B&B Electronics RT12-2222-ZP-12, RT12-0044-ZP-12 manual RT12-4444-9T-W20 Front Panel Identification

Page 8

Note: This section assumes that your computer is equipped with a serial port and you have installed the RT series configuration software.

To Connect to a Controller:

1)Install the configuration software (setup.exe).

2)Apply Power to the controller. The heartbeat/sanity LED will begin to FLASH.

3)Connect the programming cable to your PC’s serial Port.

4)Launch the “Configuration” software.

5)You must select a communications port. Select “Comm”, “Serial” then the desired serial port.

6)The “Connect” box will be Red.

7)Press the “Connect” Button. The “Asserting” check box will become checked.

8)If the software successfully connects to the controller,

9)The “Connect” check box will become checked and the “Connect” button will turn Green.

10)The software will begin retrieving configuration data from the controller you are connected to. If all data boxes are not filled in refer back to step #6 in this section.

11)The software will indicate the type of device, Master or Slave.

12)For further programming features see, “Configuration/Programming Software Setup.”

Manual Documentation Number: RT-12 series-4006m

9

B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104www.bb-elec.comB&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445www.bb-europe.com

Chapter 2 – System Identification

RT12-4444-9T-W20 – Front Panel Identification

All analog voltage inputs and outputs are 12-bit, 0-5 Vdc. All digital inputs are from 0 to 12 Vdc. Digital inputs must fall to 0 Vdc as a LOW. Digital outputs are Open Drain.

Connection Screw Terminal Description

PIN NAME DESCRIPTION

1AO 1 Analog Output-1

2AO 2 Analog Output-2

3AO 3 Analog Output-3

4AO 4 Analog Output-4

5

DO 1

Digital Output-1

6

DO 1

Digital Output-2

7

DO 1

Digital Output-3

8

DO 1

Digital Output-4

9

GND

(-) Power Input. Ground.

10

PWR

(+) Power Input. 10-28 Vdc.

11

AI 1

Analog Input-1

12

AI 2

Analog Input-2

13

AI 3

Analog Input-3

14

AI 4

Analog Input-4

15

DI 1

Digital Input-1

16

DI 2

Digital Input-2

17

DI 3

Digital Input-3

18

DI 4

Digital Input-4

19

BAT

(+) Battery I/O. 10.5-28 Vdc.

20

GND

(-) Battery.

10

Manual Documentation Number: RT-12 series-4006m

B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104www.bb-elec.comB&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445www.bb-europe.com

Image 8
Contents Wireless Modbus I/O Modules Wireless I/O Modules from B&B Electronics Table of Contents For Modbus Slave RTU mode, check and confirm the following Theory of OperationFor Peer-to-Peer mode, check and confirm the following Modbus Overview RT12-4444 Modbus Map Modbus Functions SupportedModbus Register Maps RT12-2222 Modbus Map Peer to Peer OverviewTo Connect to a Controller RT12-4444-9T-W20 Front Panel IdentificationConnection Screw Terminal Description Power 10.5~28 Vdc Data Activity LED IndicatorsLink/Sanity LED Indicators Serial RS-232 InterfaceRT12-4444-9T-W20 External Battery Back-up RT12-2222-ZP-S12 Front Panel IdentificationConnection Screw Terminals Description RT12-2222-ZP-S12 External Battery Back-up RT12-0044-ZP-S12 Front Panel IdentificationPower 10.5~28 Vdc Typical Application Peer-to-Peer RT12-0044-ZP-S12 External Battery Back-upHardware Set-up Typical Application Peer-to-Peer Typical Application Modbus Typical Application Well Monitor and Control Peer-to-Peer Typical Application Well Monitor and Control ModbusPin# Connection color Configuration Cable DescriptionTypical Application 4-20 mA to Voltage Conversion Configuration/Monitoring Software System Map Configuration/Monitoring Software MainController Configuration Current Controller SettingsManual Documentation Number RT-12 series-4006m Connecting / Disconnecting Master, Slave, Modbus, Peer-to-PeerModbus Configuration Digital Input TypesRTU Alarms Input Voltage Alarm Limits Analog Outputs Resting VoltageManual Documentation Number RT-12 series-4006m Updating/Sending Configuration to RTU Third Party Communications Protocol SupportStatus Bar Digital Outputs