Battery Features (continued)
Battery Replacement Procedure
Pure Sine Wave |
Intelligent |
Critical Load Control |
MAX® Home |
Cinema UPS |
1.Remove the right side front panel using
2.Remove the two retaining screws of the cable protection cover then remove the cover.
3. Disconnect the black and red cable. |
6. Slide a new battery pack into the unit. |
Assemble the screws, cover, cable and front |
panel in the reverse sequence of above steps. |
Battery pullout tab handle
4. Remove the four retaining screws. | 5. Pull the battery pack out from the unit. |
7. Recharge the unit for |
the UPS performs expected runtime. |
Diagnostics
Power | Wiring | AVR LED | Using | Circuit | Audible | Condition |
On LED | Fault LED |
| Battery LED | Breaker | Alarm |
|
|
|
|
|
|
|
|
On | Off | Off | Off | Set | Off | Normal |
|
|
|
|
|
|
|
On | Off | Slow Flash | Off | Set | Off | AVR- Max. boost 13% of input voltage for output regulation while input voltage is |
|
|
|
|
|
| from 8% to 15% under nominal. |
|
|
|
|
|
|
|
On | Off | Rapid Flash | Off | Set | Off | AVR- Max. boost 26% of input voltage for output regulation while input voltage is |
|
|
|
|
|
| from 15% to 26% under nominal. |
|
|
|
|
|
|
|
On | Off | On | Off | Set | Off | AVR- Max. buck 15% of input voltage for output regulation while input voltage is |
|
|
|
|
|
| from 8% to 26% over nominal. |
|
|
|
|
|
|
|
Off | Off | Off | On | Set | Two Beeps | Utility Failure- The UPS is providing battery power to the connected equipment. |
|
|
|
|
|
|
|
Off | Off | Off | On | Set | Rapid Beeps | Utility Failure- The UPS is providing battery power. Rapid beeps indicate the battery |
|
|
|
|
|
| will run out of charge within a few minutes. |
|
|
|
|
|
|
|
On/Off | Off | On/Off/Flash | On/Off | Set | Long Beep | Overload- Turn the UPS off and unplug at least one piece of equipment from the UPS. |
|
|
|
|
|
| Wait 5 seconds, reset the circuit breaker and restart the UPS. |
|
|
|
|
|
|
|
Off | Off | Off | On | Up | Long Beep | Overload- Turn the UPS off and unplug at least one piece of equipment from the UPS. |
|
|
|
|
|
| Wait 5 seconds, reset the circuit breaker and restart the UPS. |
|
|
|
|
|
|
|
On | Off | On/Off/Flash | Off | Set | None | Weak Battery- Recharge the battery for at least 8 hours. If Check Battery is illuminat- |
|
|
|
|
|
| ed, contact Panamax for battery replacement information. |
|
|
|
|
|
|
|
Off | Off | Off | Off | Set | Off | Surge Protection Malfunction- Power surge has damaged the unit. Please contact |
|
|
|
|
|
| Panamax. |
|
|
|
|
|
|
|
On/Off | On | On/Off/Flash | On/Off | Set/Up | None | Electrical Wiring Fault- Indicates wiring problems such as a bad ground, missed |
|
|
|
|
|
| ground or reversed wiring within the AC outlet. User is advised to disconnect all |
|
|
|
|
|
| electrical equipment from the outlet and have the outlet checked by an electrician. |
|
|
|
|
|
|
|