Kohler 48RCL, 38RCL, 60RCL Changing the Exercise Setting, Procedure to Change the Exercise Setting

Page 19

2.Press Select button to save the year and move to the month.

3.Use the arrow and select buttons to set the month and the day.

4.The time is displayed with the hour flashing. Use the up or down arrow key to step to the current hour and am or pm setting.

Note: Check the am/pm setting displayed. If pm is displayed and you need to change it to am, use the down arrow button to step down in time until the correct hour and am are displayed.

5.Press the Select button to save the hour and move to minutes.

6.Use the up or down arrow button to change the minutes.

7.Press Select to save the time and move to the next screen.

8.Next Exercise is displayed. Use the up, down, and select buttons to set the exercise time and date. Be sure to set a time and date in the future.

9.Press Select. The controller exits the exercise menu.

10.Press the Auto button and verify that the AUTO LED is lit. The generator set must be in automatic mode for the exercise to run as scheduled.

The exercise will run every 7 days at the same time, starting on the date set. To change the exerciser to run every other week or on a different day and time, use the following procedure.

2.5.8Changing the Exercise Setting

Set the date and time on the controller before setting the exercise schedule. Set the exerciser to automatically run the generator set for 20 minutes every week or every two weeks. Follow the procedure below and see the flowchart in Figure 2-3 to set the exercise time and date, mode, and frequency.

Procedure to Change the Exercise Setting

1. Press the AUTO button on the controller.

2.Press the Select button to go to the main menu. See Figure 2-2.

3.Press the down arrow button to step to the Genset System menu.

4.Press the Select button to enter the Genset system menu. See Figure 2-3.

5.Use the down arrow button to step to the next Exercise menu.

6.Press the Select button. The setting flashes to show that it can be changed. For example, the hour flashes to show that the hour can be changed.

7.Press the UP or Down arrow buttons to change the setting.

8.Press the Select button to save the setting and move to the next. For example, save the hour setting and move to minutes.

9.Repeat steps 5 through 8 to change the next item on the line until the desired settings are displayed.

10.Press Select to save after all settings have been selected. Settings will stop flashing.

11.If the generator set is connected to a Kohlerr Model RXT transfer switch, the exercise can be changed to a loaded exercise. Set the Exercise Mode to loaded full speed, unloaded full speed, or unloaded cycle as shown in Figure 2-3.

12.Set the exercise frequency (weekly or every two weeks). Weekly exercises are recommended.

13.Press the down arrow button to step to the Return menu. Press the Select button to return to the main menu.

14.Check that the AUTO LED is lit. The generator set must be in automatic mode for the exercise to run as scheduled.

After a scheduled exercise run, the next exercise time and date will be updated automatically based on the Exercise Frequency setting.

Other transfer switches: For a loaded exercise with a transfer switch other than a Kohlerr Model RXT, program the exercise at the transfer switch controller. Refer to the transfer switch operation manual for instructions.

TP-6810 11/13

Section 2 Generator Set Operation 19

Image 19
Contents TP-6810 11/13b RDC2Generator Set Identification Numbers Accessory Number Accessory DescriptionProduct Identification Information Controller IdentificationTable of Contents Troubleshooting Scheduled MaintenanceAppendix a Abbreviations Accidental starting Can cause severe injury or death Safety Precautions and InstructionsBattery Accidental StartingExhaust System Engine Backfire/Flash FireFuel System Hazardous noise Can cause hearing loss Hazardous NoiseHazardous voltage Will cause severe injury or death Hot Parts Heavy EquipmentHot coolant and steam Can cause severe injury or death Nameplate IntroductionLiterature Type Part Number List of Related LiteratureService Assistance Service Assistance TP-6810 11/13 NON-SERVICE Side Service Views260RCL Service Views Keep the generator set area clear. Maintain at least Prestart ChecklistGenerator Set Operation Operating AreaGenerator Set Operation Exercising the Generator SetExercise Automatic Operation with Model RDT or RSB Transfer SwitchesUnloaded Cycle Exercise with Complete System Diagnostics System DiagnosticsUnloaded Full-Speed Exercise Power Failure During ExerciseExerciser Reset Setting the Exerciser at Power-upProcedure to Change the Exercise Setting Changing the Exercise Setting2RDC2 Main Menu 3Procedure to Set the Exerciser Procedure to Reset the Controller after a Fault Shutdown FaultsResetting the Controller after a Fault Shutdown ATS Communication ErrorsFault Shutdown SD Condition Check 5Controller Fault Messages Event Log Model RXT Transfer Switch OperationProcedure to View Event History SettingPreferred Source Fails Time DelaysATS Load Control Relay Time Delay ATS Control Sequence of OperationRDC2 Controller Operation Controls and IndicatorsLED Operation Controller Keypad LED IndicatorsButton Button FunctionActive Alert LCD DisplayProcedure to Change Settings Controller PowerBattery Charging Changing Settings6Changing Settings Changing Settings on the RDC2 ControllerMain Menu Controller MenusEngine Metering Menu Overview MenuVoltage Calibration Generator Metering MenuGenset Run Time Menu Generator Set Information MenuGenset System Menu Voltage Regulator VR Voltage AdjustSetting the Exerciser Adjusting the Display Contrast14ATS Status Menu, with Calibration ATS Status MenuChanging ATS Configuration Settings ATS Configuration MenuDate and Time 02Dec2011 1234pm Time Format 12hr24hr Date and Time Menu17Networking Information Menu Networking Information MenusDhcp Networking Status SubmenuOnCue Password Networking Configuration Submenu OnCue Password20RBUS Information Submenu Rbus Information Submenu21Remote Devices Submenu Remote Devices SubmenuProgrammable Interface Module PIM Menus 23Load Control Status Menu Load Control MenusGeneral Maintenance Scheduled MaintenanceEvery Operation Daily Service ScheduleOil Additions Oil SpecificationsLubrication System Oil CheckCheck for leaks Air CleanerReset the maintenance timer on the RDC2 Air Cleaner Service ProcedureChecking and Filling Coolant Cooling SystemExhaust System Inspection Points Draining Cooling System Flushing and CleaningFlushing and Cleaning Procedure Cooling System InspectionModel Spark plug gap 38 RCL, 48RCL, and 60RCL Ignition System511 Storage Procedure Scheduled Maintenance TP-6810 11/13 USB Port TroubleshootingFault Messages IntroductionProblem Possible Cause Corrective Action Generator Set Troubleshooting2RDC2 Troubleshooting Chart Controller TroubleshootingTroubleshooting TP-6810 11/13 Ansi Appendix a AbbreviationsLCB Page 2012, 2013 by Kohler Co. All rights reserved

38RCL, 48RCL, 60RCL specifications

The Kohler RCL series of generators, particularly the 60RCL, 48RCL, and 38RCL models, represents a premium choice for those seeking reliable power solutions for residential and light commercial applications. Each model is tailored to meet diverse power needs, ensuring uninterrupted electricity supply during outages.

The 60RCL is engineered for maximum performance, offering 60 kW of power. This model is ideal for larger homes or small businesses that require dependable backup power. Its powerful Kohler engine is designed to deliver a quiet, smooth performance, while the advanced sound-dampening features keep noise levels to a minimum. The 48RCL offers a slightly lower output at 48 kW, making it suitable for medium-sized homes. Its compact design allows for flexible installation options, whether it’s outdoors or in a utility area, while still providing robust power during critical times.

The 38RCL, while the smallest of the series with 38 kW output, is perfect for homes that need a reliable backup generator without the bulk. Its streamlined design does not compromise on performance, making it an excellent choice for energy-efficient homes. All models in the RCL series come equipped with Kohler's Command Pro commercial-grade engine, ensuring longevity and reliability even in the harshest conditions.

A standout feature of the RCL series is the integrated KOHLER® 2.4-inch color display, which allows users to monitor generator performance in real-time. This user-friendly interface provides vital information such as operational status, run time, and maintenance notifications. Additionally, the series is designed with automatic transfer switches that allow for seamless switching between utility and generator power.

Moreover, these generators incorporate advanced control systems with remote monitoring capabilities, enabling users to check the status of their power supply from a smartphone or tablet. Designed with efficiency in mind, the RCL series boasts a fuel-efficient operation that supports both natural gas and propane, catering to diverse energy preferences.

In summary, the Kohler 60RCL, 48RCL, and 38RCL generators combine high performance, advanced technology, and user-friendly features. They are reliable solutions for anyone looking to safeguard their power needs, ensuring peace of mind when it matters most.