B&B Electronics RT12-0044-ZP-12, RT12-4444-9T-W20, RT12-2222-ZP-12 manual Power 10.5~28 Vdc

Page 13

Power: 10.5~28 Vdc

Most DC power supplies rated from 10.5 to 28 Vdc @ 200 mA, will work with the RT12-0044-ZP-S12. Do not use a power supply rated less than 200 mA, doing so may cause the RT12-0044-ZP-S12 to continuously reset. Make sure that the power supply voltage is maintained between the programmable HIGH and LOW supply voltage limits or an alarm may occur. If a rechargeable battery is used or if you are supplying voltage to a sensor using the same power used to power the RT12-0044-ZP-S12, then the input voltage will need to be adjusted to the proper voltage to maintain respective equipment. Never exceed 28 Vdc damage, overheating to the controller will occur causing the system to malfunction.

Data Activity LED Indicators

The RT12-0044-ZP-S12 RTU is equipment with three LED indicators. The RED/GREEN pair labeled “RX” and ”TX”, indicate data transmit and data received. The RED LED will blink when data is being transmitted The GREEN LED will blink any time data is received.

Link/Sanity LED Indicators

The yellow LED indicator is locate internally and indicates proper system operation. The second yellow LED indicator, labeled “Error”, will flash any thing an alarm is program and the respective alarm is active. The Status LED indicator may be seen through a small hole on the top of enclosure.

Serial RS-232 Interface

Used to configure the RTU. See “Software Setup”.

Manual Documentation Number: RT-12 series-4006m

19

B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104www.bb-elec.comB&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445www.bb-europe.com

The RT12-0044-ZP-S12 has two rows of 6, screw type, connections. Using a common type screwdriver, loosen the respective terminal screw, insert the respective wire and tighten.

The front panel is stenciled with each Connection number. Listed below are the respective Connection numbers and Connection description.

Connection Screw Terminals Description

Pin 1: “Batt” (+) Battery Charge During Normal Main Power Input. Battery Backup during Main Power Fails

Pin 2: “GND” (-) Power and Battery Ground

Pin 3: “DO 4” (+) Digital Output 4. Open Drain, Active Low, Output

Pin 4: “PWR” VIN(+) Main Supply 10.5 to 28.0 Vdc, Must be > 13.0 to Charge External Battery. Do Not Exceed 28 Vdc

Pin 5: “GND” (-) Main Supply GROUND

Pin 6: “DI 4” (+) Digital Input - 4, 0-12 Vdc

Pin 7: “DO 3” (+) Digital Output - 3, Open Drain, Active Low, Output

Pin 8: “DO 2” (+) Digital Output - 2, Open Drain, Active Low, Output

Pin 9: “DO 1” (+) Digital Output - 1, Open Drain, Active Low, Output

Pin 10: “DI 3” (+) Digital Input - 3, 0-12 Vdc

Pin 11: “DI 2” (+) Digital Input - 2, 0-12 Vdc

Pin 12: “DI 1” (+) Digital Input - 1, 0-12 Vdc

20

Manual Documentation Number: RT-12 series-4006m

B&B Electronics Mfg Co Inc – 707 Dayton Rd - PO Box 1040 - Ottawa IL 61350 - Ph 815-433-5100 - Fax 815-433-5104www.bb-elec.comB&B Electronics – Westlink Commercial Park – Oranmore, Galway, Ireland – Ph +353 91-792444 – Fax +353 91-792445www.bb-europe.com

Image 13
Contents Wireless Modbus I/O Modules Wireless I/O Modules from B&B Electronics Table of Contents For Peer-to-Peer mode, check and confirm the following Theory of OperationFor Modbus Slave RTU mode, check and confirm the following Modbus Overview Modbus Register Maps Modbus Functions SupportedRT12-4444 Modbus Map Peer to Peer Overview RT12-2222 Modbus MapConnection Screw Terminal Description RT12-4444-9T-W20 Front Panel IdentificationTo Connect to a Controller Data Activity LED Indicators Power 10.5~28 VdcLink/Sanity LED Indicators Serial RS-232 InterfaceRT12-2222-ZP-S12 Front Panel Identification RT12-4444-9T-W20 External Battery Back-upConnection Screw Terminals Description RT12-0044-ZP-S12 Front Panel Identification RT12-2222-ZP-S12 External Battery Back-upPower 10.5~28 Vdc Hardware Set-up RT12-0044-ZP-S12 External Battery Back-upTypical Application Peer-to-Peer Typical Application Peer-to-Peer Typical Application Modbus Typical Application Well Monitor and Control Modbus Typical Application Well Monitor and Control Peer-to-PeerTypical Application 4-20 mA to Voltage Conversion Configuration Cable DescriptionPin# Connection color Configuration/Monitoring Software Main Configuration/Monitoring Software System MapCurrent Controller Settings Controller ConfigurationManual Documentation Number RT-12 series-4006m Master, Slave, Modbus, Peer-to-Peer Connecting / DisconnectingDigital Input Types Modbus ConfigurationRTU Alarms Analog Outputs Resting Voltage Input Voltage Alarm LimitsManual Documentation Number RT-12 series-4006m Third Party Communications Protocol Support Updating/Sending Configuration to RTUDigital Outputs Status Bar