can be used to start and stop the generator set. Close the switch to start and run the generator set. Open the switch to stop the generator set.

Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.

2.4.4Engine Start Crank Cycle

The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off). If the generator set does not start in three attempts, the system shuts down on an overcrank fault. See Section 2.6.

Pressing the OFF button during the crank cycle stops the cranking. No other buttons are acknowledged during the crank cycle.

2.4.5Engine Cooldown

The engine cooldown time delay allows the engine to run after the loads have been removed.

The engine cooldown time delay is set to 5 minutes. The engine stops before the cooldown time delay expires if the temperature drops below the cooled-down temperature level, or if the temperature rises above the high limit during the cooldown cycle.

The electric fans continue to run for two minutes after the engine shuts down to evacuate the engine compartment.

If a transfer switch other than the Model RXT is used, an additional engine cooldown time delay may be programmed on the transfer switch. To allow the smart engine cooldown on the RDC2 controller to operate most efficiently, set the cooldown time on the transfer switch controller to zero or the minimum time allowed. Refer to the instructions provided with the transfer switch for more information.

2.4.6Automatic Operation with Model RXT Transfer Switch

The Model RXT transfer switch connects to the RDC2 controller through the ATS interface board on the transfer switch. Also see Section 2.7, Model RXT Transfer Switch Operation.

The RDC2 controller must be in AUTO mode for automatic transfer switch operation.

Automatic Start

The RDC2 controller receives utility source voltage sensing data from the Model RXT transfer switch.

1.If the utility source voltage falls below an acceptable level, the controller starts the engine start time delay.

2.If the utility source is not restored before the time delay expires, the generator set starts.

3.After the Normal-to-Emergency time delay, the ATS is signaled to transfer the load to the emergency source.

16 Section 2 Generator Set Operation

TP-6810 11/13

Image 16
Contents RDC2 TP-6810 11/13bAccessory Number Accessory Description Product Identification InformationController Identification Generator Set Identification NumbersTable of Contents Troubleshooting Scheduled MaintenanceAppendix a Abbreviations Safety Precautions and Instructions BatteryAccidental Starting Accidental starting Can cause severe injury or deathExhaust System Engine Backfire/Flash FireFuel System Hazardous noise Can cause hearing loss Hazardous NoiseHazardous voltage Will cause severe injury or death Hot Parts Heavy EquipmentHot coolant and steam Can cause severe injury or death Introduction NameplateList of Related Literature Literature Type Part NumberService Assistance Service Assistance TP-6810 11/13 Service Views NON-SERVICE Side260RCL Service Views Prestart Checklist Generator Set OperationOperating Area Keep the generator set area clear. Maintain at leastExercising the Generator Set Generator Set OperationAutomatic Operation with Model RDT or RSB Transfer Switches Unloaded Cycle Exercise with Complete System DiagnosticsSystem Diagnostics ExercisePower Failure During Exercise Exerciser ResetSetting the Exerciser at Power-up Unloaded Full-Speed ExerciseChanging the Exercise Setting Procedure to Change the Exercise Setting2RDC2 Main Menu 3Procedure to Set the Exerciser Faults Resetting the Controller after a Fault ShutdownATS Communication Errors Procedure to Reset the Controller after a Fault ShutdownFault Shutdown SD Condition Check 5Controller Fault Messages Model RXT Transfer Switch Operation Procedure to View Event HistorySetting Event LogTime Delays ATS Load Control Relay Time DelayATS Control Sequence of Operation Preferred Source FailsControls and Indicators RDC2 Controller OperationController Keypad LED Indicators ButtonButton Function LED OperationLCD Display Active AlertController Power Battery ChargingChanging Settings Procedure to Change SettingsChanging Settings on the RDC2 Controller 6Changing SettingsController Menus Main MenuOverview Menu Engine Metering MenuGenerator Metering Menu Voltage CalibrationGenerator Set Information Menu Genset Run Time MenuVoltage Regulator VR Voltage Adjust Setting the ExerciserAdjusting the Display Contrast Genset System MenuATS Status Menu 14ATS Status Menu, with CalibrationATS Configuration Menu Changing ATS Configuration SettingsDate and Time Menu Date and Time 02Dec2011 1234pm Time Format 12hr24hrNetworking Information Menus 17Networking Information MenuNetworking Status Submenu DhcpNetworking Configuration Submenu OnCue Password OnCue PasswordRbus Information Submenu 20RBUS Information SubmenuRemote Devices Submenu 21Remote Devices SubmenuProgrammable Interface Module PIM Menus Load Control Menus 23Load Control Status MenuScheduled Maintenance General MaintenanceService Schedule Every Operation DailyOil Specifications Lubrication SystemOil Check Oil AdditionsAir Cleaner Reset the maintenance timer on the RDC2Air Cleaner Service Procedure Check for leaksChecking and Filling Coolant Cooling SystemExhaust System Inspection Points Flushing and Cleaning Flushing and Cleaning ProcedureCooling System Inspection Draining Cooling SystemIgnition System Model Spark plug gap 38 RCL, 48RCL, and 60RCL511 Storage Procedure Scheduled Maintenance TP-6810 11/13 Troubleshooting Fault MessagesIntroduction USB PortGenerator Set Troubleshooting Problem Possible Cause Corrective ActionController Troubleshooting 2RDC2 Troubleshooting ChartTroubleshooting TP-6810 11/13 Appendix a Abbreviations AnsiLCB Page 2012, 2013 by Kohler Co. All rights reserved

38RCL, 48RCL, 60RCL specifications

The Kohler RCL series of generators, particularly the 60RCL, 48RCL, and 38RCL models, represents a premium choice for those seeking reliable power solutions for residential and light commercial applications. Each model is tailored to meet diverse power needs, ensuring uninterrupted electricity supply during outages.

The 60RCL is engineered for maximum performance, offering 60 kW of power. This model is ideal for larger homes or small businesses that require dependable backup power. Its powerful Kohler engine is designed to deliver a quiet, smooth performance, while the advanced sound-dampening features keep noise levels to a minimum. The 48RCL offers a slightly lower output at 48 kW, making it suitable for medium-sized homes. Its compact design allows for flexible installation options, whether it’s outdoors or in a utility area, while still providing robust power during critical times.

The 38RCL, while the smallest of the series with 38 kW output, is perfect for homes that need a reliable backup generator without the bulk. Its streamlined design does not compromise on performance, making it an excellent choice for energy-efficient homes. All models in the RCL series come equipped with Kohler's Command Pro commercial-grade engine, ensuring longevity and reliability even in the harshest conditions.

A standout feature of the RCL series is the integrated KOHLER® 2.4-inch color display, which allows users to monitor generator performance in real-time. This user-friendly interface provides vital information such as operational status, run time, and maintenance notifications. Additionally, the series is designed with automatic transfer switches that allow for seamless switching between utility and generator power.

Moreover, these generators incorporate advanced control systems with remote monitoring capabilities, enabling users to check the status of their power supply from a smartphone or tablet. Designed with efficiency in mind, the RCL series boasts a fuel-efficient operation that supports both natural gas and propane, catering to diverse energy preferences.

In summary, the Kohler 60RCL, 48RCL, and 38RCL generators combine high performance, advanced technology, and user-friendly features. They are reliable solutions for anyone looking to safeguard their power needs, ensuring peace of mind when it matters most.