Chapter 1 – Introduction
Theory of Operation
This manual will refer to two types of SCADA communications topologies, Peer to Peer (P2P) and Modbus.
The Peer to Peer topology consists of one “Master” and one “Slave” RTU. Analog and digital I/O is communicated between the Master and Slave.
The Modbus topology consists of one Modbus Master, and as many as 255 Modbus slaves. The Modbus master is responsible for requesting data from a respective Modbus slave.
The ‘RT’ series RTU’s have several unique functions and features and has been designed to replicate a wired sensor system. Transmission distances of up to 40 miles (64 km), (depending on the radio type and with modified antennas), user programmable sample/polling rates from 10 samples/sec to one sample every 20 seconds, programmable transmission retries, user programmable “full scale” engineering units allow users to enter full scale for a respective sensor, just to name a few.
The hardware architecture for RT series RTU’s are identical. Number of analog or digital I/O depends on the type of RTU. Each respective RTU has
Other features include:
An enhanced monitoring and configuration windows based program, allows you to configure each controller as well as monitor data.
Manual Documentation Number: | 1 |
B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph
Your system may consist of two RT type wireless analog bridges or RTU. In Peer to Peer mode, one controller must be programmed as the master and the other as the slave. It is critical that your system be programmed properly. Confirm your system configuration before using your system.
All configuration parameters may be retrieved by connecting to the respective device’s serial configuration port. The wireless type and other parameters may be adjusted or viewed.
For Peer-to-Peer mode, check and confirm the following:
___ Your system consists of one MASTER and one SLAVE. Do not allow two masters or two slaves to communicate with each other. The devices may communicate but a systems failure will occur.
___ Make sure the system ID’s and
WARNING:
ID numbers for the Master and Slave must match and must not be repeated with any other Master/Slave pairs with the same
___ Make sure both Master and Slave have an antenna attached and installed correctly.
___ Make sure that the input power supply does NOT exceed 28 Vdc.
___ Make sure that the input power supply does NOT fall below 8.5 Vdc.
___ When power is applied to both the master and slave both units will communicate with each other.
For Modbus Slave RTU mode, check and confirm the following:
___ Your system does not consist of two RT RTU/devices with the same Slave ID numbers.
___ Each RTU/device has the same Radio ID and
2Manual Documentation Number: